Compliance record
Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.
| Violation | Type | Status | Period |
|---|---|---|---|
| MCL | Health-based | Resolved | 2000-08-01 → 2000-08-31 |
| MCL | Health-based | Resolved | 2000-08-01 → 2000-08-31 |
| MCL | Health-based | Resolved | 2000-08-01 → 2000-08-31 |
| MCL | Health-based | Resolved | 2000-08-01 → 2000-08-31 |
| MCL | Health-based | Resolved | 2000-08-01 → 2000-08-31 |
| MCL | Health-based | Resolved | 2000-08-01 → 2000-08-31 |
| MCL | Health-based | Resolved | 1996-03-01 → 1996-03-31 |
| MCL | Health-based | Resolved | 1996-03-01 → 1996-03-31 |
| MCL | Health-based | Resolved | 1996-03-01 → 1996-03-31 |
| RPT | Monitoring | Resolved | 2025-07-02 |
PFAS detected
Other contaminants detected
| Contaminant | Level vs EPA limit | Detection rate | Source | Period |
|---|---|---|---|---|
| TTHM | 52.2 µg/L 65% of the EPA limit 80 µg/L | 153/159 | SYR4 | 2012–2019 |
| Nitrate | 895 µg/L 9% of the EPA limit 10000 µg/L | 130/268 | SYR4 | 2012–2019 |
| Chloroform | 13 µg/L No EPA limit set | 116/140 | SYR4 | 2012–2019 |
| Dibromochloromethane | 19 µg/L No EPA limit set | 115/140 | SYR4 | 2012–2019 |
| Bromodichloromethane | 17 µg/L No EPA limit set | 114/140 | SYR4 | 2012–2019 |
| Bromoform | 10 µg/L No EPA limit set | 98/140 | SYR4 | 2012–2019 |
| Total Haloacetic Acids (HAA5) | 17.4 µg/L 29% of the EPA limit 60 µg/L | 96/156 | SYR4 | 2012–2019 |
| Dichloroacetic Acid | 12 µg/L No EPA limit set | 80/120 | SYR4 | 2015–2019 |
| Dibromoacetic Acid | 7.5 µg/L No EPA limit set | 77/120 | SYR4 | 2015–2019 |
| Chlorite | 350 µg/L 35% of the EPA limit 1000 µg/L | 71/138 | SYR4 | 2015–2019 |
| Nitrate-Nitrite | 895 µg/L 9% of the EPA limit 10000 µg/L | 64/132 | SYR4 | 2012–2019 |
| Fluoride | 1900 µg/L 48% of the EPA limit 4000 µg/L | 49/51 | SYR4 | 2012–2019 |
| Barium | 231 µg/L 12% of the EPA limit 2000 µg/L | 48/48 | SYR4 | 2012–2019 |
| Lead | 0.0020 mg/L 13% of the EPA limit 0.0150 mg/L | 34/34 | LCR | 2025 |
| Combined Radium (-226 And -228) | 5.8 pCi/L 116% of the EPA limit, in the worst sample — 5 pCi/L | 30/30 | SYR4 | 2012–2019 |
| Lithium | 27.6 µg/L No EPA limit set | 26/26 | UCMR-5 | 2025 |
| Gross Beta Particle Activity | 13.1 pCi/L No EPA limit set | 22/22 | SYR4 | 2012–2019 |
| Gross Alpha, Excl. Radon And U | 8.9 pCi/L 59% of the EPA limit 15 pCi/L | 20/22 | SYR4 | 2012–2019 |
| Trichloroacetic Acid | 4.3 µg/L No EPA limit set | 17/120 | SYR4 | 2015–2019 |
| Combined Uranium | 13.9 µg/L 46% of the EPA limit 30 µg/L | 11/22 | SYR4 | 2012–2019 |
| Selenium | 3 µg/L 6% of the EPA limit 50 µg/L | 10/48 | SYR4 | 2012–2019 |
| Arsenic | 2 µg/L 20% of the EPA limit 10 µg/L | 4/48 | SYR4 | 2012–2019 |
| Di(2-ethylhexyl) Adipate | 11 µg/L 2.8% of the EPA limit 400 µg/L | 4/100 | SYR4 | 2012–2019 |
| Monobromoacetic Acid | 1.2 µg/L No EPA limit set | 4/120 | SYR4 | 2015–2019 |
| Chromium | 2.6 µg/L 2.6% of the EPA limit 100 µg/L | 1/48 | SYR4 | 2012–2019 |
| Di(2-ethylhexyl) Phthalate | 4.6 µg/L 77% of the EPA limit 6 µg/L | 1/99 | SYR4 | 2012–2019 |
| Nitrite | 57 µg/L 5.7% of the EPA limit 1000 µg/L | 1/134 | SYR4 | 2012–2019 |
79 contaminants tested, none detected
Utility contact
Frequently asked questions about Parker Wsd
Is Parker Wsd tap water safe to drink?
EPA monitoring detected 32 contaminants in Parker Wsd's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.
What contaminants were detected in Parker Wsd's water?
EPA monitoring detected TTHM, Nitrate, Chloroform, Dibromochloromethane, Bromodichloromethane, and others. The full list with the level and data source for each is above.
How many people does Parker Wsd serve?
Parker Wsd reports serving 75,949 people in Colorado, per its EPA record.
Has Parker Wsd had any water quality violations?
The EPA has 465 violations on file for Parker Wsd, of which 9 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.
Where does this data come from?
Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.