← Louisiana

Tap water quality report

Rayville, LA

EPA monitoring detected 31 contaminants across the 4 water suppliers serving Rayville. A detection doesn't automatically mean the water is unsafe — see the level at the main supplier for each below, with its EPA source and period.

4
water suppliers
8,547
people served
31
contaminants found

What was found in Rayville's water

The level at the city's main supplier, the highest level anywhere in the city, the EPA limit for each, and where every figure comes from.

ContaminantLevel vs EPA limitSuppliersSource
Copper
600 µg/L 46%
of the EPA limit 1300 µg/L
Main supplier: TOWN OF RAYVILLE WATER SYSTEM · 4,842 people · 2019
Highest in the city: 1675 µg/L — BCC DETENTION CENTER WS · 150 people · 2019
4/4 SYR4
Nitrate-Nitrite
1000 µg/L 10%
of the EPA limit 10000 µg/L
Main supplier: TOWN OF RAYVILLE WATER SYSTEM · 4,842 people · 2019
Highest in the city: 1650 µg/L — BCC DETENTION CENTER WS · 150 people · 2019
4/4 SYR4
Fluoride
238 µg/L 5.9%
of the EPA limit 4000 µg/L
Main supplier: TOWN OF RAYVILLE WATER SYSTEM · 4,842 people · 2019
Highest in the city: 307.5 µg/L — PALMETTO ADDICTION RECOVERY · 45 people · 2019
4/4 SYR4
Barium
173 µg/L 8.6%
of the EPA limit 2000 µg/L
Main supplier: TOWN OF RAYVILLE WATER SYSTEM · 4,842 people · 2019
Highest in the city: 210 µg/L — BCC DETENTION CENTER WS · 150 people · 2019
4/4 SYR4
TTHM
161.05 µg/L 201%
of the EPA limit, at the 95th percentile of samples — 80 µg/L
Main supplier: TOWN OF RAYVILLE WATER SYSTEM · 4,842 people · 2019
4/4 SYR4
Chloroform
110.94 µg/L
No EPA limit set
Main supplier: TOWN OF RAYVILLE WATER SYSTEM · 4,842 people · 2019
4/4 SYR4
Total Haloacetic Acids (HAA5)
84.94 µg/L 142%
of the EPA limit, at the 95th percentile of samples — 60 µg/L
Main supplier: TOWN OF RAYVILLE WATER SYSTEM · 4,842 people · 2019
4/4 SYR4
Bromoform
10.431 µg/L
No EPA limit set
Main supplier: TOWN OF RAYVILLE WATER SYSTEM · 4,842 people · 2019
Highest in the city: 56.399 µg/L — PALMETTO ADDICTION RECOVERY · 45 people · 2019
4/4 SYR4
Bromodichloromethane
46.725 µg/L
No EPA limit set
Main supplier: TOWN OF RAYVILLE WATER SYSTEM · 4,842 people · 2019
4/4 SYR4
Trichloroacetic Acid
46.71 µg/L
No EPA limit set
Main supplier: TOWN OF RAYVILLE WATER SYSTEM · 4,842 people · 2019
4/4 SYR4
Lead
3.8 µg/L 25%
of the EPA limit 15 µg/L
Main supplier: TOWN OF RAYVILLE WATER SYSTEM · 4,842 people · 2019
Highest in the city: 45.8 µg/L — RIVER ROAD WATER SYSTEM · 3,510 people · 2019
4/4 SYR4
Dichloroacetic Acid
27.88 µg/L
No EPA limit set
Main supplier: TOWN OF RAYVILLE WATER SYSTEM · 4,842 people · 2019
Highest in the city: 30.33 µg/L — RIVER ROAD WATER SYSTEM · 3,510 people · 2019
4/4 SYR4
Dibromochloromethane
20.06 µg/L
No EPA limit set
Main supplier: TOWN OF RAYVILLE WATER SYSTEM · 4,842 people · 2019
Highest in the city: 29.85 µg/L — RIVER ROAD WATER SYSTEM · 3,510 people · 2019
4/4 SYR4
Monochloroacetic Acid
26.96 µg/L
No EPA limit set
Main supplier: TOWN OF RAYVILLE WATER SYSTEM · 4,842 people · 2019
2/4 SYR4
Monobromoacetic Acid
1.92 µg/L
No EPA limit set
Main supplier: TOWN OF RAYVILLE WATER SYSTEM · 4,842 people · 2019
Highest in the city: 18.52 µg/L — RIVER ROAD WATER SYSTEM · 3,510 people · 2019
3/4 SYR4
Arsenic
5.3 µg/L 53%
of the EPA limit 10 µg/L
Main supplier: TOWN OF RAYVILLE WATER SYSTEM · 4,842 people · 2019
Highest in the city: 15 µg/L — PALMETTO ADDICTION RECOVERY · 45 people · 2019
4/4 SYR4
Dibromoacetic Acid
5 µg/L
No EPA limit set
Main supplier: TOWN OF RAYVILLE WATER SYSTEM · 4,842 people · 2019
Highest in the city: 10.622 µg/L — RIVER ROAD WATER SYSTEM · 3,510 people · 2019
4/4 SYR4
Gross Alpha, Excl. Radon And U
8 pCi/L 53%
of the EPA limit 15 pCi/L
Main supplier: TOWN OF RAYVILLE WATER SYSTEM · 4,842 people · 2016
1/4 SYR4
Gross Beta Particle Activity
5.505 pCi/L
No EPA limit set
Main supplier: TOWN OF RAYVILLE WATER SYSTEM · 4,842 people · 2019
Highest in the city: 6.495 pCi/L — BCC DETENTION CENTER WS · 150 people · 2019
4/4 SYR4
Cyanide
5.7 µg/L 2.9%
of the EPA limit 200 µg/L
Highest in the city: RIVER ROAD WATER SYSTEM · 3,510 people · 2018
1/4 SYR4
Combined Radium (-226 And -228)
0.9000 pCi/L 18%
of the EPA limit 5 pCi/L
Main supplier: TOWN OF RAYVILLE WATER SYSTEM · 4,842 people · 2019
Highest in the city: 2.045 pCi/L — RIVER ROAD WATER SYSTEM · 3,510 people · 2018
4/4 SYR4
Combined Uranium
1.4075 µg/L 4.7%
of the EPA limit 30 µg/L
Main supplier: TOWN OF RAYVILLE WATER SYSTEM · 4,842 people · 2016
2/4 SYR4
Selenium
1.257 µg/L 2.5%
of the EPA limit 50 µg/L
Main supplier: TOWN OF RAYVILLE WATER SYSTEM · 4,842 people · 2019
Highest in the city: 1.4 µg/L — RIVER ROAD WATER SYSTEM · 3,510 people · 2018
2/4 SYR4
Dalapon
1.36 µg/L 0.7%
of the EPA limit 200 µg/L
Highest in the city: PALMETTO ADDICTION RECOVERY · 45 people · 2019
1/4 SYR4
Cadmium
1 µg/L 20%
of the EPA limit 5 µg/L
Main supplier: TOWN OF RAYVILLE WATER SYSTEM · 4,842 people · 2019
2/4 SYR4
Di(2-ethylhexyl) Phthalate
0.6630 µg/L 11%
of the EPA limit 6 µg/L
Main supplier: TOWN OF RAYVILLE WATER SYSTEM · 4,842 people · 2019
Highest in the city: 0.8610 µg/L — RIVER ROAD WATER SYSTEM · 3,510 people · 2018
4/4 SYR4
Tetrachloroethylene
0.7000 µg/L 14%
of the EPA limit 5 µg/L
Main supplier: TOWN OF RAYVILLE WATER SYSTEM · 4,842 people · 2019
1/4 SYR4
Hexachlorobenzene
0.1900 µg/L 19%
of the EPA limit 1 µg/L
Main supplier: TOWN OF RAYVILLE WATER SYSTEM · 4,842 people · 2019
1/4 SYR4
Picloram
0.0980 µg/L 0%
of the EPA limit 500 µg/L
Highest in the city: BCC DETENTION CENTER WS · 150 people · 2019
1/4 SYR4
PFHXS
0.0034 µg/L
No EPA limit set
Main supplier: TOWN OF RAYVILLE WATER SYSTEM · 4,842 people · 2024
1/4 UCMR-5
Lead
0.0010 mg/L 6.7%
of the EPA limit 0.0150 mg/L
Main supplier: TOWN OF RAYVILLE WATER SYSTEM · 4,842 people · 2022
Highest in the city: 0.0026 mg/L — RIVER ROAD WATER SYSTEM · 3,510 people · 2025
4/4 LCR
Each bar shows the measured level as a share of the EPA limit: green is well under, amber is close to it, red is over. For lead and copper the limit applies to exactly the 90th-percentile figure shown, so red there means a real exceedance. For everything else the limit applies to a running annual average while the figure is the 95th percentile of the system's samples — over 100% is worth reading, but is not by itself a violation. Formal violations are listed separately. These are the utilities' own EPA-reported results, not a city-wide average. A detection means the lab measured the substance — it isn't the same as exceeding a legal limit. Hover a source tag to see the EPA program and years behind each figure.

Water suppliers serving Rayville

Frequently asked questions about Rayville tap water

Is Rayville tap water safe to drink?

EPA testing detected 31 contaminants in the water serving Rayville. A detection isn't the same as a violation — most detected levels are within federal limits. Check the level and source for each contaminant above, and your utility's annual Consumer Confidence Report for the official compliance status.

How many water suppliers serve Rayville?

4 public water suppliers report drinking-water monitoring for Rayville, Louisiana to the EPA. Each is listed above with its population served.

What contaminants are in Rayville's water?

The contaminants EPA monitoring detected in Rayville include Copper, Nitrate-Nitrite, Fluoride, Barium, TTHM. The full list, with the level at the main supplier and the data source, is in the table above.

Where does this data come from?

Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.