Compliance record
Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.
| Violation | Type | Status | Period |
|---|---|---|---|
| TT | Health-based | Resolved | 2024-10-17 |
| TT | Health-based | Unaddressed | 2023-09-01 |
| TT | Health-based | Unaddressed | 2023-09-01 |
| TT | Health-based | Unaddressed | 2023-09-01 |
| TT | Health-based | Resolved | 2023-09-01 |
| TT | Health-based | Resolved | 2023-09-01 |
| TT | Health-based | Resolved | 2023-09-01 |
| TT | Health-based | Resolved | 2023-09-01 |
| TT | Health-based | Resolved | 2023-09-01 |
| TT | Health-based | Resolved | 2023-09-01 |
Other contaminants detected
| Contaminant | Level vs EPA limit | Detection rate | Source | Period |
|---|---|---|---|---|
| Nitrate-Nitrite | 1650 µg/L 17% of the EPA limit 10000 µg/L
worst single sample: 2000 µg/L | 28/40 | SYR4 | 2012–2019 |
| Copper | 1675 µg/L 129% of the EPA limit, at the 95th percentile of samples — 1300 µg/L
worst single sample: 2200 µg/L | 26/48 | SYR4 | 2014–2019 |
| Fluoride | 197 µg/L 4.9% of the EPA limit 4000 µg/L
worst single sample: 210 µg/L | 14/15 | SYR4 | 2013–2019 |
| Arsenic | 1.225 µg/L 12% of the EPA limit 10 µg/L
worst single sample: 1.5 µg/L | 12/15 | SYR4 | 2013–2019 |
| Lead | 0.00040 mg/L 2.7% of the EPA limit 0.0150 mg/L | 12/12 | LCR | 2025 |
| Dibromochloromethane | 3.95 µg/L No EPA limit set
worst single sample: 4.3 µg/L | 11/14 | SYR4 | 2013–2019 |
| Gross Beta Particle Activity | 6.495 pCi/L No EPA limit set
worst single sample: 6.84 pCi/L | 11/16 | SYR4 | 2013–2019 |
| Lead | 21.5 µg/L 143% of the EPA limit, at the 95th percentile of samples — 15 µg/L
worst single sample: 31 µg/L | 11/48 | SYR4 | 2014–2019 |
| TTHM | 15.26 µg/L 19% of the EPA limit 80 µg/L
worst single sample: 20 µg/L | 11/14 | SYR4 | 2013–2019 |
| Barium | 210 µg/L 11% of the EPA limit 2000 µg/L | 10/15 | SYR4 | 2013–2019 |
| Bromodichloromethane | 4.506 µg/L No EPA limit set
worst single sample: 6.9 µg/L | 10/14 | SYR4 | 2013–2019 |
| Bromoform | 5.5865 µg/L No EPA limit set
worst single sample: 5.69 µg/L | 10/14 | SYR4 | 2013–2019 |
| Chloroform | 6.48 µg/L No EPA limit set
worst single sample: 9 µg/L | 7/14 | SYR4 | 2013–2019 |
| Dibromoacetic Acid | 2.75 µg/L No EPA limit set
worst single sample: 2.8 µg/L | 6/14 | SYR4 | 2013–2019 |
| Total Haloacetic Acids (HAA5) | 2.875 µg/L 4.8% of the EPA limit 60 µg/L
worst single sample: 2.9 µg/L | 6/14 | SYR4 | 2013–2019 |
| Di(2-ethylhexyl) Phthalate | 0.7980 µg/L 13% of the EPA limit 6 µg/L
worst single sample: 0.8200 µg/L | 5/12 | SYR4 | 2013–2019 |
| Combined Radium (-226 And -228) | 0.8343 pCi/L 17% of the EPA limit 5 pCi/L
worst single sample: 0.8870 pCi/L | 3/10 | SYR4 | 2016–2019 |
| Dichloroacetic Acid | 0.3755 µg/L No EPA limit set
worst single sample: 0.3800 µg/L | 2/14 | SYR4 | 2013–2019 |
| Trichloroacetic Acid | 0.7055 µg/L No EPA limit set
worst single sample: 0.7200 µg/L | 2/14 | SYR4 | 2013–2019 |
| Cadmium | 1 µg/L 20% of the EPA limit 5 µg/L | 1/15 | SYR4 | 2013–2019 |
| Monobromoacetic Acid | 0.3300 µg/L No EPA limit set | 1/14 | SYR4 | 2013–2019 |
| Picloram | 0.0980 µg/L 0% of the EPA limit 500 µg/L | 1/15 | SYR4 | 2013–2019 |
60 contaminants tested, none detected
Utility contact
Frequently asked questions about Bcc Detention Center Ws
Is Bcc Detention Center Ws tap water safe to drink?
EPA monitoring detected 22 contaminants in Bcc Detention Center Ws's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.
What contaminants were detected in Bcc Detention Center Ws's water?
EPA monitoring detected Nitrate-Nitrite, Copper, Fluoride, Arsenic, Lead, and others. The full list with the level and data source for each is above.
How many people does Bcc Detention Center Ws serve?
Bcc Detention Center Ws reports serving 150 people in Louisiana, per its EPA record.
Has Bcc Detention Center Ws had any water quality violations?
The EPA has 202 violations on file for Bcc Detention Center Ws, of which 56 are health-based (a contaminant limit or required treatment was breached) and 15 remain open. The rest are monitoring or reporting failures.
Where does this data come from?
Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.