← West Virginia

Tap water quality report

Beverly Town of

EPA monitoring tested this supplier for 76 contaminants and detected 23. A detection doesn't automatically mean the water is unsafe — the level and EPA source for each is below.

76
contaminants tested
23
detected
2,268
people served
0
health-based violations
Water source
Surface water
Ownership
Local government
Counties served
Randolph

Compliance record

Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.

0
health-based violations
275
violations on file
2
still open
ViolationTypeStatusPeriod
Other Monitoring Resolved 2023-11-16
Other Monitoring Resolved 2023-11-16
Other Monitoring Resolved 2023-11-15
Other Monitoring Resolved 2023-11-15
Other Monitoring Resolved 2023-11-15
Other Monitoring Resolved 2023-11-15
Other Monitoring Resolved 2023-08-13
Other Monitoring Resolved 2023-08-13
Other Monitoring Resolved 2023-05-14
Other Monitoring Resolved 2023-05-14

Other contaminants detected

Each bar shows the measured level as a share of the EPA limit: green is well under, amber is close to it, red is over. For lead and copper the limit applies to exactly the 90th-percentile figure shown, so red there means a real exceedance. For everything else the limit applies to a running annual average while the figure is the 95th percentile of this system's samples — over 100% is worth reading, but is not by itself a violation. Where a single sample came in higher than that percentile, it is noted under the bar. Formal violations are listed separately.
ContaminantLevel vs EPA limitDetection rateSourcePeriod
Copper
219.55 µg/L 17%
of the EPA limit 1300 µg/L
worst single sample: 661 µg/L
120/120 SYR4 2013–2019
Lead
27.25 µg/L 182%
of the EPA limit, at the 95th percentile of samples — 15 µg/L
worst single sample: 54.4 µg/L
40/120 SYR4 2013–2019
Chloroform
63.32 µg/L
No EPA limit set
worst single sample: 82.3 µg/L
33/33 SYR4 2012–2019
Dichloroacetic Acid
30.94 µg/L
No EPA limit set
worst single sample: 41 µg/L
33/33 SYR4 2012–2019
TTHM
72.72 µg/L 91%
of the EPA limit 80 µg/L
worst single sample: 87.2 µg/L
33/33 SYR4 2012–2019
Total Haloacetic Acids (HAA5)
61.3 µg/L 102%
of the EPA limit, at the 95th percentile of samples — 60 µg/L
worst single sample: 69 µg/L
33/33 SYR4 2012–2019
Trichloroacetic Acid
31.76 µg/L
No EPA limit set
worst single sample: 32.8 µg/L
33/33 SYR4 2012–2019
Bromodichloromethane
6.26 µg/L
No EPA limit set
worst single sample: 9.2 µg/L
31/33 SYR4 2012–2019
Lead
0.00036 mg/L 2.4%
of the EPA limit 0.0150 mg/L
23/23 LCR 2025
Nitrate
950 µg/L 9.5%
of the EPA limit 10000 µg/L
18/22 SYR4 2012–2019
Fluoride
1030 µg/L 26%
of the EPA limit 4000 µg/L
worst single sample: 1120 µg/L
11/12 SYR4 2012–2019
Barium
34.44 µg/L 1.7%
of the EPA limit 2000 µg/L
worst single sample: 36 µg/L
9/9 SYR4 2012–2019
Monochloroacetic Acid
2.4755 µg/L
No EPA limit set
worst single sample: 2.57 µg/L
8/33 SYR4 2012–2019
Dibromochloromethane
1.025 µg/L
No EPA limit set
worst single sample: 1.1 µg/L
7/33 SYR4 2012–2019
Dibromoacetic Acid
0.9700 µg/L
No EPA limit set
worst single sample: 1 µg/L
3/33 SYR4 2012–2019
Cadmium
0.3300 µg/L 6.6%
of the EPA limit 5 µg/L
1/9 SYR4 2012–2019
Chromium
1 µg/L 1%
of the EPA limit 100 µg/L
1/9 SYR4 2012–2019
Di(2-ethylhexyl) Adipate
0.7070 µg/L 0.2%
of the EPA limit 400 µg/L
1/4 SYR4 2012–2019
Gross Alpha, Excl. Radon And U
0.4960 pCi/L 3.3%
of the EPA limit 15 pCi/L
1/1 SYR4 2019
Monobromoacetic Acid
1 µg/L
No EPA limit set
1/33 SYR4 2012–2019
Nitrate-Nitrite
820 µg/L 8.2%
of the EPA limit 10000 µg/L
1/1 SYR4 2019
Nitrite
210 µg/L 21%
of the EPA limit 1000 µg/L
1/1 SYR4 2019
Xylenes, Total
260 µg/L 2.6%
of the EPA limit 10000 µg/L
1/8 SYR4 2012–2019
53 contaminants tested, none detected
1,1,1-Trichloroethane1,1,2-Trichloroethane1,1-Dichloroethylene1,2,4-Trichlorobenzene1,2-DIBROMO-3-CHLOROPROPANE1,2-Dichloroethane1,2-Dichloropropane2,4,5-TP2,4-DAntimony, TotalArsenicAtrazineBhc-GammaBenzeneBenzo(A)PyreneBeryllium, TotalBromoformChlorobenzeneCyanideCarbofuranCarbon TetrachlorideChlordaneDichloromethaneDalaponDi(2-ethylhexyl) PhthalateDinosebEthylene DibromideEndrinEthylbenzeneHexachlorobenzeneHeptachlorHeptachlor EpoxideHexachlorocyclopentadieneLassoMercuryMethoxychlorOxamylPentachlorophenolPicloramSeleniumSimazineStyreneTetrachloroethyleneThallium, TotalTolueneTotal Polychlorinated Biphenyls (PCB)ToxapheneTrichloroethyleneVinyl Chloridecis-1,2-DichloroethyleneO-DichlorobenzeneP-Dichlorobenzenetrans-1,2-Dichloroethylene

Utility contact

Contact
BURNS, JOHN
Phone
304-636-5360
Email
beverlytownof@yahoo.com

Frequently asked questions about Beverly Town of

Is Beverly Town of tap water safe to drink?

EPA monitoring detected 23 contaminants in Beverly Town of's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.

What contaminants were detected in Beverly Town of's water?

EPA monitoring detected Copper, Lead, Chloroform, Dichloroacetic Acid, TTHM, and others. The full list with the level and data source for each is above.

How many people does Beverly Town of serve?

Beverly Town of reports serving 2,268 people in West Virginia, per its EPA record.

Has Beverly Town of had any water quality violations?

The EPA has 275 violations on file for Beverly Town of, of which 0 are health-based (a contaminant limit or required treatment was breached) and 2 remain open. The rest are monitoring or reporting failures.

Where does this data come from?

Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.