← Texas

Tap water quality report

West Cedar Creek Mud

EPA monitoring tested this supplier for 107 contaminants and detected 27. A detection doesn't automatically mean the water is unsafe — the level and EPA source for each is below.

107
contaminants tested
27
detected
24,414
people served
29
health-based violations
Water source
Surface water
Ownership
Local government
Counties served
Henderson

Compliance record

Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.

29
health-based violations
80
violations on file
1
still open
ViolationTypeStatusPeriod
TT Health-based Resolved 2011-09-01 → 2011-09-30
TT Health-based Resolved 2011-09-01 → 2011-09-30
TT Health-based Resolved 2011-09-01 → 2011-09-30
TT Health-based Resolved 2011-09-01 → 2011-09-30
TT Health-based Resolved 2011-01-01 → 2011-01-31
MCL Health-based Resolved 2009-10-01 → 2009-10-31
MCL Health-based Resolved 2009-10-01 → 2009-10-31
MCL Health-based Resolved 2009-10-01 → 2009-10-31
MCL Health-based Resolved 2009-10-01 → 2009-10-31
MCL Health-based Resolved 2009-10-01 → 2009-10-31

PFAS detected

PFAS are industrial “forever chemicals”. These are the EPA's latest nationwide test results (2023–2025).
ContaminantMaxDetection ratePeriod
Pfba 0.0161 µg/L 6/8 2024

Other contaminants detected

Each bar shows the measured level as a share of the EPA limit: green is well under, amber is close to it, red is over. For lead and copper the limit applies to exactly the 90th-percentile figure shown, so red there means a real exceedance. For everything else the limit applies to a running annual average while the figure is the 95th percentile of this system's samples — over 100% is worth reading, but is not by itself a violation. Where a single sample came in higher than that percentile, it is noted under the bar. Formal violations are listed separately.
ContaminantLevel vs EPA limitDetection rateSourcePeriod
Bromodichloromethane
17.16 µg/L
No EPA limit set
worst single sample: 22 µg/L
130/130 SYR4 2012–2019
Copper
529.1 µg/L 41%
of the EPA limit 1300 µg/L
worst single sample: 1230 µg/L
130/130 SYR4 2012–2017
Chloroform
49.16 µg/L
No EPA limit set
worst single sample: 143.5 µg/L
130/130 SYR4 2012–2019
Dichloroacetic Acid
30.175 µg/L
No EPA limit set
worst single sample: 42.1 µg/L
114/114 SYR4 2012–2019
TTHM
46.585 µg/L 58%
of the EPA limit 80 µg/L
worst single sample: 84.1 µg/L
114/116 SYR4 2012–2019
Total Haloacetic Acids (HAA5)
44.545 µg/L 74%
of the EPA limit 60 µg/L
worst single sample: 71.4 µg/L
114/114 SYR4 2012–2019
Trichloroacetic Acid
12.54 µg/L
No EPA limit set
worst single sample: 33.9 µg/L
114/114 SYR4 2012–2019
Dibromochloromethane
3.9 µg/L
No EPA limit set
worst single sample: 6.01 µg/L
73/130 SYR4 2012–2019
Lead
18.55 µg/L 124%
of the EPA limit, at the 95th percentile of samples — 15 µg/L
worst single sample: 186 µg/L
71/130 SYR4 2012–2017
Monochloroacetic Acid
4.875 µg/L
No EPA limit set
worst single sample: 6.9 µg/L
66/114 SYR4 2012–2019
Nitrate
422.5 µg/L 4.2%
of the EPA limit 10000 µg/L
worst single sample: 460 µg/L
36/36 SYR4 2012–2019
Monobromoacetic Acid
9.535 µg/L
No EPA limit set
worst single sample: 11.6 µg/L
24/114 SYR4 2012–2019
Dibromoacetic Acid
2.89 µg/L
No EPA limit set
worst single sample: 2.9 µg/L
22/114 SYR4 2012–2019
Fluoride
190.25 µg/L 4.8%
of the EPA limit 4000 µg/L
worst single sample: 200 µg/L
16/16 SYR4 2012–2019
Lead
0.0 mg/L 0%
of the EPA limit 0.0150 mg/L
16/16 LCR 2023
Barium
54.7 µg/L 2.7%
of the EPA limit 2000 µg/L
worst single sample: 56 µg/L
14/14 SYR4 2013–2019
Atrazine
0.2571 µg/L 8.6%
of the EPA limit 3 µg/L
worst single sample: 0.3000 µg/L
12/26 SYR4 2012–2019
Di(2-ethylhexyl) Phthalate
1.303 µg/L 22%
of the EPA limit 6 µg/L
worst single sample: 1.5 µg/L
5/26 SYR4 2012–2019
Simazine
0.1880 µg/L 4.7%
of the EPA limit 4 µg/L
worst single sample: 0.1900 µg/L
5/26 SYR4 2012–2019
Chromium
1.272 µg/L 1.3%
of the EPA limit 100 µg/L
worst single sample: 1.29 µg/L
4/14 SYR4 2013–2019
Arsenic
1.618 µg/L 16%
of the EPA limit 10 µg/L
worst single sample: 1.7 µg/L
3/14 SYR4 2013–2019
Cyanide
93.89 µg/L 47%
of the EPA limit 200 µg/L
worst single sample: 103 µg/L
3/12 SYR4 2014–2019
Antimony, Total
0.2456 µg/L 4.1%
of the EPA limit 6 µg/L
worst single sample: 0.2470 µg/L
2/14 SYR4 2013–2019
Di(2-ethylhexyl) Adipate
0.0416 µg/L 0%
of the EPA limit 400 µg/L
worst single sample: 0.0421 µg/L
2/26 SYR4 2012–2019
Gross Beta Particle Activity
4.19 pCi/L
No EPA limit set
worst single sample: 4.2 pCi/L
2/2 SYR4 2017
Nitrite
6.5 µg/L 0.7%
of the EPA limit 1000 µg/L
1/2 SYR4 2013
80 contaminants tested, none detected
1,1,1-Trichloroethane1,1,2-Trichloroethane1,1-Dichloroethylene1,2,4-Trichlorobenzene1,2-DIBROMO-3-CHLOROPROPANE1,2-Dichloroethane1,2-Dichloropropane11Cl-PF3OUdS2,4,5-TP2,4-D4:2 Fts6:2 Fts8:2 Fts9Cl-PF3ONSAdonaAsbestosBhc-GammaBenzeneBenzo(A)PyreneBeryllium, TotalBromoformChlorobenzeneCadmiumCarbofuranCarbon TetrachlorideChlordaneCombined UraniumDichloromethaneDalaponDinosebEthylene DibromideEndrinEthylbenzeneGross Alpha, Excl. Radon And UHexachlorobenzeneHfpo-DaHeptachlorHeptachlor EpoxideHexachlorocyclopentadieneLassoMercuryMethoxychlorNetfosaaNfdhaNmefosaaOxamylPFBSPfdaPfdoaPfeesaPfhpaPfhpsPfhxaPFHXSPfmbaPfmpaPFNAPFOAPFOSPfpeaPfpesPftaPftrdaPfunaPentachlorophenolPicloramSeleniumStyreneTetrachloroethyleneThallium, TotalTolueneToxapheneTrichloroethyleneVinyl ChlorideXylenes, Totalcis-1,2-DichloroethyleneLithiumO-DichlorobenzeneP-Dichlorobenzenetrans-1,2-Dichloroethylene

Utility contact

Contact
MCKINSEY, MAC
Phone
903-432-3704
Email
austinmac3@embarqmail.com

Frequently asked questions about West Cedar Creek Mud

Is West Cedar Creek Mud tap water safe to drink?

EPA monitoring detected 27 contaminants in West Cedar Creek Mud's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.

What contaminants were detected in West Cedar Creek Mud's water?

EPA monitoring detected Bromodichloromethane, Copper, Chloroform, Dichloroacetic Acid, TTHM, and others. The full list with the level and data source for each is above.

How many people does West Cedar Creek Mud serve?

West Cedar Creek Mud reports serving 24,414 people in Texas, per its EPA record.

Has West Cedar Creek Mud had any water quality violations?

The EPA has 80 violations on file for West Cedar Creek Mud, of which 29 are health-based (a contaminant limit or required treatment was breached) and 1 remain open. The rest are monitoring or reporting failures.

Where does this data come from?

Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.