Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.
| Violation | Type | Status | Period |
|---|---|---|---|
| MR | Monitoring | Resolved | 2021-06-01 → 2021-06-30 |
| MR | Monitoring | Resolved | 2021-06-01 → 2021-06-30 |
| MR | Monitoring | Resolved | 2021-06-01 → 2021-06-30 |
| MR | Monitoring | Resolved | 2021-06-01 → 2021-06-30 |
| MR | Monitoring | Resolved | 2020-12-01 → 2020-12-31 |
| MR | Monitoring | Resolved | 2020-12-01 → 2020-12-31 |
| MR | Monitoring | Resolved | 2020-12-01 → 2020-12-31 |
| MR | Monitoring | Resolved | 2020-12-01 → 2020-12-31 |
| MR | Monitoring | Resolved | 2020-11-01 → 2020-11-30 |
| MR | Monitoring | Resolved | 2020-11-01 → 2020-11-30 |
Other contaminants detected
| Contaminant | Level vs EPA limit | Detection rate | Source | Period |
|---|---|---|---|---|
| Nitrate | 263.5 µg/L 2.6% of the EPA limit 10000 µg/L
worst single sample: 270 µg/L | 34/34 | SYR4 | 2012–2019 |
| Bromodichloromethane | 25.9 µg/L No EPA limit set
worst single sample: 27.2 µg/L | 26/26 | SYR4 | 2012–2019 |
| Chloroform | 45.15 µg/L No EPA limit set
worst single sample: 70.2 µg/L | 26/26 | SYR4 | 2012–2019 |
| Dibromochloromethane | 19.825 µg/L No EPA limit set
worst single sample: 21 µg/L | 26/26 | SYR4 | 2012–2019 |
| Bromoform | 6.885 µg/L No EPA limit set
worst single sample: 8.5 µg/L | 20/26 | SYR4 | 2012–2019 |
| Cyanide | 180.5 µg/L 90% of the EPA limit 200 µg/L
worst single sample: 240 µg/L | 18/24 | SYR4 | 2014–2019 |
| Dichloroacetic Acid | 36.525 µg/L No EPA limit set
worst single sample: 58.2 µg/L | 18/18 | SYR4 | 2012–2019 |
| TTHM | 81.665 µg/L 102% of the EPA limit, at the 95th percentile of samples — 80 µg/L
worst single sample: 103 µg/L | 18/19 | SYR4 | 2012–2019 |
| Total Haloacetic Acids (HAA5) | 60.73 µg/L 101% of the EPA limit, at the 95th percentile of samples — 60 µg/L
worst single sample: 93.2 µg/L | 18/18 | SYR4 | 2012–2019 |
| Trichloroacetic Acid | 21.4 µg/L No EPA limit set
worst single sample: 29.9 µg/L | 18/18 | SYR4 | 2012–2019 |
| Dibromoacetic Acid | 8.08 µg/L No EPA limit set
worst single sample: 8.4 µg/L | 17/18 | SYR4 | 2012–2019 |
| Fluoride | 246.5 µg/L 6.2% of the EPA limit 4000 µg/L
worst single sample: 250 µg/L | 8/8 | SYR4 | 2012–2019 |
| Barium | 139.3 µg/L 7% of the EPA limit 2000 µg/L
worst single sample: 142 µg/L | 7/7 | SYR4 | 2013–2019 |
| Copper | 5.005 µg/L 0.4% of the EPA limit 1300 µg/L
worst single sample: 5.2 µg/L | 4/5 | SYR4 | 2013–2017 |
| Monochloroacetic Acid | 5.71 µg/L No EPA limit set
worst single sample: 6.1 µg/L | 4/18 | SYR4 | 2012–2019 |
| Nitrate-Nitrite | 201 µg/L 2% of the EPA limit 10000 µg/L
worst single sample: 210 µg/L | 4/4 | SYR4 | 2012–2015 |
| Arsenic | 3.045 µg/L 30% of the EPA limit 10 µg/L
worst single sample: 3.1 µg/L | 2/7 | SYR4 | 2013–2019 |
| Combined Radium (-226 And -228) | 1.5 pCi/L 30% of the EPA limit 5 pCi/L | 1/1 | SYR4 | 2017 |
| Gross Beta Particle Activity | 6.1 pCi/L No EPA limit set | 1/1 | SYR4 | 2017 |
| Monobromoacetic Acid | 4 µg/L No EPA limit set | 1/18 | SYR4 | 2012–2019 |
| Selenium | 4.25 µg/L 8.5% of the EPA limit 50 µg/L | 1/7 | SYR4 | 2013–2019 |
57 contaminants tested, none detected
Utility contact
Frequently asked questions about Brown County Wid 1
Is Brown County Wid 1 tap water safe to drink?
EPA monitoring detected 21 contaminants in Brown County Wid 1's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.
What contaminants were detected in Brown County Wid 1's water?
EPA monitoring detected Nitrate, Bromodichloromethane, Chloroform, Dibromochloromethane, Bromoform, and others. The full list with the level and data source for each is above.
How many people does Brown County Wid 1 serve?
Brown County Wid 1 reports serving 0 people in Texas, per its EPA record.
Has Brown County Wid 1 had any water quality violations?
The EPA has 23 violations on file for Brown County Wid 1, of which 0 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.
Where does this data come from?
Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.