Compliance record
Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.
| Violation | Type | Status | Period |
|---|---|---|---|
| TT | Health-based | Resolved | 2026-03-05 |
| TT | Health-based | Resolved | 2026-03-05 |
| MCL | Health-based | Archived | 2026-01-01 → 2026-03-31 |
| TT | Health-based | Archived | 2025-10-01 → 2025-10-31 |
| TT | Health-based | Archived | 2025-10-01 → 2025-10-31 |
| MCL | Health-based | Archived | 2025-10-01 → 2025-12-31 |
| MCL | Health-based | Archived | 2025-10-01 → 2025-12-31 |
| TT | Health-based | Unaddressed | 2025-08-14 |
| TT | Health-based | Unaddressed | 2025-08-14 |
| TT | Health-based | Unaddressed | 2025-08-14 |
Other contaminants detected
| Contaminant | Level vs EPA limit | Detection rate | Source | Period |
|---|---|---|---|---|
| TTHM | 114.36 µg/L 143% of the EPA limit, at the 95th percentile of samples — 80 µg/L
worst single sample: 151 µg/L | 39/39 | SYR4 | 2012–2019 |
| Total Haloacetic Acids (HAA5) | 79.68 µg/L 133% of the EPA limit, at the 95th percentile of samples — 60 µg/L
worst single sample: 108.1 µg/L | 39/39 | SYR4 | 2012–2019 |
| Lead | 0.0 mg/L 0% of the EPA limit 0.0150 mg/L | 12/12 | LCR | 2025 |
| Atrazine | 1.1695 µg/L 39% of the EPA limit 3 µg/L
worst single sample: 1.32 µg/L | 8/34 | SYR4 | 2012–2019 |
| Copper | 109.8 µg/L 8.4% of the EPA limit 1300 µg/L
worst single sample: 142 µg/L | 8/10 | SYR4 | 2016–2019 |
| Nitrate | 1220 µg/L 12% of the EPA limit 10000 µg/L | 6/16 | SYR4 | 2012–2019 |
| Di(2-ethylhexyl) Phthalate | 13.164 µg/L 219% of the EPA limit, at the 95th percentile of samples — 6 µg/L
worst single sample: 13.54 µg/L | 5/34 | SYR4 | 2012–2019 |
| Fluoride | 47.8 µg/L 1.2% of the EPA limit 4000 µg/L
worst single sample: 49 µg/L | 5/8 | SYR4 | 2012–2019 |
| Bromodichloromethane | 3.88 µg/L No EPA limit set
worst single sample: 4 µg/L | 3/3 | SYR4 | 2012–2014 |
| Lead | 17.99 µg/L 120% of the EPA limit, at the 95th percentile of samples — 15 µg/L
worst single sample: 19.5 µg/L | 3/10 | SYR4 | 2016–2019 |
| Arsenic | 5 µg/L 50% of the EPA limit 10 µg/L
worst single sample: 5.2 µg/L | 2/9 | SYR4 | 2012–2019 |
| Barium | 76.465 µg/L 3.8% of the EPA limit 2000 µg/L
worst single sample: 80 µg/L | 2/8 | SYR4 | 2012–2019 |
| Chloroform | 30.095 µg/L No EPA limit set
worst single sample: 30.5 µg/L | 2/3 | SYR4 | 2012–2014 |
| Di(2-ethylhexyl) Adipate | 0.6490 µg/L 0.2% of the EPA limit 400 µg/L
worst single sample: 0.6500 µg/L | 2/34 | SYR4 | 2012–2019 |
| Ethylbenzene | 1.735 µg/L 0.2% of the EPA limit 700 µg/L
worst single sample: 1.8 µg/L | 2/8 | SYR4 | 2012–2019 |
| Xylenes, Total | 3.94 µg/L 0% of the EPA limit 10000 µg/L
worst single sample: 4 µg/L | 2/8 | SYR4 | 2012–2019 |
| Antimony, Total | 0.6000 µg/L 10% of the EPA limit 6 µg/L | 1/8 | SYR4 | 2012–2019 |
| Chromium | 2 µg/L 2% of the EPA limit 100 µg/L | 1/8 | SYR4 | 2012–2019 |
| Gross Alpha, Excl. Radon And U | 0.5150 pCi/L 3.4% of the EPA limit 15 pCi/L | 1/1 | SYR4 | 2017 |
| Selenium | 2.2 µg/L 4.4% of the EPA limit 50 µg/L | 1/8 | SYR4 | 2012–2019 |
| Simazine | 0.1100 µg/L 2.8% of the EPA limit 4 µg/L | 1/34 | SYR4 | 2012–2019 |
52 contaminants tested, none detected
Utility contact
Frequently asked questions about Salt Creek Services, Inc.
Is Salt Creek Services, Inc. tap water safe to drink?
EPA monitoring detected 21 contaminants in Salt Creek Services, Inc.'s water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.
What contaminants were detected in Salt Creek Services, Inc.'s water?
EPA monitoring detected TTHM, Total Haloacetic Acids (HAA5), Lead, Atrazine, Copper, and others. The full list with the level and data source for each is above.
How many people does Salt Creek Services, Inc. serve?
Salt Creek Services, Inc. reports serving 90 people in Indiana, per its EPA record.
Has Salt Creek Services, Inc. had any water quality violations?
The EPA has 381 violations on file for Salt Creek Services, Inc., of which 108 are health-based (a contaminant limit or required treatment was breached) and 7 remain open. The rest are monitoring or reporting failures.
Where does this data come from?
Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.