← Florida

Tap water quality report

Tampa Bay Water -Cypress Creek

EPA monitoring tested this supplier for 71 contaminants and detected 22. A detection doesn't automatically mean the water is unsafe — the level and EPA source for each is below.

71
contaminants tested
22
detected
25
people served
18
health-based violations
Water source
SWP
Ownership
Mixed public/private
Counties served
Pasco

Compliance record

Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.

18
health-based violations
25
violations on file
2
still open
ViolationTypeStatusPeriod
TT Health-based Unaddressed 2025-02-01
MCL Health-based Resolved 1988-03-01 → 1991-02-28
MCL Health-based Resolved 1988-03-01 → 1991-02-28
MCL Health-based Resolved 1988-03-01 → 1991-02-28
MCL Health-based Resolved 1988-03-01 → 1991-02-28
MCL Health-based Resolved 1988-03-01 → 1991-02-28
MCL Health-based Resolved 1987-12-01 → 1990-11-30
MCL Health-based Resolved 1987-12-01 → 1990-11-30
MCL Health-based Resolved 1987-12-01 → 1990-11-30
MCL Health-based Resolved 1987-12-01 → 1990-11-30

Other contaminants detected

Each bar shows the measured level as a share of the EPA limit: green is well under, amber is close to it, red is over. For lead and copper the limit applies to exactly the 90th-percentile figure shown, so red there means a real exceedance. For everything else the limit applies to a running annual average while the figure is the single worst sample on record — over 100% is worth reading, but is not by itself a violation. Formal violations are listed separately.
ContaminantLevel vs EPA limitDetection rateSourcePeriod
Nitrate
480 µg/L 4.8%
of the EPA limit 10000 µg/L
448/460 SYR4 2012–2019
TTHM
34.79 µg/L 43%
of the EPA limit 80 µg/L
207/208 SYR4 2012–2019
Total Haloacetic Acids (HAA5)
29 µg/L 48%
of the EPA limit 60 µg/L
207/208 SYR4 2012–2019
Fluoride
340 µg/L 8.5%
of the EPA limit 4000 µg/L
115/115 SYR4 2012–2019
Copper
60 µg/L 4.6%
of the EPA limit 1300 µg/L
54/219 SYR4 2012–2019
Nitrite
440 µg/L 44%
of the EPA limit 1000 µg/L
47/253 SYR4 2012–2019
Barium
20 µg/L 1%
of the EPA limit 2000 µg/L
46/47 SYR4 2012–2019
Combined Uranium
2.384 µg/L 7.9%
of the EPA limit 30 µg/L
37/56 SYR4 2012–2019
Gross Alpha, Excl. Radon And U
6.1 pCi/L 41%
of the EPA limit 15 pCi/L
28/37 SYR4 2012–2017
Arsenic
5 µg/L 50%
of the EPA limit 10 µg/L
22/57 SYR4 2012–2019
Selenium
4.4 µg/L 8.8%
of the EPA limit 50 µg/L
11/56 SYR4 2012–2019
Lead
4.9 µg/L 33%
of the EPA limit 15 µg/L
10/226 SYR4 2012–2019
Chromium
8.4 µg/L 8.4%
of the EPA limit 100 µg/L
9/58 SYR4 2012–2019
Lead
0.0 mg/L 0%
of the EPA limit 0.0150 mg/L
6/6 LCR 2003
Cyanide
21 µg/L 11%
of the EPA limit 200 µg/L
3/58 SYR4 2012–2019
Antimony, Total
1.1 µg/L 18%
of the EPA limit 6 µg/L
2/63 SYR4 2012–2019
Benzo(A)Pyrene
0.0200 µg/L 10%
of the EPA limit 0.2000 µg/L
1/61 SYR4 2012–2019
Beryllium, Total
0.2000 µg/L 5%
of the EPA limit 4 µg/L
1/57 SYR4 2012–2019
Dalapon
0.3600 µg/L 0.2%
of the EPA limit 200 µg/L
1/57 SYR4 2012–2019
Di(2-ethylhexyl) Adipate
0.2000 µg/L 0.1%
of the EPA limit 400 µg/L
1/61 SYR4 2012–2019
Mercury
0.1000 µg/L 5%
of the EPA limit 2 µg/L
1/58 SYR4 2012–2019
Thallium, Total
0.5000 µg/L 25%
of the EPA limit 2 µg/L
1/53 SYR4 2012–2019
49 contaminants tested, none detected
1,1,1-Trichloroethane1,1,2-Trichloroethane1,1-Dichloroethylene1,2,4-Trichlorobenzene1,2-DIBROMO-3-CHLOROPROPANE1,2-Dichloroethane1,2-Dichloropropane2,4,5-TP2,4-DAsbestosAtrazineBhc-GammaBenzeneChlorobenzeneCadmiumCarbofuranCarbon TetrachlorideChlordaneDichloromethaneDi(2-ethylhexyl) PhthalateDinosebDiquatEthylene DibromideEndothallEndrinEthylbenzeneGlyphosateHexachlorobenzeneHeptachlorHeptachlor EpoxideHexachlorocyclopentadieneLassoMethoxychlorOxamylPentachlorophenolPicloramSimazineStyreneTetrachloroethyleneTolueneTotal Polychlorinated Biphenyls (PCB)ToxapheneTrichloroethyleneVinyl ChlorideXylenes, Totalcis-1,2-DichloroethyleneO-DichlorobenzeneP-Dichlorobenzenetrans-1,2-Dichloroethylene

Utility contact

Contact
ANDREW GREENBAUM
Phone
813-796-2355

Frequently asked questions about Tampa Bay Water -Cypress Creek

Is Tampa Bay Water -Cypress Creek tap water safe to drink?

EPA monitoring detected 22 contaminants in Tampa Bay Water -Cypress Creek's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.

What contaminants were detected in Tampa Bay Water -Cypress Creek's water?

EPA monitoring detected Nitrate, TTHM, Total Haloacetic Acids (HAA5), Fluoride, Copper, and others. The full list with the level and data source for each is above.

How many people does Tampa Bay Water -Cypress Creek serve?

Tampa Bay Water -Cypress Creek reports serving 25 people in Florida, per its EPA record.

Has Tampa Bay Water -Cypress Creek had any water quality violations?

The EPA has 25 violations on file for Tampa Bay Water -Cypress Creek, of which 18 are health-based (a contaminant limit or required treatment was breached) and 2 remain open. The rest are monitoring or reporting failures.

Where does this data come from?

Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.