Compliance record
Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.
| Violation | Type | Status | Period |
|---|---|---|---|
| MCL | Health-based | Resolved | 2008-10-01 → 2008-12-31 |
| MCL | Health-based | Resolved | 2008-07-01 → 2008-09-30 |
| MCL | Health-based | Resolved | 2008-04-01 → 2008-06-30 |
| MCL | Health-based | Resolved | 1993-12-01 → 1993-12-31 |
| MR | Monitoring | Resolved | 2007-10-01 → 2007-12-31 |
| Other | Monitoring | Archived | 1989-12-01 → 1989-12-31 |
PFAS detected
Other contaminants detected
| Contaminant | Level vs EPA limit | Detection rate | Source | Period |
|---|---|---|---|---|
| Arsenic | 15 µg/L 150% of the EPA limit, at the 95th percentile of samples — 10 µg/L
worst single sample: 17 µg/L | 407/620 | SYR4 | 2012–2019 |
| Nitrate | 4520 µg/L 45% of the EPA limit 10000 µg/L | 60/138 | SYR4 | 2012–2019 |
| Lead | 0.0 mg/L 0% of the EPA limit 0.0150 mg/L | 30/30 | LCR | 2025 |
| Barium | 145 µg/L 7.2% of the EPA limit 2000 µg/L
worst single sample: 150 µg/L | 11/20 | SYR4 | 2012–2017 |
| Fluoride | 135 µg/L 3.4% of the EPA limit 4000 µg/L
worst single sample: 150 µg/L | 11/20 | SYR4 | 2012–2017 |
| Nitrate-Nitrite | 3800 µg/L 38% of the EPA limit 10000 µg/L | 3/10 | SYR4 | 2017 |
| Combined Uranium | 3.27055 µg/L 11% of the EPA limit 30 µg/L
worst single sample: 3.278 µg/L | 2/13 | SYR4 | 2012–2017 |
| Toluene | 0.5700 µg/L 0.1% of the EPA limit 1000 µg/L | 1/25 | SYR4 | 2012–2017 |
95 contaminants tested, none detected
Utility contact
Frequently asked questions about Elk Grove Water District
Is Elk Grove Water District tap water safe to drink?
EPA monitoring detected 10 contaminants in Elk Grove Water District's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.
What contaminants were detected in Elk Grove Water District's water?
EPA monitoring detected Arsenic, Nitrate, Lead, Barium, Fluoride, and others. The full list with the level and data source for each is above.
How many people does Elk Grove Water District serve?
Elk Grove Water District reports serving 43,813 people in California, per its EPA record.
Has Elk Grove Water District had any water quality violations?
The EPA has 6 violations on file for Elk Grove Water District, of which 4 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.
Where does this data come from?
Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.