← Texas

Tap water quality report

Ballinger, TX

EPA monitoring detected 32 contaminants across the 1 water supplier serving Ballinger. A detection doesn't automatically mean the water is unsafe — see the highest level found for each below, with its EPA source and period.

1
water supplier
3,583
people served
32
contaminants found

What was found in Ballinger's water

The highest level seen across the city's suppliers, the EPA limit for each, and where the figure comes from.

ContaminantLevel vs EPA limitSuppliersSource
Copper
1500 µg/L 115%
of the EPA limit, in the worst sample — 1300 µg/L
1/1 SYR4
Nitrate
1360 µg/L 14%
of the EPA limit 10000 µg/L
1/1 SYR4
Fluoride
810 µg/L 20%
of the EPA limit 4000 µg/L
1/1 SYR4
Chlorite
800 µg/L 80%
of the EPA limit 1000 µg/L
1/1 SYR4
TTHM
582 µg/L 728%
of the EPA limit, in the worst sample — 80 µg/L
1/1 SYR4
Dibromochloromethane
247 µg/L
No EPA limit set
1/1 SYR4
Cyanide
180 µg/L 90%
of the EPA limit 200 µg/L
1/1 SYR4
Barium
179 µg/L 9%
of the EPA limit 2000 µg/L
1/1 SYR4
Bromoform
161 µg/L
No EPA limit set
1/1 SYR4
Bromodichloromethane
134 µg/L
No EPA limit set
1/1 SYR4
Lithium
83 µg/L
No EPA limit set
1/1 UCMR-5
Total Haloacetic Acids (HAA5)
58.6 µg/L 98%
of the EPA limit 60 µg/L
1/1 SYR4
Chloroform
40.2 µg/L
No EPA limit set
1/1 SYR4
Dichloroacetic Acid
35.3 µg/L
No EPA limit set
1/1 SYR4
Dibromoacetic Acid
33.3 µg/L
No EPA limit set
1/1 SYR4
Trichloroacetic Acid
17.4 µg/L
No EPA limit set
1/1 SYR4
Selenium
10.3 µg/L 21%
of the EPA limit 50 µg/L
1/1 SYR4
Gross Beta Particle Activity
7.6 pCi/L
No EPA limit set
1/1 SYR4
Monochloroacetic Acid
6.1 µg/L
No EPA limit set
1/1 SYR4
Monobromoacetic Acid
4.7 µg/L
No EPA limit set
1/1 SYR4
Lead
4.12 µg/L 27%
of the EPA limit 15 µg/L
1/1 SYR4
Arsenic
4 µg/L 40%
of the EPA limit 10 µg/L
1/1 SYR4
Chromium
3.41 µg/L 3.4%
of the EPA limit 100 µg/L
1/1 SYR4
Combined Uranium
1.4 µg/L 4.7%
of the EPA limit 30 µg/L
1/1 SYR4
Di(2-ethylhexyl) Phthalate
0.6400 µg/L 11%
of the EPA limit 6 µg/L
1/1 SYR4
Thallium, Total
0.6230 µg/L 31%
of the EPA limit 2 µg/L
1/1 SYR4
Atrazine
0.1500 µg/L 5%
of the EPA limit 3 µg/L
1/1 SYR4
Pfba
0.0150 µg/L
No EPA limit set
1/1 UCMR-5
Lead
0.0064 mg/L 43%
of the EPA limit 0.0150 mg/L
1/1 LCR
6:2 Fts
0.0060 µg/L
No EPA limit set
1/1 UCMR-5
PFBS
0.0051 µg/L
No EPA limit set
1/1 UCMR-5
PFHXS
0.0050 µg/L
No EPA limit set
1/1 UCMR-5
Each bar shows the measured level as a share of the EPA limit: green is well under, amber is close to it, red is over. For lead and copper the limit applies to exactly the 90th-percentile figure shown, so red there means a real exceedance. For everything else the limit applies to a running annual average while the figure is the single worst sample on record — over 100% is worth reading, but is not by itself a violation. Formal violations are listed separately. These are the utilities' own EPA-reported results, not a city-wide average. A detection means the lab measured the substance — it isn't the same as exceeding a legal limit. Hover a source tag to see the EPA program and years behind each figure.

Water suppliers serving Ballinger

SupplierPopulation served
CITY OF BALLINGER 3,583

Frequently asked questions about Ballinger tap water

Is Ballinger tap water safe to drink?

EPA testing detected 32 contaminants in the water serving Ballinger. A detection isn't the same as a violation — most detected levels are within federal limits. Check the level and source for each contaminant above, and your utility's annual Consumer Confidence Report for the official compliance status.

How many water suppliers serve Ballinger?

1 public water supplier report drinking-water monitoring for Ballinger, Texas to the EPA. Each is listed above with its population served.

What contaminants are in Ballinger's water?

The contaminants EPA monitoring detected in Ballinger include Copper, Nitrate, Fluoride, Chlorite, TTHM. The full list, with the highest level found and the data source, is in the table above.

Where does this data come from?

Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.