← Greenwood, IN

Tap water quality report

ZIP 46131 — Greenwood, IN

EPA monitoring across the 4 water suppliers serving ZIP 46131 in Greenwood, IN detected 17 contaminants. A detection doesn't automatically mean the water is unsafe — see the highest level found below, with the EPA limit for each.

4
water suppliers
138,873
people served
17
contaminants found

What was found in ZIP 46131

The highest level seen across the suppliers serving this ZIP, the EPA limit for each, and where the figure comes from.

ContaminantLevel vs EPA limitSuppliersSource
Nitrate-Nitrite
2900 µg/L 29%
of the EPA limit 10000 µg/L
4/4 SYR4
Nitrate
2400 µg/L 24%
of the EPA limit 10000 µg/L
4/4 SYR4
Copper
1012 µg/L 78%
of the EPA limit 1300 µg/L
4/4 SYR4
Fluoride
900 µg/L 23%
of the EPA limit 4000 µg/L
4/4 SYR4
Barium
400 µg/L 20%
of the EPA limit 2000 µg/L
4/4 SYR4
TTHM
52 µg/L 65%
of the EPA limit 80 µg/L
4/4 SYR4
Total Haloacetic Acids (HAA5)
31.3 µg/L 52%
of the EPA limit 60 µg/L
4/4 SYR4
Lead
26.6 µg/L 177%
of the EPA limit, in the worst sample — 15 µg/L
4/4 SYR4
Lithium
10 µg/L
No EPA limit set
1/4 UCMR-5
Arsenic
4.5 µg/L 45%
of the EPA limit 10 µg/L
3/4 SYR4
Gross Alpha, Excl. Radon And U
4.3 pCi/L 29%
of the EPA limit 15 pCi/L
3/4 SYR4
Combined Uranium
1.9 µg/L 6.3%
of the EPA limit 30 µg/L
2/4 SYR4
Combined Radium (-226 And -228)
0.4400 pCi/L 8.8%
of the EPA limit 5 pCi/L
1/4 SYR4
Pfpea
0.0082 µg/L
No EPA limit set
2/4 UCMR-5
Pfba
0.0060 µg/L
No EPA limit set
1/4 UCMR-5
Pfhxa
0.0051 µg/L
No EPA limit set
2/4 UCMR-5
Lead
0.0028 mg/L 19%
of the EPA limit 0.0150 mg/L
4/4 LCR
Each bar shows the measured level as a share of the EPA limit: green is well under, amber is close to it, red is over. For lead and copper the limit applies to exactly the 90th-percentile figure shown, so red there means a real exceedance. For everything else the limit applies to a running annual average while the figure is the single worst sample on record — over 100% is worth reading, but is not by itself a violation. Formal violations are listed separately.

Water suppliers serving ZIP 46131

Frequently asked questions about ZIP 46131 tap water

Is the tap water in ZIP 46131 safe to drink?

EPA testing detected 17 contaminants across the water suppliers serving ZIP 46131. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and your utility's annual Consumer Confidence Report for the official status.

Which water suppliers serve ZIP 46131?

4 public water suppliers report EPA drinking-water monitoring for ZIP 46131. Each is listed above with its population served.

What contaminants are in ZIP 46131's water?

EPA monitoring detected Nitrate-Nitrite, Nitrate, Copper, Fluoride, Barium, and others across this ZIP's suppliers. The full list with levels and sources is above.