← Chesterfield, SC

Tap water quality report

ZIP 29520 — Chesterfield, SC

EPA monitoring across the 2 water suppliers serving ZIP 29520 in Chesterfield, SC detected 21 contaminants. A detection doesn't automatically mean the water is unsafe — see the highest level found below, with the EPA limit for each.

2
water suppliers
32,016
people served
21
contaminants found

What was found in ZIP 29520

The highest level seen across the suppliers serving this ZIP, the EPA limit for each, and where the figure comes from.

ContaminantLevel vs EPA limitSuppliersSource
Nitrate
1100 µg/L 11%
of the EPA limit 10000 µg/L
1/2 SYR4
Fluoride
660 µg/L 17%
of the EPA limit 4000 µg/L
1/2 SYR4
Copper
220 µg/L 17%
of the EPA limit 1300 µg/L
2/2 SYR4
TTHM
104.88 µg/L 131%
of the EPA limit, in the worst sample — 80 µg/L
2/2 SYR4
Chloroform
94.12 µg/L
No EPA limit set
2/2 SYR4
Total Haloacetic Acids (HAA5)
67.7 µg/L 113%
of the EPA limit, in the worst sample — 60 µg/L
2/2 SYR4
Barium
50 µg/L 2.5%
of the EPA limit 2000 µg/L
1/2 SYR4
Dichloroacetic Acid
48.12 µg/L
No EPA limit set
2/2 SYR4
Lead
37 µg/L 247%
of the EPA limit, in the worst sample — 15 µg/L
2/2 SYR4
Trichloroacetic Acid
28.36 µg/L
No EPA limit set
2/2 SYR4
Bromodichloromethane
20.64 µg/L
No EPA limit set
2/2 SYR4
Monobromoacetic Acid
11.28 µg/L
No EPA limit set
2/2 SYR4
Dibromochloromethane
7.37 µg/L
No EPA limit set
2/2 SYR4
Bromoform
2.04 µg/L
No EPA limit set
1/2 SYR4
Dibromoacetic Acid
1.69 µg/L
No EPA limit set
2/2 SYR4
Atrazine
0.5500 µg/L 18%
of the EPA limit 3 µg/L
1/2 SYR4
Pfba
0.0054 µg/L
No EPA limit set
1/2 UCMR-5
PFOS
0.0053 µg/L
No EPA limit set
1/2 UCMR-5
Pfpea
0.0043 µg/L
No EPA limit set
1/2 UCMR-5
Pfhxa
0.0038 µg/L
No EPA limit set
1/2 UCMR-5
Lead
0.0017 mg/L 11%
of the EPA limit 0.0150 mg/L
2/2 LCR
Each bar shows the measured level as a share of the EPA limit: green is well under, amber is close to it, red is over. For lead and copper the limit applies to exactly the 90th-percentile figure shown, so red there means a real exceedance. For everything else the limit applies to a running annual average while the figure is the single worst sample on record — over 100% is worth reading, but is not by itself a violation. Formal violations are listed separately.

Water suppliers serving ZIP 29520

SupplierStatePopulation served
CHESTERFIELD CO RURAL WATER (SC1320003) SC 25,691
CHERAW TOWN OF (SC1310001) SC 6,325

Frequently asked questions about ZIP 29520 tap water

Is the tap water in ZIP 29520 safe to drink?

EPA testing detected 21 contaminants across the water suppliers serving ZIP 29520. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and your utility's annual Consumer Confidence Report for the official status.

Which water suppliers serve ZIP 29520?

2 public water suppliers report EPA drinking-water monitoring for ZIP 29520. Each is listed above with its population served.

What contaminants are in ZIP 29520's water?

EPA monitoring detected Nitrate, Fluoride, Copper, TTHM, Chloroform, and others across this ZIP's suppliers. The full list with levels and sources is above.