EPA monitoring across the 4 water suppliers serving ZIP 15044 in Pittsburgh, PA detected 25 contaminants. A detection doesn't automatically mean the water is unsafe — see the level at the main supplier below, with the EPA limit for each.

4
water suppliers
312,040
people served
25
contaminants found

What was found in ZIP 15044

The level at this ZIP's main supplier, the highest level anywhere in it, the EPA limit for each, and where the figure comes from.

ContaminantLevel vs EPA limitSuppliersSource
Nitrate
1192.5 µg/L 12%
of the EPA limit 10000 µg/L
Main supplier: WEST VIEW WATER AUTHORITY · 200,000 people · 2019
3/4 SYR4
Fluoride
700 µg/L 18%
of the EPA limit 4000 µg/L
Main supplier: WEST VIEW WATER AUTHORITY · 200,000 people · 2019
3/4 SYR4
Nitrite
326 µg/L 33%
of the EPA limit 1000 µg/L
Main supplier: WEST VIEW WATER AUTHORITY · 200,000 people · 2019
2/4 SYR4
Copper
160 µg/L 12%
of the EPA limit 1300 µg/L
Main supplier: WEST VIEW WATER AUTHORITY · 200,000 people · 2019
Highest in the ZIP: 234.25 µg/L — HAMPTON SHALER WATER AUTHORITY · 61,949 people · 2019
4/4 SYR4
TTHM
68.02 µg/L 85%
of the EPA limit 80 µg/L
Main supplier: WEST VIEW WATER AUTHORITY · 200,000 people · 2019
Highest in the ZIP: 84.615 µg/L — HAMPTON SHALER WATER AUTHORITY · 61,949 people · 2019
4/4 SYR4
Total Haloacetic Acids (HAA5)
26.35 µg/L 44%
of the EPA limit 60 µg/L
Main supplier: WEST VIEW WATER AUTHORITY · 200,000 people · 2019
Highest in the ZIP: 49.77 µg/L — OAKMONT WATER AUTHORITY · 39,901 people · 2019
4/4 SYR4
Chloroform
37.3 µg/L
No EPA limit set
Main supplier: WEST VIEW WATER AUTHORITY · 200,000 people · 2019
Highest in the ZIP: 49.235 µg/L — OAKMONT WATER AUTHORITY · 39,901 people · 2019
4/4 SYR4
Barium
41.6 µg/L 2.1%
of the EPA limit 2000 µg/L
Main supplier: WEST VIEW WATER AUTHORITY · 200,000 people · 2019
2/4 SYR4
Trichloroacetic Acid
9.91 µg/L
No EPA limit set
Main supplier: WEST VIEW WATER AUTHORITY · 200,000 people · 2019
Highest in the ZIP: 27.605 µg/L — OAKMONT WATER AUTHORITY · 39,901 people · 2019
4/4 SYR4
Bromodichloromethane
20.12 µg/L
No EPA limit set
Main supplier: WEST VIEW WATER AUTHORITY · 200,000 people · 2019
Highest in the ZIP: 26.045 µg/L — HAMPTON SHALER WATER AUTHORITY · 61,949 people · 2019
4/4 SYR4
Lead
21 µg/L 140%
of the EPA limit, at the 95th percentile of samples — 15 µg/L
Main supplier: WEST VIEW WATER AUTHORITY · 200,000 people · 2019
Highest in the ZIP: 25.22 µg/L — HAMPTON SHALER WATER AUTHORITY · 61,949 people · 2019
4/4 SYR4
Dichloroacetic Acid
14.64 µg/L
No EPA limit set
Main supplier: WEST VIEW WATER AUTHORITY · 200,000 people · 2019
Highest in the ZIP: 24.245 µg/L — OAKMONT WATER AUTHORITY · 39,901 people · 2019
4/4 SYR4
Dibromochloromethane
16.52 µg/L
No EPA limit set
Main supplier: WEST VIEW WATER AUTHORITY · 200,000 people · 2019
Highest in the ZIP: 22 µg/L — HAMPTON SHALER WATER AUTHORITY · 61,949 people · 2019
4/4 SYR4
Monochloroacetic Acid
3.308 µg/L
No EPA limit set
Main supplier: WEST VIEW WATER AUTHORITY · 200,000 people · 2019
Highest in the ZIP: 12.32 µg/L — RICHLAND TWP WATER AUTHORITY · 10,190 people · 2019
4/4 SYR4
Lithium
11 µg/L
No EPA limit set
Highest in the ZIP: OAKMONT WATER AUTHORITY · 39,901 people · 2024
2/4 UCMR-5
Bromoform
5.5 µg/L
No EPA limit set
Main supplier: WEST VIEW WATER AUTHORITY · 200,000 people · 2019
Highest in the ZIP: 9.82 µg/L — HAMPTON SHALER WATER AUTHORITY · 61,949 people · 2019
4/4 SYR4
Antimony, Total
9.09 µg/L 152%
of the EPA limit, at the 95th percentile of samples — 6 µg/L
Highest in the ZIP: OAKMONT WATER AUTHORITY · 39,901 people · 2019
1/4 SYR4
Cyanide
7.2 µg/L 3.6%
of the EPA limit 200 µg/L
Main supplier: WEST VIEW WATER AUTHORITY · 200,000 people · 2019
1/4 SYR4
Dibromoacetic Acid
4.1 µg/L
No EPA limit set
Main supplier: WEST VIEW WATER AUTHORITY · 200,000 people · 2019
3/4 SYR4
cis-1,2-Dichloroethylene
2.069 µg/L 3%
of the EPA limit 70 µg/L
Highest in the ZIP: HAMPTON SHALER WATER AUTHORITY · 61,949 people · 2019
1/4 SYR4
Arsenic
2 µg/L 20%
of the EPA limit 10 µg/L
Main supplier: WEST VIEW WATER AUTHORITY · 200,000 people · 2019
1/4 SYR4
Tetrachloroethylene
1.2453 µg/L 25%
of the EPA limit 5 µg/L
Highest in the ZIP: HAMPTON SHALER WATER AUTHORITY · 61,949 people · 2019
1/4 SYR4
Monobromoacetic Acid
1.01 µg/L
No EPA limit set
Highest in the ZIP: RICHLAND TWP WATER AUTHORITY · 10,190 people · 2019
1/4 SYR4
Di(2-ethylhexyl) Phthalate
0.8000 µg/L 13%
of the EPA limit 6 µg/L
Main supplier: WEST VIEW WATER AUTHORITY · 200,000 people · 2019
1/4 SYR4
Lead
0.0 mg/L 0%
of the EPA limit 0.0150 mg/L
Main supplier: WEST VIEW WATER AUTHORITY · 200,000 people · 2025
Highest in the ZIP: 0.0014 mg/L — RICHLAND TWP WATER AUTHORITY · 10,190 people · 2025
4/4 LCR
Each bar shows the measured level as a share of the EPA limit: green is well under, amber is close to it, red is over. For lead and copper the limit applies to exactly the 90th-percentile figure shown, so red there means a real exceedance. For everything else the limit applies to a running annual average while the figure is the 95th percentile of the system's samples — over 100% is worth reading, but is not by itself a violation. Formal violations are listed separately.

Water suppliers serving ZIP 15044

SupplierStatePopulation served
WEST VIEW WATER AUTHORITY PA 200,000
HAMPTON SHALER WATER AUTHORITY PA 61,949
OAKMONT WATER AUTHORITY PA 39,901
RICHLAND TWP WATER AUTHORITY PA 10,190

Frequently asked questions about ZIP 15044 tap water

Is the tap water in ZIP 15044 safe to drink?

EPA testing detected 25 contaminants across the water suppliers serving ZIP 15044. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and your utility's annual Consumer Confidence Report for the official status.

Which water suppliers serve ZIP 15044?

4 public water suppliers report EPA drinking-water monitoring for ZIP 15044. Each is listed above with its population served.

What contaminants are in ZIP 15044's water?

EPA monitoring detected Nitrate, Fluoride, Nitrite, Copper, TTHM, and others across this ZIP's suppliers. The full list with levels and sources is above.