Compliance record
Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.
| Violation | Type | Status | Period |
|---|---|---|---|
| MR | Monitoring | Archived | 2025-12-01 → 2025-12-31 |
| MR | Monitoring | Archived | 2025-12-01 → 2025-12-31 |
| MR | Monitoring | Archived | 2025-12-01 → 2025-12-31 |
| MR | Monitoring | Archived | 2025-12-01 → 2025-12-31 |
| Other | Monitoring | Unaddressed | 2025-11-15 |
| MR | Monitoring | Archived | 2025-10-01 → 2025-12-31 |
| MR | Monitoring | Archived | 2025-10-01 → 2025-12-31 |
| MR | Monitoring | Archived | 2025-10-01 → 2025-12-31 |
| MR | Monitoring | Archived | 2025-10-01 → 2025-12-31 |
| MR | Monitoring | Unaddressed | 2024-10-01 |
Other contaminants detected
| Contaminant | Level vs EPA limit | Detection rate | Source | Period |
|---|---|---|---|---|
| Bromodichloromethane | 11.6 µg/L No EPA limit set | 32/32 | SYR4 | 2012–2019 |
| Chloroform | 82.2 µg/L No EPA limit set | 32/32 | SYR4 | 2012–2019 |
| TTHM | 95.2 µg/L 119% of the EPA limit, in the worst sample — 80 µg/L | 32/32 | SYR4 | 2012–2019 |
| Dichloroacetic Acid | 37.2 µg/L No EPA limit set | 31/32 | SYR4 | 2012–2019 |
| Total Haloacetic Acids (HAA5) | 72.2 µg/L 120% of the EPA limit, in the worst sample — 60 µg/L | 31/32 | SYR4 | 2012–2019 |
| Trichloroacetic Acid | 44.3 µg/L No EPA limit set | 31/32 | SYR4 | 2012–2019 |
| Copper | 670 µg/L 52% of the EPA limit 1300 µg/L | 29/30 | SYR4 | 2012–2018 |
| Dibromochloromethane | 1.68 µg/L No EPA limit set | 29/32 | SYR4 | 2012–2019 |
| Monochloroacetic Acid | 3.8 µg/L No EPA limit set | 26/32 | SYR4 | 2012–2019 |
| Nitrate | 450 µg/L 4.5% of the EPA limit 10000 µg/L | 16/16 | SYR4 | 2012–2019 |
| Lead | 0.0033 mg/L 22% of the EPA limit 0.0150 mg/L | 13/13 | LCR | 2025 |
| Barium | 43.7 µg/L 2.2% of the EPA limit 2000 µg/L | 8/8 | SYR4 | 2012–2019 |
| Fluoride | 1080 µg/L 27% of the EPA limit 4000 µg/L | 8/8 | SYR4 | 2012–2019 |
| Monobromoacetic Acid | 2.7 µg/L No EPA limit set | 3/32 | SYR4 | 2012–2019 |
| Nitrate-Nitrite | 270 µg/L 2.7% of the EPA limit 10000 µg/L | 3/3 | SYR4 | 2014–2019 |
| Gross Alpha, Excl. Radon And U | 0.7170 pCi/L 4.8% of the EPA limit 15 pCi/L | 2/2 | SYR4 | 2013–2019 |
| Dibromoacetic Acid | 0.5200 µg/L No EPA limit set | 1/32 | SYR4 | 2012–2019 |
| Lead | 0.9400 µg/L 6.3% of the EPA limit 15 µg/L | 1/30 | SYR4 | 2012–2018 |
58 contaminants tested, none detected
Utility contact
Frequently asked questions about Taylor County Psd
Is Taylor County Psd tap water safe to drink?
EPA monitoring detected 18 contaminants in Taylor County Psd's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.
What contaminants were detected in Taylor County Psd's water?
EPA monitoring detected Bromodichloromethane, Chloroform, TTHM, Dichloroacetic Acid, Total Haloacetic Acids (HAA5), and others. The full list with the level and data source for each is above.
How many people does Taylor County Psd serve?
Taylor County Psd reports serving 1,322 people in West Virginia, per its EPA record.
Has Taylor County Psd had any water quality violations?
The EPA has 50 violations on file for Taylor County Psd, of which 0 are health-based (a contaminant limit or required treatment was breached) and 8 remain open. The rest are monitoring or reporting failures.
Where does this data come from?
Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.