Compliance record
Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.
| Violation | Type | Status | Period |
|---|---|---|---|
| MCL | Health-based | Resolved | 2005-07-01 → 2005-09-30 |
| MCL | Health-based | Resolved | 2005-07-01 → 2005-09-30 |
| MCL | Health-based | Resolved | 2005-07-01 → 2005-09-30 |
| MCL | Health-based | Resolved | 2005-07-01 → 2005-09-30 |
| MCL | Health-based | Resolved | 2005-01-01 → 2005-03-31 |
| MCL | Health-based | Resolved | 2005-01-01 → 2005-03-31 |
| MCL | Health-based | Resolved | 2005-01-01 → 2005-03-31 |
| MCL | Health-based | Resolved | 2005-01-01 → 2005-03-31 |
| TT | Health-based | Resolved | 1993-07-01 → 1993-07-31 |
| TT | Health-based | Resolved | 1993-07-01 → 1993-07-31 |
Other contaminants detected
| Contaminant | Level vs EPA limit | Detection rate | Source | Period |
|---|---|---|---|---|
| Copper | 351 µg/L 27% of the EPA limit 1300 µg/L | 60/61 | SYR4 | 2012–2018 |
| Bromodichloromethane | 8.01 µg/L No EPA limit set | 58/58 | SYR4 | 2012–2019 |
| Chloroform | 73.1 µg/L No EPA limit set | 58/58 | SYR4 | 2012–2019 |
| Dichloroacetic Acid | 38 µg/L No EPA limit set | 58/58 | SYR4 | 2012–2019 |
| TTHM | 79.3 µg/L 99% of the EPA limit 80 µg/L | 58/58 | SYR4 | 2012–2019 |
| Total Haloacetic Acids (HAA5) | 83 µg/L 138% of the EPA limit, in the worst sample — 60 µg/L | 58/58 | SYR4 | 2012–2019 |
| Trichloroacetic Acid | 41.4 µg/L No EPA limit set | 57/58 | SYR4 | 2012–2019 |
| Monochloroacetic Acid | 21.8 µg/L No EPA limit set | 43/58 | SYR4 | 2012–2019 |
| Lead | 9.2 µg/L 61% of the EPA limit 15 µg/L | 36/61 | SYR4 | 2012–2018 |
| Lead | 0.0027 mg/L 18% of the EPA limit 0.0150 mg/L | 18/18 | LCR | 2024 |
| Dibromochloromethane | 1.2 µg/L No EPA limit set | 17/58 | SYR4 | 2012–2019 |
| Nitrate | 250 µg/L 2.5% of the EPA limit 10000 µg/L | 14/20 | SYR4 | 2012–2019 |
| Monobromoacetic Acid | 16.9 µg/L No EPA limit set | 10/58 | SYR4 | 2012–2019 |
| Fluoride | 840 µg/L 21% of the EPA limit 4000 µg/L | 9/9 | SYR4 | 2012–2019 |
| Barium | 24.5 µg/L 1.2% of the EPA limit 2000 µg/L | 8/8 | SYR4 | 2012–2019 |
| Dibromoacetic Acid | 0.6140 µg/L No EPA limit set | 3/58 | SYR4 | 2012–2019 |
| Cyanide | 77 µg/L 39% of the EPA limit 200 µg/L | 2/8 | SYR4 | 2012–2019 |
| Di(2-ethylhexyl) Phthalate | 1 µg/L 17% of the EPA limit 6 µg/L | 1/4 | SYR4 | 2016–2019 |
| Gross Alpha, Excl. Radon And U | 1.28 pCi/L 8.5% of the EPA limit 15 pCi/L | 1/1 | SYR4 | 2019 |
| Nitrate-Nitrite | 140 µg/L 1.4% of the EPA limit 10000 µg/L | 1/1 | SYR4 | 2018 |
56 contaminants tested, none detected
Utility contact
Frequently asked questions about Craigsville Psd
Is Craigsville Psd tap water safe to drink?
EPA monitoring detected 20 contaminants in Craigsville Psd's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.
What contaminants were detected in Craigsville Psd's water?
EPA monitoring detected Copper, Bromodichloromethane, Chloroform, Dichloroacetic Acid, TTHM, and others. The full list with the level and data source for each is above.
How many people does Craigsville Psd serve?
Craigsville Psd reports serving 4,997 people in West Virginia, per its EPA record.
Has Craigsville Psd had any water quality violations?
The EPA has 50 violations on file for Craigsville Psd, of which 12 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.
Where does this data come from?
Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.