Compliance record
Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.
| Violation | Type | Status | Period |
|---|---|---|---|
| TT | Health-based | Resolved | 2020-09-17 |
| TT | Health-based | Resolved | 2020-09-17 |
| TT | Health-based | Resolved | 2020-09-17 |
| TT | Health-based | Resolved | 2020-09-17 |
| TT | Health-based | Resolved | 2020-09-17 |
| TT | Health-based | Resolved | 2020-01-01 → 2020-03-31 |
| TT | Health-based | Resolved | 2020-01-01 → 2020-03-31 |
| TT | Health-based | Resolved | 2020-01-01 → 2020-03-31 |
| MCL | Health-based | Resolved | 2011-07-01 → 2011-09-30 |
| MCL | Health-based | Resolved | 2011-07-01 → 2011-09-30 |
Other contaminants detected
| Contaminant | Level vs EPA limit | Detection rate | Source | Period |
|---|---|---|---|---|
| Bromodichloromethane | 6.1835 µg/L No EPA limit set
worst single sample: 7.05 µg/L | 32/32 | SYR4 | 2012–2019 |
| Chloroform | 46.075 µg/L No EPA limit set
worst single sample: 54.2 µg/L | 32/32 | SYR4 | 2012–2019 |
| Dichloroacetic Acid | 29.005 µg/L No EPA limit set
worst single sample: 29.6 µg/L | 32/32 | SYR4 | 2012–2019 |
| TTHM | 52.62 µg/L 66% of the EPA limit 80 µg/L
worst single sample: 58.5 µg/L | 32/32 | SYR4 | 2012–2019 |
| Total Haloacetic Acids (HAA5) | 60.97 µg/L 102% of the EPA limit, at the 95th percentile of samples — 60 µg/L
worst single sample: 73.3 µg/L | 32/32 | SYR4 | 2012–2019 |
| Trichloroacetic Acid | 32.75 µg/L No EPA limit set
worst single sample: 41.1 µg/L | 32/32 | SYR4 | 2012–2019 |
| Copper | 201.5 µg/L 16% of the EPA limit 1300 µg/L
worst single sample: 291 µg/L | 31/31 | SYR4 | 2012–2019 |
| Lead | 2.96 µg/L 20% of the EPA limit 15 µg/L
worst single sample: 3.4 µg/L | 28/31 | SYR4 | 2012–2019 |
| Monochloroacetic Acid | 3.9055 µg/L No EPA limit set
worst single sample: 11.6 µg/L | 24/32 | SYR4 | 2012–2019 |
| Nitrate | 740 µg/L 7.4% of the EPA limit 10000 µg/L | 20/20 | SYR4 | 2012–2019 |
| Lead | 0.0011 mg/L 7.3% of the EPA limit 0.0150 mg/L | 14/14 | LCR | 2024 |
| Barium | 24.44 µg/L 1.2% of the EPA limit 2000 µg/L
worst single sample: 25 µg/L | 8/8 | SYR4 | 2012–2019 |
| Fluoride | 1005.5 µg/L 25% of the EPA limit 4000 µg/L
worst single sample: 1030 µg/L | 8/9 | SYR4 | 2012–2019 |
| Dibromochloromethane | 1.0275 µg/L No EPA limit set
worst single sample: 1.13 µg/L | 6/32 | SYR4 | 2012–2019 |
| Combined Radium (-226 And -228) | 0.9073 pCi/L 18% of the EPA limit 5 pCi/L
worst single sample: 0.9250 pCi/L | 4/4 | SYR4 | 2013–2019 |
| Gross Alpha, Excl. Radon And U | 0.4410 pCi/L 2.9% of the EPA limit 15 pCi/L
worst single sample: 0.4500 pCi/L | 3/3 | SYR4 | 2013–2019 |
| Monobromoacetic Acid | 2.996 µg/L No EPA limit set
worst single sample: 3 µg/L | 3/32 | SYR4 | 2012–2019 |
| Nitrate-Nitrite | 567 µg/L 5.7% of the EPA limit 10000 µg/L
worst single sample: 580 µg/L | 3/3 | SYR4 | 2017–2019 |
| Antimony, Total | 0.5000 µg/L 8.3% of the EPA limit 6 µg/L | 1/8 | SYR4 | 2012–2019 |
| Cyanide | 22 µg/L 11% of the EPA limit 200 µg/L | 1/8 | SYR4 | 2012–2019 |
| Thallium, Total | 4.7 µg/L 235% of the EPA limit, at the 95th percentile of samples — 2 µg/L | 1/8 | SYR4 | 2012–2019 |
| Toluene | 0.8500 µg/L 0.1% of the EPA limit 1000 µg/L | 1/8 | SYR4 | 2012–2019 |
55 contaminants tested, none detected
Utility contact
Frequently asked questions about Alderson Water
Is Alderson Water tap water safe to drink?
EPA monitoring detected 22 contaminants in Alderson Water's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.
What contaminants were detected in Alderson Water's water?
EPA monitoring detected Bromodichloromethane, Chloroform, Dichloroacetic Acid, TTHM, Total Haloacetic Acids (HAA5), and others. The full list with the level and data source for each is above.
How many people does Alderson Water serve?
Alderson Water reports serving 2,458 people in West Virginia, per its EPA record.
Has Alderson Water had any water quality violations?
The EPA has 58 violations on file for Alderson Water, of which 20 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.
Where does this data come from?
Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.