← Wisconsin

Tap water quality report

Coulee Manor Trailer Park

EPA monitoring tested this supplier for 62 contaminants and detected 9. A detection doesn't automatically mean the water is unsafe — the level and EPA source for each is below.

62
contaminants tested
9
detected
39
people served
5
health-based violations
Water source
Ground water
Ownership
Private
Counties served
La Crosse

Compliance record

Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.

5
health-based violations
359
violations on file
0
still open
ViolationTypeStatusPeriod
MCL Health-based Resolved 2010-06-01 → 2010-06-30
MCL Health-based Resolved 2010-06-01 → 2010-06-30
MCL Health-based Resolved 2010-06-01 → 2010-06-30
MCL Health-based Resolved 2010-06-01 → 2010-06-30
MCL Health-based Resolved 2010-06-01 → 2010-06-30
RPT Monitoring Resolved 2025-07-02
MON Monitoring Resolved 2024-03-01 → 2024-03-31
MON Monitoring Resolved 2024-03-01 → 2024-03-31
MON Monitoring Resolved 2024-03-01 → 2024-03-31
MON Monitoring Resolved 2024-03-01 → 2024-03-31

Other contaminants detected

Each bar shows the measured level as a share of the EPA limit: green is well under, amber is close to it, red is over. For lead and copper the limit applies to exactly the 90th-percentile figure shown, so red there means a real exceedance. For everything else the limit applies to a running annual average while the figure is the single worst sample on record — over 100% is worth reading, but is not by itself a violation. Formal violations are listed separately.
ContaminantLevel vs EPA limitDetection rateSourcePeriod
Lead
0.0091 mg/L 60%
of the EPA limit 0.0150 mg/L
13/13 LCR 2024
Nitrate
1060 µg/L 11%
of the EPA limit 10000 µg/L
10/16 SYR4 2012–2019
Lead
7.46 µg/L 50%
of the EPA limit 15 µg/L
6/15 SYR4 2012–2018
Barium
46.3 µg/L 2.3%
of the EPA limit 2000 µg/L
1/1 SYR4 2018
Copper
20.3 µg/L 1.6%
of the EPA limit 1300 µg/L
1/15 SYR4 2012–2018
Combined Radium (-226 And -228)
1.52 pCi/L 30%
of the EPA limit 5 pCi/L
1/1 SYR4 2015
Fluoride
90 µg/L 2.3%
of the EPA limit 4000 µg/L
1/1 SYR4 2018
Gross Alpha, Excl. Radon And U
1.4 pCi/L 9.3%
of the EPA limit 15 pCi/L
1/1 SYR4 2015
Nitrate-Nitrite
774 µg/L 7.7%
of the EPA limit 10000 µg/L
1/1 SYR4 2018
53 contaminants tested, none detected
1,1,1-Trichloroethane1,1,2-Trichloroethane1,1-Dichloroethylene1,2,4-Trichlorobenzene1,2-Dichloroethane1,2-Dichloropropane2,4,5-TP2,4-DAntimony, TotalArsenicAtrazineBhc-GammaBenzeneBeryllium, TotalChlorobenzeneCadmiumCarbofuranCarbon TetrachlorideChlordaneChromiumDichloromethaneDalaponDinosebDiquatEndothallEndrinEthylbenzeneGlyphosateHexachlorobenzeneHeptachlorHeptachlor EpoxideHexachlorocyclopentadieneLassoMercuryMethoxychlorNitriteOxamylPentachlorophenolPicloramSeleniumSimazineStyreneTetrachloroethyleneThallium, TotalTolueneToxapheneTrichloroethyleneVinyl ChlorideXylenes, Totalcis-1,2-DichloroethyleneO-DichlorobenzeneP-Dichlorobenzenetrans-1,2-Dichloroethylene

Utility contact

Frequently asked questions about Coulee Manor Trailer Park

Is Coulee Manor Trailer Park tap water safe to drink?

EPA monitoring detected 9 contaminants in Coulee Manor Trailer Park's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.

What contaminants were detected in Coulee Manor Trailer Park's water?

EPA monitoring detected Lead, Nitrate, Lead, Barium, Copper, and others. The full list with the level and data source for each is above.

How many people does Coulee Manor Trailer Park serve?

Coulee Manor Trailer Park reports serving 39 people in Wisconsin, per its EPA record.

Has Coulee Manor Trailer Park had any water quality violations?

The EPA has 359 violations on file for Coulee Manor Trailer Park, of which 5 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.

Where does this data come from?

Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.