Compliance record
Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.
| Violation | Type | Status | Period |
|---|---|---|---|
| TT | Health-based | Resolved | 2024-10-17 |
| TT | Health-based | Resolved | 2024-10-17 |
| TT | Health-based | Resolved | 2024-10-17 |
| TT | Health-based | Resolved | 2021-05-02 |
| TT | Health-based | Resolved | 2021-05-02 |
| TT | Health-based | Resolved | 2015-12-22 |
| TT | Health-based | Resolved | 2015-12-22 |
| TT | Health-based | Resolved | 2015-12-22 |
| TT | Health-based | Resolved | 2015-12-22 |
| TT | Health-based | Resolved | 2015-12-22 |
Other contaminants detected
| Contaminant | Level vs EPA limit | Detection rate | Source | Period |
|---|---|---|---|---|
| Lead | 0.0042 mg/L 28% of the EPA limit 0.0150 mg/L | 14/14 | LCR | 2023 |
| Copper | 98.2 µg/L 7.6% of the EPA limit 1300 µg/L
worst single sample: 100 µg/L | 10/10 | SYR4 | 2014–2017 |
| Lead | 1.71 µg/L 11% of the EPA limit 15 µg/L
worst single sample: 1.8 µg/L | 10/10 | SYR4 | 2014–2017 |
| Dibromochloromethane | 2.24 µg/L No EPA limit set
worst single sample: 2.3 µg/L | 4/6 | SYR4 | 2013–2019 |
| Dibromoacetic Acid | 1.256 µg/L No EPA limit set
worst single sample: 1.3 µg/L | 3/3 | SYR4 | 2013–2019 |
| TTHM | 8.908 µg/L 11% of the EPA limit 80 µg/L
worst single sample: 9.23 µg/L | 3/4 | SYR4 | 2013–2019 |
| Total Haloacetic Acids (HAA5) | 3.545 µg/L 5.9% of the EPA limit 60 µg/L
worst single sample: 3.75 µg/L | 3/3 | SYR4 | 2013–2019 |
| Barium | 87.9 µg/L 4.4% of the EPA limit 2000 µg/L
worst single sample: 88 µg/L | 2/2 | SYR4 | 2014–2017 |
| Bromodichloromethane | 3.24 µg/L No EPA limit set
worst single sample: 3.3 µg/L | 2/6 | SYR4 | 2013–2019 |
| Chloroform | 3.12 µg/L No EPA limit set
worst single sample: 3.2 µg/L | 2/6 | SYR4 | 2013–2019 |
| Combined Radium (-226 And -228) | 4.937 pCi/L 99% of the EPA limit 5 pCi/L
worst single sample: 4.98 pCi/L | 2/2 | SYR4 | 2014–2017 |
| Dichloroacetic Acid | 1.87 µg/L No EPA limit set
worst single sample: 1.9 µg/L | 2/3 | SYR4 | 2013–2019 |
| Ethylbenzene | 1.785 µg/L 0.3% of the EPA limit 700 µg/L
worst single sample: 1.8 µg/L | 2/7 | SYR4 | 2014–2019 |
| Gross Alpha, Excl. Radon And U | 8.878 pCi/L 59% of the EPA limit 15 pCi/L
worst single sample: 8.96 pCi/L | 2/2 | SYR4 | 2014–2017 |
| Xylenes, Total | 10.85 µg/L 0.1% of the EPA limit 10000 µg/L
worst single sample: 11 µg/L | 2/7 | SYR4 | 2014–2019 |
| 1,2,4-Trichlorobenzene | 1.3 µg/L 1.9% of the EPA limit 70 µg/L | 1/6 | SYR4 | 2014–2019 |
| Arsenic | 1.1 µg/L 11% of the EPA limit 10 µg/L | 1/2 | SYR4 | 2014–2017 |
57 contaminants tested, none detected
Utility contact
Frequently asked questions about Pound Waterworks
Is Pound Waterworks tap water safe to drink?
EPA monitoring detected 17 contaminants in Pound Waterworks's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.
What contaminants were detected in Pound Waterworks's water?
EPA monitoring detected Lead, Copper, Lead, Dibromochloromethane, Dibromoacetic Acid, and others. The full list with the level and data source for each is above.
How many people does Pound Waterworks serve?
Pound Waterworks reports serving 349 people in Wisconsin, per its EPA record.
Has Pound Waterworks had any water quality violations?
The EPA has 58 violations on file for Pound Waterworks, of which 21 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.
Where does this data come from?
Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.