← Washington

Tap water quality report

Yacolt

EPA monitoring tested this supplier for 57 contaminants and detected 10. A detection doesn't automatically mean the water is unsafe — the level and EPA source for each is below.

57
contaminants tested
10
detected
3,034
people served
16
health-based violations
Water source
Ground water
Ownership
Local government
Counties served
Clark

Compliance record

Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.

16
health-based violations
79
violations on file
0
still open
ViolationTypeStatusPeriod
TT Health-based Resolved 2022-10-02
MCL Health-based Archived 1997-01-01 → 1997-01-31
MCL Health-based Archived 1997-01-01 → 1997-01-31
MCL Health-based Archived 1997-01-01 → 1997-01-31
MCL Health-based Archived 1996-06-01 → 1996-06-30
MCL Health-based Archived 1995-12-01 → 1995-12-31
MCL Health-based Archived 1995-08-01 → 1995-08-31
MCL Health-based Archived 1994-06-01 → 1994-06-30
MCL Health-based Archived 1992-12-01 → 1992-12-31
MCL Health-based Archived 1992-09-01 → 1992-09-30

Other contaminants detected

Each bar shows the measured level as a share of the EPA limit: green is well under, amber is close to it, red is over. For lead and copper the limit applies to exactly the 90th-percentile figure shown, so red there means a real exceedance. For everything else the limit applies to a running annual average while the figure is the single worst sample on record — over 100% is worth reading, but is not by itself a violation. Formal violations are listed separately.
ContaminantLevel vs EPA limitDetection rateSourcePeriod
Nitrate
2900 µg/L 29%
of the EPA limit 10000 µg/L
32/32 SYR4 2012–2019
Lead
0.0019 mg/L 13%
of the EPA limit 0.0150 mg/L
11/11 LCR 2015
Chloroform
0.9900 µg/L
No EPA limit set
8/17 SYR4 2013–2019
TTHM
0.9900 µg/L 1.2%
of the EPA limit 80 µg/L
8/8 SYR4 2013–2019
Copper
13 µg/L 1%
of the EPA limit 1300 µg/L
3/3 SYR4 2013–2018
Total Haloacetic Acids (HAA5)
1.1 µg/L 1.8%
of the EPA limit 60 µg/L
3/11 SYR4 2013–2018
Dichloroacetic Acid
1.1 µg/L
No EPA limit set
2/12 SYR4 2013–2019
Monochloroacetic Acid
0.5500 µg/L
No EPA limit set
2/12 SYR4 2013–2019
Chromium
2 µg/L 2%
of the EPA limit 100 µg/L
1/1 SYR4 2013
Nitrate-Nitrite
2160 µg/L 22%
of the EPA limit 10000 µg/L
1/1 SYR4 2013
47 contaminants tested, none detected
1,1,1-Trichloroethane1,1,2-Trichloroethane1,1-Dichloroethylene1,2,4-Trichlorobenzene1,2-DIBROMO-3-CHLOROPROPANE1,2-Dichloroethane1,2-Dichloropropane2,4,5-TP2,4-DAntimony, TotalArsenicBariumBenzeneBeryllium, TotalBromodichloromethaneBromoformChlorobenzeneCyanideCadmiumCarbon TetrachlorideDichloromethaneDalaponDibromoacetic AcidDibromochloromethaneDinosebEthylene DibromideEthylbenzeneFluorideLeadMercuryMonobromoacetic AcidNitritePentachlorophenolPicloramSeleniumStyreneTetrachloroethyleneThallium, TotalTolueneTrichloroacetic AcidTrichloroethyleneVinyl ChlorideXylenes, Totalcis-1,2-DichloroethyleneO-DichlorobenzeneP-Dichlorobenzenetrans-1,2-Dichloroethylene

Utility contact

Contact
John Roth

Frequently asked questions about Yacolt

Is Yacolt tap water safe to drink?

EPA monitoring detected 10 contaminants in Yacolt's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.

What contaminants were detected in Yacolt's water?

EPA monitoring detected Nitrate, Lead, Chloroform, TTHM, Copper, and others. The full list with the level and data source for each is above.

How many people does Yacolt serve?

Yacolt reports serving 3,034 people in Washington, per its EPA record.

Has Yacolt had any water quality violations?

The EPA has 79 violations on file for Yacolt, of which 16 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.

Where does this data come from?

Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.