Compliance record
Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.
| Violation | Type | Status | Period |
|---|---|---|---|
| MCL | Health-based | Archived | 2025-10-01 → 2025-12-31 |
| MCL | Health-based | Resolved | 2013-04-01 → 2013-06-30 |
| MCL | Health-based | Archived | 2005-07-01 → 2005-07-31 |
| MCL | Health-based | Resolved | 2004-07-01 → 2004-09-30 |
| MCL | Health-based | Resolved | 2004-04-01 → 2004-06-30 |
| MCL | Health-based | Resolved | 2004-01-01 → 2004-03-31 |
| MCL | Health-based | Resolved | 2003-04-01 → 2003-06-30 |
| MCL | Health-based | Resolved | 2003-01-01 → 2003-12-31 |
| MCL | Health-based | Archived | 2000-09-01 → 2000-09-30 |
| MCL | Health-based | Archived | 2000-09-01 → 2000-09-30 |
Other contaminants detected
| Contaminant | Level vs EPA limit | Detection rate | Source | Period |
|---|---|---|---|---|
| Nitrate | 8301 µg/L 83% of the EPA limit 10000 µg/L
worst single sample: 11000 µg/L | 274/276 | SYR4 | 2012–2019 |
| Combined Uranium | 34.005 µg/L 113% of the EPA limit, at the 95th percentile of samples — 30 µg/L
worst single sample: 36.1 µg/L | 54/54 | SYR4 | 2012–2019 |
| Lead | 0.0014 mg/L 9.3% of the EPA limit 0.0150 mg/L | 12/12 | LCR | 2025 |
| Barium | 88.975 µg/L 4.4% of the EPA limit 2000 µg/L
worst single sample: 89.5 µg/L | 4/4 | SYR4 | 2012–2016 |
| Copper | 7.828 µg/L 0.6% of the EPA limit 1300 µg/L
worst single sample: 8.77 µg/L | 4/4 | SYR4 | 2012–2016 |
| Arsenic | 20.47 µg/L 205% of the EPA limit, at the 95th percentile of samples — 10 µg/L
worst single sample: 20.6 µg/L | 3/4 | SYR4 | 2012–2016 |
| Fluoride | 423.2 µg/L 11% of the EPA limit 4000 µg/L
worst single sample: 430 µg/L | 3/4 | SYR4 | 2012–2016 |
| Nitrate-Nitrite | 11200 µg/L 112% of the EPA limit, at the 95th percentile of samples — 10000 µg/L | 1/4 | SYR4 | 2012–2016 |
| Selenium | 1.97 µg/L 3.9% of the EPA limit 50 µg/L | 1/4 | SYR4 | 2012–2016 |
42 contaminants tested, none detected
Utility contact
Frequently asked questions about Country Villa Mobile Park
Is Country Villa Mobile Park tap water safe to drink?
EPA monitoring detected 9 contaminants in Country Villa Mobile Park's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.
What contaminants were detected in Country Villa Mobile Park's water?
EPA monitoring detected Nitrate, Combined Uranium, Lead, Barium, Copper, and others. The full list with the level and data source for each is above.
How many people does Country Villa Mobile Park serve?
Country Villa Mobile Park reports serving 162 people in Washington, per its EPA record.
Has Country Villa Mobile Park had any water quality violations?
The EPA has 49 violations on file for Country Villa Mobile Park, of which 18 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.
Where does this data come from?
Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.