Compliance record
Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.
| Violation | Type | Status | Period |
|---|---|---|---|
| MCL | Health-based | Resolved | 2013-06-01 → 2013-06-30 |
| MCL | Health-based | Resolved | 2013-06-01 → 2013-06-30 |
| MCL | Health-based | Resolved | 2013-06-01 → 2013-06-30 |
| MCL | Health-based | Resolved | 2013-06-01 → 2013-06-30 |
| MCL | Health-based | Archived | 2000-10-01 → 2000-10-31 |
| MCL | Health-based | Archived | 2000-10-01 → 2000-10-31 |
| MCL | Health-based | Archived | 2000-10-01 → 2000-10-31 |
| MR | Monitoring | Resolved | 2011-04-01 → 2011-04-30 |
| MR | Monitoring | Resolved | 2011-04-01 → 2011-04-30 |
| MR | Monitoring | Resolved | 2011-04-01 → 2011-04-30 |
Other contaminants detected
| Contaminant | Level vs EPA limit | Detection rate | Source | Period |
|---|---|---|---|---|
| Copper | 156.578 µg/L 12% of the EPA limit 1300 µg/L
worst single sample: 210 µg/L | 53/57 | SYR4 | 2012–2019 |
| Lead | 2.374 µg/L 16% of the EPA limit 15 µg/L
worst single sample: 3.7 µg/L | 34/57 | SYR4 | 2012–2019 |
| Lead | 0.00074 mg/L 4.9% of the EPA limit 0.0150 mg/L | 19/19 | LCR | 2023 |
| Combined Radium (-226 And -228) | 5.82 pCi/L 116% of the EPA limit, at the 95th percentile of samples — 5 pCi/L
worst single sample: 8.5 pCi/L | 9/10 | SYR4 | 2014–2019 |
| TTHM | 16.78 µg/L 21% of the EPA limit 80 µg/L
worst single sample: 20.1 µg/L | 9/9 | SYR4 | 2013–2018 |
| Dibromochloromethane | 5.2575 µg/L No EPA limit set
worst single sample: 6.15 µg/L | 8/9 | SYR4 | 2013–2018 |
| Nitrate-Nitrite | 170 µg/L 1.7% of the EPA limit 10000 µg/L | 8/34 | SYR4 | 2012–2019 |
| Bromodichloromethane | 5.578 µg/L No EPA limit set
worst single sample: 6.4 µg/L | 7/9 | SYR4 | 2013–2018 |
| Chloroform | 5.525 µg/L No EPA limit set
worst single sample: 5.69 µg/L | 7/9 | SYR4 | 2013–2018 |
| Dichloroacetic Acid | 2.35 µg/L No EPA limit set | 6/7 | SYR4 | 2013–2018 |
| Fluoride | 2007.5 µg/L 50% of the EPA limit 4000 µg/L
worst single sample: 2010 µg/L | 6/6 | SYR4 | 2013–2018 |
| Gross Beta Particle Activity | 8.025 pCi/L No EPA limit set
worst single sample: 8.4 pCi/L | 6/10 | SYR4 | 2014–2019 |
| Barium | 9.98 µg/L 0.5% of the EPA limit 2000 µg/L
worst single sample: 10 µg/L | 5/6 | SYR4 | 2013–2018 |
| Gross Alpha, Excl. Radon And U | 4.22 pCi/L 28% of the EPA limit 15 pCi/L
worst single sample: 4.4 pCi/L | 5/5 | SYR4 | 2014–2017 |
| Dibromoacetic Acid | 1.7455 µg/L No EPA limit set
worst single sample: 1.81 µg/L | 4/7 | SYR4 | 2013–2018 |
| Total Haloacetic Acids (HAA5) | 6.917 µg/L 12% of the EPA limit 60 µg/L
worst single sample: 6.98 µg/L | 4/7 | SYR4 | 2013–2018 |
| Monochloroacetic Acid | 2.671 µg/L No EPA limit set
worst single sample: 2.78 µg/L | 3/7 | SYR4 | 2013–2018 |
| Xylenes, Total | 2011.57 µg/L 20% of the EPA limit 10000 µg/L
worst single sample: 2230 µg/L | 3/15 | SYR4 | 2014–2019 |
| Bromoform | 1.821 µg/L No EPA limit set
worst single sample: 1.85 µg/L | 2/9 | SYR4 | 2013–2018 |
| Chromium | 3.025 µg/L 3% of the EPA limit 100 µg/L
worst single sample: 3.1 µg/L | 2/6 | SYR4 | 2013–2018 |
| Ethylbenzene | 2.8965 µg/L 0.4% of the EPA limit 700 µg/L
worst single sample: 3.03 µg/L | 2/15 | SYR4 | 2014–2019 |
| Trichloroacetic Acid | 1.786 µg/L No EPA limit set
worst single sample: 1.82 µg/L | 2/7 | SYR4 | 2013–2018 |
| Cyanide | 21 µg/L 11% of the EPA limit 200 µg/L | 1/5 | SYR4 | 2015–2018 |
| Selenium | 1 µg/L 2% of the EPA limit 50 µg/L | 1/6 | SYR4 | 2013–2018 |
| Styrene | 420 µg/L 420% of the EPA limit, at the 95th percentile of samples — 100 µg/L | 1/15 | SYR4 | 2014–2019 |
| Thallium, Total | 0.2000 µg/L 10% of the EPA limit 2 µg/L | 1/6 | SYR4 | 2013–2018 |
24 contaminants tested, none detected
Frequently asked questions about Town of Saluda
Is Town of Saluda tap water safe to drink?
EPA monitoring detected 26 contaminants in Town of Saluda's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.
What contaminants were detected in Town of Saluda's water?
EPA monitoring detected Copper, Lead, Lead, Combined Radium (-226 And -228), TTHM, and others. The full list with the level and data source for each is above.
How many people does Town of Saluda serve?
Town of Saluda reports serving 323 people, per its EPA record.
Has Town of Saluda had any water quality violations?
The EPA has 11 violations on file for Town of Saluda, of which 7 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.
Where does this data come from?
Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.