Tap water quality report

Duffield_Scott Co Psa

EPA monitoring tested this supplier for 110 contaminants and detected 21. A detection doesn't automatically mean the water is unsafe — the level and EPA source for each is below.

110
contaminants tested
21
detected
4,600
people served
19
health-based violations
Water source
Surface water
Ownership
Local government
Counties served
Scott

Compliance record

Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.

19
health-based violations
109
violations on file
2
still open
ViolationTypeStatusPeriod
MCL Health-based Resolved 2014-10-01 → 2014-10-31
MCL Health-based Resolved 2014-10-01 → 2014-10-31
MCL Health-based Resolved 2014-10-01 → 2014-10-31
MCL Health-based Resolved 2014-10-01 → 2014-10-31
TT Health-based Resolved 2012-11-25
TT Health-based Resolved 2012-11-25
TT Health-based Resolved 2012-11-25
TT Health-based Resolved 2012-11-25
TT Health-based Resolved 2012-11-25
TT Health-based Resolved 2012-11-25

Other contaminants detected

Each bar shows the measured level as a share of the EPA limit: green is well under, amber is close to it, red is over. For lead and copper the limit applies to exactly the 90th-percentile figure shown, so red there means a real exceedance. For everything else the limit applies to a running annual average while the figure is the single worst sample on record — over 100% is worth reading, but is not by itself a violation. Formal violations are listed separately.
ContaminantLevel vs EPA limitDetection rateSourcePeriod
Chloroform
73 µg/L
No EPA limit set
53/63 SYR4 2012–2019
Bromodichloromethane
9 µg/L
No EPA limit set
48/63 SYR4 2012–2019
TTHM
80 µg/L 100%
of the EPA limit 80 µg/L
46/54 SYR4 2012–2019
Dichloroacetic Acid
30 µg/L
No EPA limit set
39/52 SYR4 2012–2019
Total Haloacetic Acids (HAA5)
63 µg/L 105%
of the EPA limit, in the worst sample — 60 µg/L
39/52 SYR4 2012–2019
Trichloroacetic Acid
30 µg/L
No EPA limit set
37/52 SYR4 2012–2019
Copper
562 µg/L 43%
of the EPA limit 1300 µg/L
27/77 SYR4 2012–2019
Dibromochloromethane
1.5 µg/L
No EPA limit set
27/63 SYR4 2012–2019
Monochloroacetic Acid
3 µg/L
No EPA limit set
13/52 SYR4 2012–2019
Barium
60 µg/L 3%
of the EPA limit 2000 µg/L
12/12 SYR4 2012–2019
Lead
0.0 mg/L 0%
of the EPA limit 0.0150 mg/L
11/11 LCR 2025
Combined Radium (-226 And -228)
8.8 pCi/L 176%
of the EPA limit, in the worst sample — 5 pCi/L
10/10 SYR4 2015–2018
Fluoride
880 µg/L 22%
of the EPA limit 4000 µg/L
8/12 SYR4 2012–2019
Nitrate-Nitrite
660 µg/L 6.6%
of the EPA limit 10000 µg/L
7/10 SYR4 2012–2019
Gross Beta Particle Activity
4.8 pCi/L
No EPA limit set
6/6 SYR4 2015–2017
Lead
4 µg/L 27%
of the EPA limit 15 µg/L
5/77 SYR4 2012–2019
Nitrate
493 µg/L 4.9%
of the EPA limit 10000 µg/L
4/6 SYR4 2018–2019
Dibromoacetic Acid
2 µg/L
No EPA limit set
2/52 SYR4 2012–2019
Gross Alpha, Excl. Radon And U
13.3 pCi/L 89%
of the EPA limit 15 pCi/L
2/2 SYR4 2016–2017
Mercury
0.2000 µg/L 10%
of the EPA limit 2 µg/L
2/12 SYR4 2012–2019
Combined Uranium
1.2 µg/L 4%
of the EPA limit 30 µg/L
1/2 SYR4 2016–2017
89 contaminants tested, none detected
1,1,1-Trichloroethane1,1,2-Trichloroethane1,1-Dichloroethylene1,2,4-Trichlorobenzene1,2-DIBROMO-3-CHLOROPROPANE1,2-Dichloroethane1,2-Dichloropropane11Cl-PF3OUdS2,4,5-TP2,4-D4:2 Fts6:2 Fts8:2 Fts9Cl-PF3ONSAdonaAntimony, TotalArsenicAtrazineBhc-GammaBenzeneBenzo(A)PyreneBeryllium, TotalBromoformChlorobenzeneCyanideCadmiumCarbofuranCarbon TetrachlorideChlordaneChromiumDichloromethaneDalaponDi(2-ethylhexyl) AdipateDi(2-ethylhexyl) PhthalateDinosebDiquatEthylene DibromideEndrinEthylbenzeneHexachlorobenzeneHfpo-DaHeptachlorHeptachlor EpoxideHexachlorocyclopentadieneLassoMethoxychlorMonobromoacetic AcidNetfosaaNfdhaNmefosaaNitriteOxamylPfbaPFBSPfdaPfdoaPfeesaPfhpaPfhpsPfhxaPFHXSPfmbaPfmpaPFNAPFOAPFOSPfpeaPfpesPftaPftrdaPfunaPentachlorophenolPicloramSeleniumSimazineStyreneTetrachloroethyleneThallium, TotalTolueneTotal Polychlorinated Biphenyls (PCB)ToxapheneTrichloroethyleneVinyl ChlorideXylenes, Totalcis-1,2-DichloroethyleneLithiumO-DichlorobenzeneP-Dichlorobenzenetrans-1,2-Dichloroethylene

Frequently asked questions about Duffield_Scott Co Psa

Is Duffield_Scott Co Psa tap water safe to drink?

EPA monitoring detected 21 contaminants in Duffield_Scott Co Psa's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.

What contaminants were detected in Duffield_Scott Co Psa's water?

EPA monitoring detected Chloroform, Bromodichloromethane, TTHM, Dichloroacetic Acid, Total Haloacetic Acids (HAA5), and others. The full list with the level and data source for each is above.

How many people does Duffield_Scott Co Psa serve?

Duffield_Scott Co Psa reports serving 4,600 people, per its EPA record.

Has Duffield_Scott Co Psa had any water quality violations?

The EPA has 109 violations on file for Duffield_Scott Co Psa, of which 19 are health-based (a contaminant limit or required treatment was breached) and 2 remain open. The rest are monitoring or reporting failures.

Where does this data come from?

Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.