← Virginia

Tap water quality report

Narrows, Town of

EPA monitoring tested this supplier for 44 contaminants and detected 13. A detection doesn't automatically mean the water is unsafe — the level and EPA source for each is below.

44
contaminants tested
13
detected
2,029
people served
0
health-based violations
Water source
GUP
Ownership
Local government
Counties served
Giles

Compliance record

Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.

0
health-based violations
299
violations on file
0
still open
ViolationTypeStatusPeriod
MR Monitoring Resolved 2024-10-01
MR Monitoring Resolved 2024-10-01
MR Monitoring Resolved 2024-10-01
MR Monitoring Resolved 2024-10-01
MR Monitoring Resolved 2024-01-01 → 2024-12-31
MR Monitoring Resolved 2024-01-01 → 2024-12-31
MR Monitoring Resolved 2024-01-01 → 2024-12-31
MR Monitoring Resolved 2024-01-01 → 2024-12-31
MR Monitoring Resolved 2022-01-01 → 2022-12-31
MR Monitoring Resolved 2022-01-01 → 2022-12-31

Other contaminants detected

Each bar shows the measured level as a share of the EPA limit: green is well under, amber is close to it, red is over. For lead and copper the limit applies to exactly the 90th-percentile figure shown, so red there means a real exceedance. For everything else the limit applies to a running annual average while the figure is the single worst sample on record — over 100% is worth reading, but is not by itself a violation. Formal violations are listed separately.
ContaminantLevel vs EPA limitDetection rateSourcePeriod
Copper
293 µg/L 23%
of the EPA limit 1300 µg/L
36/38 SYR4 2012–2018
TTHM
22.8 µg/L 29%
of the EPA limit 80 µg/L
25/27 SYR4 2012–2019
Chloroform
900 µg/L
No EPA limit set
24/26 SYR4 2012–2019
Dichloroacetic Acid
18.7 µg/L
No EPA limit set
22/23 SYR4 2012–2019
Lead
7 µg/L 47%
of the EPA limit 15 µg/L
22/38 SYR4 2012–2018
Total Haloacetic Acids (HAA5)
39 µg/L 65%
of the EPA limit 60 µg/L
22/23 SYR4 2012–2019
Bromodichloromethane
750 µg/L
No EPA limit set
21/27 SYR4 2012–2019
Trichloroacetic Acid
18.8 µg/L
No EPA limit set
20/23 SYR4 2012–2019
Lead
0.00077 mg/L 5.1%
of the EPA limit 0.0150 mg/L
15/15 LCR 2025
Monochloroacetic Acid
7.06 µg/L
No EPA limit set
14/23 SYR4 2012–2019
Dibromochloromethane
2.83 µg/L
No EPA limit set
13/29 SYR4 2012–2019
Dibromoacetic Acid
3.1 µg/L
No EPA limit set
1/23 SYR4 2012–2019
Monobromoacetic Acid
1.4 µg/L
No EPA limit set
1/23 SYR4 2012–2019
31 contaminants tested, none detected
11Cl-PF3OUdS4:2 Fts6:2 Fts8:2 Fts9Cl-PF3ONSAdonaBromoformHfpo-DaNetfosaaNfdhaNmefosaaPfbaPFBSPfdaPfdoaPfeesaPfhpaPfhpsPfhxaPFHXSPfmbaPfmpaPFNAPFOAPFOSPfpeaPfpesPftaPftrdaPfunaLithium

Utility contact

Contact
NICHOLSON, TERRY
Email
tnicholson@townofnarrows.org

Frequently asked questions about Narrows, Town of

Is Narrows, Town of tap water safe to drink?

EPA monitoring detected 13 contaminants in Narrows, Town of's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.

What contaminants were detected in Narrows, Town of's water?

EPA monitoring detected Copper, TTHM, Chloroform, Dichloroacetic Acid, Lead, and others. The full list with the level and data source for each is above.

How many people does Narrows, Town of serve?

Narrows, Town of reports serving 2,029 people in Virginia, per its EPA record.

Has Narrows, Town of had any water quality violations?

The EPA has 299 violations on file for Narrows, Town of, of which 0 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.

Where does this data come from?

Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.