Compliance record
Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.
| Violation | Type | Status | Period |
|---|---|---|---|
| MCL | Health-based | Resolved | 2008-09-01 → 2008-09-30 |
| MCL | Health-based | Resolved | 2008-09-01 → 2008-09-30 |
| MCL | Health-based | Resolved | 2008-09-01 → 2008-09-30 |
| MR | Monitoring | Resolved | 2019-12-30 |
| MR | Monitoring | Resolved | 2019-12-30 |
| MR | Monitoring | Resolved | 2019-12-30 |
| Other | Monitoring | Resolved | 2017-10-01 |
| Other | Monitoring | Resolved | 2017-10-01 |
| Other | Monitoring | Resolved | 2017-10-01 |
| MON | Monitoring | Resolved | 2016-12-01 → 2016-12-31 |
Other contaminants detected
| Contaminant | Level vs EPA limit | Detection rate | Source | Period |
|---|---|---|---|---|
| TTHM | 78.12 µg/L 98% of the EPA limit 80 µg/L
worst single sample: 112.4 µg/L | 69/73 | SYR4 | 2012–2019 |
| Total Haloacetic Acids (HAA5) | 31.7 µg/L 53% of the EPA limit 60 µg/L
worst single sample: 49.7 µg/L | 66/73 | SYR4 | 2012–2019 |
| Bromodichloromethane | 6.15 µg/L No EPA limit set
worst single sample: 8.4 µg/L | 56/61 | SYR4 | 2012–2019 |
| Chloroform | 76.525 µg/L No EPA limit set
worst single sample: 108.3 µg/L | 56/61 | SYR4 | 2012–2019 |
| Dichloroacetic Acid | 19.07 µg/L No EPA limit set
worst single sample: 27.6 µg/L | 52/58 | SYR4 | 2012–2019 |
| Trichloroacetic Acid | 17.74 µg/L No EPA limit set
worst single sample: 22.1 µg/L | 52/58 | SYR4 | 2012–2019 |
| Copper | 350.065 µg/L 27% of the EPA limit 1300 µg/L
worst single sample: 441 µg/L | 30/30 | SYR4 | 2013–2019 |
| Lead | 3.74 µg/L 25% of the EPA limit 15 µg/L
worst single sample: 4.1 µg/L | 27/30 | SYR4 | 2013–2019 |
| Lead | 0.0017 mg/L 11% of the EPA limit 0.0150 mg/L | 22/22 | LCR | 2025 |
| Dibromochloromethane | 1.335 µg/L No EPA limit set
worst single sample: 1.4 µg/L | 14/61 | SYR4 | 2012–2019 |
| Arsenic | 1.17 µg/L 12% of the EPA limit 10 µg/L
worst single sample: 1.2 µg/L | 3/3 | SYR4 | 2013–2019 |
| Barium | 84.97 µg/L 4.2% of the EPA limit 2000 µg/L
worst single sample: 85 µg/L | 3/3 | SYR4 | 2013–2019 |
| Cyanide | 2 µg/L 1% of the EPA limit 200 µg/L | 1/3 | SYR4 | 2013–2019 |
| Gross Alpha, Excl. Radon And U | 1.6 pCi/L 11% of the EPA limit 15 pCi/L | 1/2 | SYR4 | 2014–2017 |
60 contaminants tested, none detected
Utility contact
Frequently asked questions about Orangeville
Is Orangeville tap water safe to drink?
EPA monitoring detected 14 contaminants in Orangeville's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.
What contaminants were detected in Orangeville's water?
EPA monitoring detected TTHM, Total Haloacetic Acids (HAA5), Bromodichloromethane, Chloroform, Dichloroacetic Acid, and others. The full list with the level and data source for each is above.
How many people does Orangeville serve?
Orangeville reports serving 1,420 people in Utah, per its EPA record.
Has Orangeville had any water quality violations?
The EPA has 369 violations on file for Orangeville, of which 3 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.
Where does this data come from?
Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.