← Texas

Tap water quality report

Ramey Wsc

EPA monitoring tested this supplier for 109 contaminants and detected 21. A detection doesn't automatically mean the water is unsafe — the level and EPA source for each is below.

109
contaminants tested
21
detected
5,238
people served
0
health-based violations
Water source
Ground water
Ownership
Local government
Counties served
Wood

Compliance record

Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.

0
health-based violations
7
violations on file
1
still open
ViolationTypeStatusPeriod
Other Monitoring Resolved 2025-07-01
Other Monitoring Resolved 2025-07-01
Other Monitoring Unaddressed 2024-01-27
MR Monitoring Resolved 2022-07-01 → 2022-12-31
MR Monitoring Resolved 2022-07-01 → 2022-12-31
MR Monitoring Resolved 2022-07-01 → 2022-12-31
MR Monitoring Resolved 2013-12-30

Other contaminants detected

Each bar shows the measured level as a share of the EPA limit: green is well under, amber is close to it, red is over. For lead and copper the limit applies to exactly the 90th-percentile figure shown, so red there means a real exceedance. For everything else the limit applies to a running annual average while the figure is the 95th percentile of this system's samples — over 100% is worth reading, but is not by itself a violation. Where a single sample came in higher than that percentile, it is noted under the bar. Formal violations are listed separately.
ContaminantLevel vs EPA limitDetection rateSourcePeriod
Nitrate
80.075 µg/L 0.8%
of the EPA limit 10000 µg/L
worst single sample: 128 µg/L
74/94 SYR4 2012–2019
Copper
389.5 µg/L 30%
of the EPA limit 1300 µg/L
worst single sample: 603 µg/L
67/71 SYR4 2013–2019
Bromodichloromethane
9.57 µg/L
No EPA limit set
worst single sample: 12.4 µg/L
35/43 SYR4 2013–2019
Dibromochloromethane
16.57 µg/L
No EPA limit set
worst single sample: 24.7 µg/L
32/43 SYR4 2013–2019
Chloroform
4.862 µg/L
No EPA limit set
worst single sample: 7.68 µg/L
30/43 SYR4 2013–2019
Bromoform
16.52 µg/L
No EPA limit set
worst single sample: 31.9 µg/L
25/43 SYR4 2013–2019
Lead
1.62 µg/L 11%
of the EPA limit 15 µg/L
worst single sample: 2.71 µg/L
25/71 SYR4 2013–2019
Barium
86.5 µg/L 4.3%
of the EPA limit 2000 µg/L
worst single sample: 90 µg/L
15/15 SYR4 2013–2019
Lead
0.0 mg/L 0%
of the EPA limit 0.0150 mg/L
14/14 LCR 2023
Nitrate-Nitrite
62.65 µg/L 0.6%
of the EPA limit 10000 µg/L
worst single sample: 75 µg/L
14/18 SYR4 2012–2015
Fluoride
195.8 µg/L 4.9%
of the EPA limit 4000 µg/L
worst single sample: 198 µg/L
12/12 SYR4 2013–2019
TTHM
54.07 µg/L 68%
of the EPA limit 80 µg/L
worst single sample: 65.5 µg/L
10/12 SYR4 2013–2019
Total Haloacetic Acids (HAA5)
39.645 µg/L 66%
of the EPA limit 60 µg/L
worst single sample: 46.8 µg/L
10/11 SYR4 2013–2019
Dibromoacetic Acid
6.86 µg/L
No EPA limit set
worst single sample: 7.7 µg/L
9/11 SYR4 2013–2019
Lithium
12.1 µg/L
No EPA limit set
6/12 UCMR-5 2024
Chromium
1.98 µg/L 2%
of the EPA limit 100 µg/L
worst single sample: 2.1 µg/L
5/15 SYR4 2013–2019
Combined Radium (-226 And -228)
1.5 pCi/L 30%
of the EPA limit 5 pCi/L
5/5 SYR4 2015
Dichloroacetic Acid
4.98 µg/L
No EPA limit set
worst single sample: 5 µg/L
5/11 SYR4 2013–2019
Monochloroacetic Acid
26.36 µg/L
No EPA limit set
worst single sample: 27.8 µg/L
5/11 SYR4 2013–2019
Trichloroacetic Acid
6.06 µg/L
No EPA limit set
worst single sample: 6.3 µg/L
4/11 SYR4 2013–2019
Cyanide
21.8 µg/L 11%
of the EPA limit 200 µg/L
1/12 SYR4 2014–2017
88 contaminants tested, none detected
1,1,1-Trichloroethane1,1,2-Trichloroethane1,1-Dichloroethylene1,2,4-Trichlorobenzene1,2-DIBROMO-3-CHLOROPROPANE1,2-Dichloroethane1,2-Dichloropropane11Cl-PF3OUdS2,4,5-TP2,4-D4:2 Fts6:2 Fts8:2 Fts9Cl-PF3ONSAdonaAntimony, TotalArsenicAsbestosAtrazineBhc-GammaBenzeneBenzo(A)PyreneBeryllium, TotalChlorobenzeneCadmiumCarbofuranCarbon TetrachlorideChlordaneCombined UraniumDichloromethaneDalaponDi(2-ethylhexyl) AdipateDi(2-ethylhexyl) PhthalateDinosebEthylene DibromideEndrinEthylbenzeneGross Alpha, Excl. Radon And UGross Beta Particle ActivityHexachlorobenzeneHfpo-DaHeptachlorHeptachlor EpoxideHexachlorocyclopentadieneLassoMercuryMethoxychlorMonobromoacetic AcidNetfosaaNfdhaNmefosaaNitriteOxamylPfbaPFBSPfdaPfdoaPfeesaPfhpaPfhpsPfhxaPFHXSPfmbaPfmpaPFNAPFOAPFOSPfpeaPfpesPftaPftrdaPfunaPentachlorophenolPicloramSeleniumSimazineStyreneTetrachloroethyleneThallium, TotalTolueneToxapheneTrichloroethyleneVinyl ChlorideXylenes, Totalcis-1,2-DichloroethyleneO-DichlorobenzeneP-Dichlorobenzenetrans-1,2-Dichloroethylene

Utility contact

Contact
SPAN, BOBBY
Phone
903-569-6502

Frequently asked questions about Ramey Wsc

Is Ramey Wsc tap water safe to drink?

EPA monitoring detected 21 contaminants in Ramey Wsc's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.

What contaminants were detected in Ramey Wsc's water?

EPA monitoring detected Nitrate, Copper, Bromodichloromethane, Dibromochloromethane, Chloroform, and others. The full list with the level and data source for each is above.

How many people does Ramey Wsc serve?

Ramey Wsc reports serving 5,238 people in Texas, per its EPA record.

Has Ramey Wsc had any water quality violations?

The EPA has 7 violations on file for Ramey Wsc, of which 0 are health-based (a contaminant limit or required treatment was breached) and 1 remain open. The rest are monitoring or reporting failures.

Where does this data come from?

Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.