← Texas

Tap water quality report

Bruni Rural Wsc

EPA monitoring tested this supplier for 79 contaminants and detected 22. A detection doesn't automatically mean the water is unsafe — the level and EPA source for each is below.

79
contaminants tested
22
detected
350
people served
689
health-based violations
Water source
Ground water
Ownership
Local government
Counties served
Webb

Compliance record

Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.

689
health-based violations
929
violations on file
4
still open
ViolationTypeStatusPeriod
MCL Health-based Resolved 2024-01-01 → 2024-03-31
MCL Health-based Resolved 2024-01-01 → 2024-03-31
MCL Health-based Resolved 2024-01-01 → 2024-03-31
MCL Health-based Resolved 2024-01-01 → 2024-03-31
MCL Health-based Resolved 2024-01-01 → 2024-03-31
MCL Health-based Resolved 2023-10-01 → 2023-12-31
MCL Health-based Resolved 2023-10-01 → 2023-12-31
MCL Health-based Resolved 2023-10-01 → 2023-12-31
MCL Health-based Resolved 2023-10-01 → 2023-12-31
MCL Health-based Resolved 2023-10-01 → 2023-12-31

Other contaminants detected

Each bar shows the measured level as a share of the EPA limit: green is well under, amber is close to it, red is over. For lead and copper the limit applies to exactly the 90th-percentile figure shown, so red there means a real exceedance. For everything else the limit applies to a running annual average while the figure is the 95th percentile of this system's samples — over 100% is worth reading, but is not by itself a violation. Where a single sample came in higher than that percentile, it is noted under the bar. Formal violations are listed separately.
ContaminantLevel vs EPA limitDetection rateSourcePeriod
Arsenic
100.2 µg/L 1002%
of the EPA limit, at the 95th percentile of samples — 10 µg/L
worst single sample: 108 µg/L
50/50 SYR4 2012–2019
Nitrate
1240 µg/L 12%
of the EPA limit 10000 µg/L
20/26 SYR4 2012–2019
Copper
86.25 µg/L 6.6%
of the EPA limit 1300 µg/L
worst single sample: 150 µg/L
18/18 SYR4 2012–2019
Combined Uranium
29.08 µg/L 97%
of the EPA limit 30 µg/L
worst single sample: 35 µg/L
17/17 SYR4 2012–2019
Gross Alpha, Excl. Radon And U
14.2 pCi/L 95%
of the EPA limit 15 pCi/L
worst single sample: 15 pCi/L
17/17 SYR4 2012–2019
Gross Beta Particle Activity
18.2 pCi/L
No EPA limit set
17/17 SYR4 2012–2019
Combined Radium (-226 And -228)
1.251 pCi/L 25%
of the EPA limit 5 pCi/L
worst single sample: 1.9 pCi/L
12/17 SYR4 2012–2019
Bromoform
7.58 µg/L
No EPA limit set
worst single sample: 8.3 µg/L
10/10 SYR4 2013–2019
Dibromochloromethane
2.42 µg/L
No EPA limit set
worst single sample: 2.6 µg/L
10/10 SYR4 2013–2019
Lead
0.0 mg/L 0%
of the EPA limit 0.0150 mg/L
9/9 LCR 2025
Barium
52.8 µg/L 2.6%
of the EPA limit 2000 µg/L
worst single sample: 54 µg/L
4/4 SYR4 2012–2018
Fluoride
800 µg/L 20%
of the EPA limit 4000 µg/L
4/4 SYR4 2012–2018
Nitrate-Nitrite
1222.5 µg/L 12%
of the EPA limit 10000 µg/L
worst single sample: 1230 µg/L
4/5 SYR4 2012–2019
Selenium
22.16 µg/L 44%
of the EPA limit 50 µg/L
worst single sample: 23 µg/L
4/4 SYR4 2012–2018
Dibromoacetic Acid
3.96 µg/L
No EPA limit set
worst single sample: 4.1 µg/L
3/3 SYR4 2013–2019
Lead
2.7535 µg/L 18%
of the EPA limit 15 µg/L
worst single sample: 3 µg/L
3/18 SYR4 2012–2019
TTHM
10.11 µg/L 13%
of the EPA limit 80 µg/L
worst single sample: 10.2 µg/L
3/3 SYR4 2013–2019
Total Haloacetic Acids (HAA5)
3.96 µg/L 6.6%
of the EPA limit 60 µg/L
worst single sample: 4.1 µg/L
3/3 SYR4 2013–2019
Thallium, Total
0.4671 µg/L 23%
of the EPA limit 2 µg/L
worst single sample: 0.4890 µg/L
2/4 SYR4 2012–2018
Bromodichloromethane
0.5000 µg/L
No EPA limit set
1/10 SYR4 2013–2019
Cyanide
19 µg/L 9.5%
of the EPA limit 200 µg/L
1/4 SYR4 2012–2018
Chromium
0.2190 µg/L 0.2%
of the EPA limit 100 µg/L
1/4 SYR4 2012–2018
57 contaminants tested, none detected
1,1,1-Trichloroethane1,1,2-Trichloroethane1,1-Dichloroethylene1,2,4-Trichlorobenzene1,2-DIBROMO-3-CHLOROPROPANE1,2-Dichloroethane1,2-Dichloropropane2,4,5-TP2,4-DAntimony, TotalAsbestosAtrazineBhc-GammaBenzeneBenzo(A)PyreneBeryllium, TotalChlorobenzeneCadmiumCarbofuranCarbon TetrachlorideChlordaneChloroformDichloromethaneDalaponDi(2-ethylhexyl) AdipateDi(2-ethylhexyl) PhthalateDichloroacetic AcidDinosebEthylene DibromideEndrinEthylbenzeneHexachlorobenzeneHeptachlorHeptachlor EpoxideHexachlorocyclopentadieneLassoMercuryMethoxychlorMonobromoacetic AcidMonochloroacetic AcidNitriteOxamylPentachlorophenolPicloramSimazineStyreneTetrachloroethyleneTolueneToxapheneTrichloroacetic AcidTrichloroethyleneVinyl ChlorideXylenes, Totalcis-1,2-DichloroethyleneO-DichlorobenzeneP-Dichlorobenzenetrans-1,2-Dichloroethylene

Utility contact

Contact
GARZA, ALAN, R
Phone
956-286-0022

Frequently asked questions about Bruni Rural Wsc

Is Bruni Rural Wsc tap water safe to drink?

EPA monitoring detected 22 contaminants in Bruni Rural Wsc's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.

What contaminants were detected in Bruni Rural Wsc's water?

EPA monitoring detected Arsenic, Nitrate, Copper, Combined Uranium, Gross Alpha, Excl. Radon And U, and others. The full list with the level and data source for each is above.

How many people does Bruni Rural Wsc serve?

Bruni Rural Wsc reports serving 350 people in Texas, per its EPA record.

Has Bruni Rural Wsc had any water quality violations?

The EPA has 929 violations on file for Bruni Rural Wsc, of which 689 are health-based (a contaminant limit or required treatment was breached) and 4 remain open. The rest are monitoring or reporting failures.

Where does this data come from?

Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.