Compliance record
Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.
| Violation | Type | Status | Period |
|---|---|---|---|
| TT | Health-based | Resolved | 2021-02-01 → 2021-02-28 |
| TT | Health-based | Resolved | 2021-02-01 → 2021-02-28 |
| TT | Health-based | Resolved | 2021-02-01 → 2021-02-28 |
| TT | Health-based | Resolved | 2021-02-01 → 2021-02-28 |
| TT | Health-based | Resolved | 2021-02-01 → 2021-02-28 |
| TT | Health-based | Resolved | 2021-02-01 → 2021-02-28 |
| TT | Health-based | Resolved | 2021-02-01 → 2021-02-28 |
| TT | Health-based | Resolved | 2021-02-01 → 2021-02-28 |
| MCL | Health-based | Resolved | 2006-10-01 → 2006-10-31 |
| MCL | Health-based | Resolved | 2006-10-01 → 2006-10-31 |
PFAS detected
| Contaminant | Max | Detection rate | Period |
|---|---|---|---|
| Pfba | 0.0142 µg/L | 1/8 | 2023 |
Other contaminants detected
| Contaminant | Level vs EPA limit | Detection rate | Source | Period |
|---|---|---|---|---|
| Chloroform | 20.58 µg/L No EPA limit set
worst single sample: 71 µg/L | 63/67 | SYR4 | 2012–2019 |
| Copper | 140.05 µg/L 11% of the EPA limit 1300 µg/L
worst single sample: 372 µg/L | 54/68 | SYR4 | 2012–2019 |
| TTHM | 41.65 µg/L 52% of the EPA limit 80 µg/L
worst single sample: 103 µg/L | 51/55 | SYR4 | 2012–2019 |
| Total Haloacetic Acids (HAA5) | 26.5 µg/L 44% of the EPA limit 60 µg/L
worst single sample: 34.3 µg/L | 51/54 | SYR4 | 2012–2019 |
| Dichloroacetic Acid | 14.79 µg/L No EPA limit set
worst single sample: 22.3 µg/L | 47/54 | SYR4 | 2012–2019 |
| Bromodichloromethane | 15.525 µg/L No EPA limit set
worst single sample: 23.6 µg/L | 32/67 | SYR4 | 2012–2019 |
| Trichloroacetic Acid | 10.11 µg/L No EPA limit set
worst single sample: 12.9 µg/L | 30/54 | SYR4 | 2012–2019 |
| Monochloroacetic Acid | 4.085 µg/L No EPA limit set
worst single sample: 5.1 µg/L | 24/54 | SYR4 | 2012–2019 |
| Dibromochloromethane | 15.72 µg/L No EPA limit set
worst single sample: 16.1 µg/L | 20/67 | SYR4 | 2012–2019 |
| Bromoform | 5.639 µg/L No EPA limit set
worst single sample: 5.86 µg/L | 18/67 | SYR4 | 2012–2019 |
| Lead | 4.7225 µg/L 31% of the EPA limit 15 µg/L
worst single sample: 11.3 µg/L | 16/68 | SYR4 | 2012–2019 |
| Nitrate | 159 µg/L 1.6% of the EPA limit 10000 µg/L | 16/26 | SYR4 | 2012–2019 |
| Dibromoacetic Acid | 4.145 µg/L No EPA limit set
worst single sample: 4.6 µg/L | 14/54 | SYR4 | 2012–2019 |
| Lead | 0.0 mg/L 0% of the EPA limit 0.0150 mg/L | 13/13 | LCR | 2025 |
| Barium | 49.12 µg/L 2.5% of the EPA limit 2000 µg/L
worst single sample: 51.1 µg/L | 10/10 | SYR4 | 2012–2019 |
| Fluoride | 504.5 µg/L 13% of the EPA limit 4000 µg/L
worst single sample: 590 µg/L | 10/10 | SYR4 | 2012–2019 |
| Chromium | 1.36 µg/L 1.4% of the EPA limit 100 µg/L
worst single sample: 1.4 µg/L | 5/10 | SYR4 | 2012–2019 |
| Cyanide | 71.32 µg/L 36% of the EPA limit 200 µg/L
worst single sample: 76.6 µg/L | 4/7 | SYR4 | 2014–2019 |
| Di(2-ethylhexyl) Phthalate | 0.7550 µg/L 13% of the EPA limit 6 µg/L
worst single sample: 0.8000 µg/L | 4/21 | SYR4 | 2012–2019 |
| Monobromoacetic Acid | 2.055 µg/L No EPA limit set
worst single sample: 2.1 µg/L | 4/54 | SYR4 | 2012–2019 |
| Arsenic | 0.8039 µg/L 8% of the EPA limit 10 µg/L
worst single sample: 0.8110 µg/L | 3/10 | SYR4 | 2012–2019 |
| Atrazine | 0.1000 µg/L 3.3% of the EPA limit 3 µg/L | 2/21 | SYR4 | 2012–2019 |
| Selenium | 1.69 µg/L 3.4% of the EPA limit 50 µg/L
worst single sample: 1.7 µg/L | 2/10 | SYR4 | 2012–2019 |
| Lithium | 10.6 µg/L No EPA limit set | 2/8 | UCMR-5 | 2023 |
| Toluene | 4.32 µg/L 0.4% of the EPA limit 1000 µg/L | 1/14 | SYR4 | 2012–2019 |
82 contaminants tested, none detected
Utility contact
Frequently asked questions about City of Canton
Is City of Canton tap water safe to drink?
EPA monitoring detected 26 contaminants in City of Canton's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.
What contaminants were detected in City of Canton's water?
EPA monitoring detected Chloroform, Copper, TTHM, Total Haloacetic Acids (HAA5), Dichloroacetic Acid, and others. The full list with the level and data source for each is above.
How many people does City of Canton serve?
City of Canton reports serving 5,028 people in Texas, per its EPA record.
Has City of Canton had any water quality violations?
The EPA has 42 violations on file for City of Canton, of which 15 are health-based (a contaminant limit or required treatment was breached) and 2 remain open. The rest are monitoring or reporting failures.
Where does this data come from?
Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.