← Texas

Tap water quality report

Travis County Mud 4

EPA monitoring tested this supplier for 77 contaminants and detected 26. A detection doesn't automatically mean the water is unsafe — the level and EPA source for each is below.

77
contaminants tested
26
detected
6,816
people served
0
health-based violations
Water source
Surface water
Ownership
Local government
Counties served
Travis

Compliance record

Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.

0
health-based violations
14
violations on file
0
still open
ViolationTypeStatusPeriod
MR Monitoring Resolved 2025-09-29
MR Monitoring Resolved 2025-09-29
MR Monitoring Resolved 2025-04-01
MR Monitoring Resolved 2025-04-01
MR Monitoring Resolved 2024-07-01 → 2024-12-31
MR Monitoring Resolved 2024-07-01 → 2024-12-31
MR Monitoring Resolved 2024-07-01 → 2024-12-31
MR Monitoring Resolved 2024-07-01 → 2024-12-31
MON Monitoring Resolved 2024-05-01 → 2024-05-31
MON Monitoring Resolved 2024-05-01 → 2024-05-31

Other contaminants detected

Each bar shows the measured level as a share of the EPA limit: green is well under, amber is close to it, red is over. For lead and copper the limit applies to exactly the 90th-percentile figure shown, so red there means a real exceedance. For everything else the limit applies to a running annual average while the figure is the 95th percentile of this system's samples — over 100% is worth reading, but is not by itself a violation. Where a single sample came in higher than that percentile, it is noted under the bar. Formal violations are listed separately.
ContaminantLevel vs EPA limitDetection rateSourcePeriod
Bromodichloromethane
26.32 µg/L
No EPA limit set
worst single sample: 29.8 µg/L
45/45 SYR4 2012–2019
Chloroform
32.56 µg/L
No EPA limit set
worst single sample: 38.2 µg/L
45/45 SYR4 2012–2019
Dibromochloromethane
18.92 µg/L
No EPA limit set
worst single sample: 29.8 µg/L
33/45 SYR4 2012–2019
Dichloroacetic Acid
16.655 µg/L
No EPA limit set
worst single sample: 24.2 µg/L
30/30 SYR4 2012–2019
TTHM
73.85 µg/L 92%
of the EPA limit 80 µg/L
worst single sample: 83.8 µg/L
30/31 SYR4 2012–2019
Total Haloacetic Acids (HAA5)
36.49 µg/L 61%
of the EPA limit 60 µg/L
worst single sample: 52.6 µg/L
30/30 SYR4 2012–2019
Nitrate
841.5 µg/L 8.4%
of the EPA limit 10000 µg/L
worst single sample: 950 µg/L
28/28 SYR4 2012–2019
Trichloroacetic Acid
14.75 µg/L
No EPA limit set
worst single sample: 23.3 µg/L
20/30 SYR4 2012–2019
Dibromoacetic Acid
5.16 µg/L
No EPA limit set
worst single sample: 6.6 µg/L
19/30 SYR4 2012–2019
Bromoform
5.66 µg/L
No EPA limit set
worst single sample: 6.3 µg/L
17/45 SYR4 2012–2019
Copper
324.8 µg/L 25%
of the EPA limit 1300 µg/L
worst single sample: 344 µg/L
17/24 SYR4 2012–2018
Barium
70.88 µg/L 3.5%
of the EPA limit 2000 µg/L
worst single sample: 74.3 µg/L
13/13 SYR4 2012–2019
Fluoride
244 µg/L 6.1%
of the EPA limit 4000 µg/L
worst single sample: 250 µg/L
13/13 SYR4 2012–2019
Cyanide
116.5 µg/L 58%
of the EPA limit 200 µg/L
worst single sample: 120 µg/L
8/11 SYR4 2014–2019
Lead
13.046 µg/L 87%
of the EPA limit 15 µg/L
worst single sample: 17.9 µg/L
7/24 SYR4 2012–2018
Monochloroacetic Acid
5.38 µg/L
No EPA limit set
worst single sample: 5.8 µg/L
4/30 SYR4 2012–2019
Di(2-ethylhexyl) Phthalate
2.181 µg/L 36%
of the EPA limit 6 µg/L
worst single sample: 2.19 µg/L
3/17 SYR4 2012–2019
Lead
0.0 mg/L 0%
of the EPA limit 0.0150 mg/L
3/3 LCR 2025
Arsenic
2.1855 µg/L 22%
of the EPA limit 10 µg/L
worst single sample: 2.19 µg/L
2/13 SYR4 2012–2019
Atrazine
0.1480 µg/L 4.9%
of the EPA limit 3 µg/L
worst single sample: 0.1500 µg/L
2/17 SYR4 2012–2019
Monobromoacetic Acid
1.38 µg/L
No EPA limit set
worst single sample: 1.4 µg/L
2/30 SYR4 2012–2019
Chromium
0.6360 µg/L 0.6%
of the EPA limit 100 µg/L
1/13 SYR4 2012–2019
Gross Beta Particle Activity
5.2 pCi/L
No EPA limit set
1/3 SYR4 2015–2018
Selenium
3.79 µg/L 7.6%
of the EPA limit 50 µg/L
1/13 SYR4 2012–2019
Simazine
0.0500 µg/L 1.3%
of the EPA limit 4 µg/L
1/17 SYR4 2012–2019
Xylenes, Total
0.6000 µg/L 0%
of the EPA limit 10000 µg/L
1/15 SYR4 2012–2019
51 contaminants tested, none detected
1,1,1-Trichloroethane1,1,2-Trichloroethane1,1-Dichloroethylene1,2,4-Trichlorobenzene1,2-DIBROMO-3-CHLOROPROPANE1,2-Dichloroethane1,2-Dichloropropane2,4,5-TP2,4-DAntimony, TotalAsbestosBhc-GammaBenzeneBenzo(A)PyreneBeryllium, TotalChlorobenzeneCadmiumCarbofuranCarbon TetrachlorideChlordaneCombined UraniumDichloromethaneDalaponDi(2-ethylhexyl) AdipateDinosebEthylene DibromideEndrinEthylbenzeneGross Alpha, Excl. Radon And UHexachlorobenzeneHeptachlorHeptachlor EpoxideHexachlorocyclopentadieneLassoMercuryMethoxychlorNitriteOxamylPentachlorophenolPicloramStyreneTetrachloroethyleneThallium, TotalTolueneToxapheneTrichloroethyleneVinyl Chloridecis-1,2-DichloroethyleneO-DichlorobenzeneP-Dichlorobenzenetrans-1,2-Dichloroethylene

Utility contact

Contact
CONNOLLY, DOUG
Phone
512-423-6771

Frequently asked questions about Travis County Mud 4

Is Travis County Mud 4 tap water safe to drink?

EPA monitoring detected 26 contaminants in Travis County Mud 4's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.

What contaminants were detected in Travis County Mud 4's water?

EPA monitoring detected Bromodichloromethane, Chloroform, Dibromochloromethane, Dichloroacetic Acid, TTHM, and others. The full list with the level and data source for each is above.

How many people does Travis County Mud 4 serve?

Travis County Mud 4 reports serving 6,816 people in Texas, per its EPA record.

Has Travis County Mud 4 had any water quality violations?

The EPA has 14 violations on file for Travis County Mud 4, of which 0 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.

Where does this data come from?

Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.