Compliance record
Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.
| Violation | Type | Status | Period |
|---|---|---|---|
| TT | Health-based | Resolved | 2024-10-17 |
| TT | Health-based | Resolved | 2024-10-17 |
| TT | Health-based | Resolved | 2024-10-17 |
| TT | Health-based | Resolved | 2024-10-17 |
| MCL | Health-based | Resolved | 2023-07-01 → 2023-09-30 |
| MCL | Health-based | Resolved | 2023-07-01 → 2023-09-30 |
| MCL | Health-based | Resolved | 2023-07-01 → 2023-09-30 |
| MCL | Health-based | Resolved | 2023-07-01 → 2023-09-30 |
| MCL | Health-based | Resolved | 2023-07-01 → 2023-09-30 |
| MCL | Health-based | Resolved | 2023-07-01 → 2023-09-30 |
Other contaminants detected
| Contaminant | Level vs EPA limit | Detection rate | Source | Period |
|---|---|---|---|---|
| Nitrate | 12600 µg/L 126% of the EPA limit, at the 95th percentile of samples — 10000 µg/L
worst single sample: 14600 µg/L | 64/64 | SYR4 | 2012–2019 |
| Arsenic | 36.515 µg/L 365% of the EPA limit, at the 95th percentile of samples — 10 µg/L
worst single sample: 42 µg/L | 32/32 | SYR4 | 2012–2019 |
| Fluoride | 7621.5 µg/L 191% of the EPA limit, at the 95th percentile of samples — 4000 µg/L
worst single sample: 7720 µg/L | 32/32 | SYR4 | 2012–2019 |
| Copper | 277 µg/L 21% of the EPA limit 1300 µg/L
worst single sample: 310 µg/L | 12/12 | SYR4 | 2012–2017 |
| Nitrate-Nitrite | 13500 µg/L 135% of the EPA limit, at the 95th percentile of samples — 10000 µg/L
worst single sample: 14600 µg/L | 12/12 | SYR4 | 2012–2015 |
| Lead | 0.0 mg/L 0% of the EPA limit 0.0150 mg/L | 8/8 | LCR | 2025 |
| Bromoform | 14.2375 µg/L No EPA limit set
worst single sample: 17.2 µg/L | 6/8 | SYR4 | 2013–2019 |
| Dibromochloromethane | 4.038 µg/L No EPA limit set
worst single sample: 4.12 µg/L | 5/8 | SYR4 | 2013–2019 |
| Barium | 43.6 µg/L 2.2% of the EPA limit 2000 µg/L
worst single sample: 44 µg/L | 3/3 | SYR4 | 2012–2018 |
| Bromodichloromethane | 1.867 µg/L No EPA limit set
worst single sample: 1.9 µg/L | 3/8 | SYR4 | 2013–2019 |
| Dibromoacetic Acid | 4.67 µg/L No EPA limit set
worst single sample: 4.9 µg/L | 3/3 | SYR4 | 2013–2019 |
| Lead | 3.49 µg/L 23% of the EPA limit 15 µg/L
worst single sample: 3.7 µg/L | 3/12 | SYR4 | 2012–2017 |
| Selenium | 29.19 µg/L 58% of the EPA limit 50 µg/L
worst single sample: 30.1 µg/L | 3/3 | SYR4 | 2012–2018 |
| TTHM | 22.69 µg/L 28% of the EPA limit 80 µg/L
worst single sample: 24.2 µg/L | 3/3 | SYR4 | 2013–2019 |
| Total Haloacetic Acids (HAA5) | 5.57 µg/L 9.3% of the EPA limit 60 µg/L
worst single sample: 5.9 µg/L | 3/3 | SYR4 | 2013–2019 |
| Antimony, Total | 0.2700 µg/L 4.5% of the EPA limit 6 µg/L | 1/3 | SYR4 | 2012–2018 |
| Chloroform | 1.26 µg/L No EPA limit set | 1/8 | SYR4 | 2013–2019 |
| Chromium | 1.6 µg/L 1.6% of the EPA limit 100 µg/L | 1/3 | SYR4 | 2012–2018 |
| Combined Uranium | 9.8 µg/L 33% of the EPA limit 30 µg/L | 1/1 | SYR4 | 2015 |
| Gross Alpha, Excl. Radon And U | 1 pCi/L 6.7% of the EPA limit 15 pCi/L | 1/1 | SYR4 | 2015 |
| Gross Beta Particle Activity | 13.3 pCi/L No EPA limit set | 1/1 | SYR4 | 2015 |
| Monobromoacetic Acid | 1 µg/L No EPA limit set | 1/3 | SYR4 | 2013–2019 |
57 contaminants tested, none detected
Utility contact
Frequently asked questions about City of Wellman
Is City of Wellman tap water safe to drink?
EPA monitoring detected 22 contaminants in City of Wellman's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.
What contaminants were detected in City of Wellman's water?
EPA monitoring detected Nitrate, Arsenic, Fluoride, Copper, Nitrate-Nitrite, and others. The full list with the level and data source for each is above.
How many people does City of Wellman serve?
City of Wellman reports serving 200 people in Texas, per its EPA record.
Has City of Wellman had any water quality violations?
The EPA has 1257 violations on file for City of Wellman, of which 1059 are health-based (a contaminant limit or required treatment was breached) and 1 remain open. The rest are monitoring or reporting failures.
Where does this data come from?
Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.