← Texas

Tap water quality report

City of Wellman

EPA monitoring tested this supplier for 79 contaminants and detected 22. A detection doesn't automatically mean the water is unsafe — the level and EPA source for each is below.

79
contaminants tested
22
detected
200
people served
1,059
health-based violations
Water source
Ground water
Ownership
Local government
Counties served
Terry

Compliance record

Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.

1,059
health-based violations
1,257
violations on file
1
still open
ViolationTypeStatusPeriod
TT Health-based Resolved 2024-10-17
TT Health-based Resolved 2024-10-17
TT Health-based Resolved 2024-10-17
TT Health-based Resolved 2024-10-17
MCL Health-based Resolved 2023-07-01 → 2023-09-30
MCL Health-based Resolved 2023-07-01 → 2023-09-30
MCL Health-based Resolved 2023-07-01 → 2023-09-30
MCL Health-based Resolved 2023-07-01 → 2023-09-30
MCL Health-based Resolved 2023-07-01 → 2023-09-30
MCL Health-based Resolved 2023-07-01 → 2023-09-30

Other contaminants detected

Each bar shows the measured level as a share of the EPA limit: green is well under, amber is close to it, red is over. For lead and copper the limit applies to exactly the 90th-percentile figure shown, so red there means a real exceedance. For everything else the limit applies to a running annual average while the figure is the 95th percentile of this system's samples — over 100% is worth reading, but is not by itself a violation. Where a single sample came in higher than that percentile, it is noted under the bar. Formal violations are listed separately.
ContaminantLevel vs EPA limitDetection rateSourcePeriod
Nitrate
12600 µg/L 126%
of the EPA limit, at the 95th percentile of samples — 10000 µg/L
worst single sample: 14600 µg/L
64/64 SYR4 2012–2019
Arsenic
36.515 µg/L 365%
of the EPA limit, at the 95th percentile of samples — 10 µg/L
worst single sample: 42 µg/L
32/32 SYR4 2012–2019
Fluoride
7621.5 µg/L 191%
of the EPA limit, at the 95th percentile of samples — 4000 µg/L
worst single sample: 7720 µg/L
32/32 SYR4 2012–2019
Copper
277 µg/L 21%
of the EPA limit 1300 µg/L
worst single sample: 310 µg/L
12/12 SYR4 2012–2017
Nitrate-Nitrite
13500 µg/L 135%
of the EPA limit, at the 95th percentile of samples — 10000 µg/L
worst single sample: 14600 µg/L
12/12 SYR4 2012–2015
Lead
0.0 mg/L 0%
of the EPA limit 0.0150 mg/L
8/8 LCR 2025
Bromoform
14.2375 µg/L
No EPA limit set
worst single sample: 17.2 µg/L
6/8 SYR4 2013–2019
Dibromochloromethane
4.038 µg/L
No EPA limit set
worst single sample: 4.12 µg/L
5/8 SYR4 2013–2019
Barium
43.6 µg/L 2.2%
of the EPA limit 2000 µg/L
worst single sample: 44 µg/L
3/3 SYR4 2012–2018
Bromodichloromethane
1.867 µg/L
No EPA limit set
worst single sample: 1.9 µg/L
3/8 SYR4 2013–2019
Dibromoacetic Acid
4.67 µg/L
No EPA limit set
worst single sample: 4.9 µg/L
3/3 SYR4 2013–2019
Lead
3.49 µg/L 23%
of the EPA limit 15 µg/L
worst single sample: 3.7 µg/L
3/12 SYR4 2012–2017
Selenium
29.19 µg/L 58%
of the EPA limit 50 µg/L
worst single sample: 30.1 µg/L
3/3 SYR4 2012–2018
TTHM
22.69 µg/L 28%
of the EPA limit 80 µg/L
worst single sample: 24.2 µg/L
3/3 SYR4 2013–2019
Total Haloacetic Acids (HAA5)
5.57 µg/L 9.3%
of the EPA limit 60 µg/L
worst single sample: 5.9 µg/L
3/3 SYR4 2013–2019
Antimony, Total
0.2700 µg/L 4.5%
of the EPA limit 6 µg/L
1/3 SYR4 2012–2018
Chloroform
1.26 µg/L
No EPA limit set
1/8 SYR4 2013–2019
Chromium
1.6 µg/L 1.6%
of the EPA limit 100 µg/L
1/3 SYR4 2012–2018
Combined Uranium
9.8 µg/L 33%
of the EPA limit 30 µg/L
1/1 SYR4 2015
Gross Alpha, Excl. Radon And U
1 pCi/L 6.7%
of the EPA limit 15 pCi/L
1/1 SYR4 2015
Gross Beta Particle Activity
13.3 pCi/L
No EPA limit set
1/1 SYR4 2015
Monobromoacetic Acid
1 µg/L
No EPA limit set
1/3 SYR4 2013–2019
57 contaminants tested, none detected
1,1,1-Trichloroethane1,1,2-Trichloroethane1,1-Dichloroethylene1,2,4-Trichlorobenzene1,2-DIBROMO-3-CHLOROPROPANE1,2-Dichloroethane1,2-Dichloropropane2,4,5-TP2,4-DAsbestosAtrazineBhc-GammaBenzeneBenzo(A)PyreneBeryllium, TotalChlorobenzeneCyanideCadmiumCarbofuranCarbon TetrachlorideChlordaneCombined Radium (-226 And -228)DichloromethaneDalaponDi(2-ethylhexyl) AdipateDi(2-ethylhexyl) PhthalateDichloroacetic AcidDinosebEthylene DibromideEndrinEthylbenzeneHexachlorobenzeneHeptachlorHeptachlor EpoxideHexachlorocyclopentadieneLassoMercuryMethoxychlorMonochloroacetic AcidNitriteOxamylPentachlorophenolPicloramSimazineStyreneTetrachloroethyleneThallium, TotalTolueneToxapheneTrichloroacetic AcidTrichloroethyleneVinyl ChlorideXylenes, Totalcis-1,2-DichloroethyleneO-DichlorobenzeneP-Dichlorobenzenetrans-1,2-Dichloroethylene

Utility contact

Contact
GARZA, EDDIE
Phone
806-441-2857

Frequently asked questions about City of Wellman

Is City of Wellman tap water safe to drink?

EPA monitoring detected 22 contaminants in City of Wellman's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.

What contaminants were detected in City of Wellman's water?

EPA monitoring detected Nitrate, Arsenic, Fluoride, Copper, Nitrate-Nitrite, and others. The full list with the level and data source for each is above.

How many people does City of Wellman serve?

City of Wellman reports serving 200 people in Texas, per its EPA record.

Has City of Wellman had any water quality violations?

The EPA has 1257 violations on file for City of Wellman, of which 1059 are health-based (a contaminant limit or required treatment was breached) and 1 remain open. The rest are monitoring or reporting failures.

Where does this data come from?

Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.