← Texas

Tap water quality report

Sand Flat Wsc

EPA monitoring tested this supplier for 109 contaminants and detected 17. A detection doesn't automatically mean the water is unsafe — the level and EPA source for each is below.

109
contaminants tested
17
detected
4,569
people served
0
health-based violations
Water source
Ground water
Ownership
Local government
Counties served
Smith

Compliance record

Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.

0
health-based violations
59
violations on file
1
still open
ViolationTypeStatusPeriod
Other Monitoring Unaddressed 2023-02-13
MR Monitoring Resolved 2022-01-01
MR Monitoring Resolved 2022-01-01
MR Monitoring Resolved 2022-01-01
Other Monitoring Resolved 2021-03-15
Other Monitoring Resolved 2021-03-15
MR Monitoring Resolved 2019-10-01
MR Monitoring Resolved 2019-10-01
MR Monitoring Resolved 2019-10-01
MR Monitoring Resolved 2019-10-01

Other contaminants detected

Each bar shows the measured level as a share of the EPA limit: green is well under, amber is close to it, red is over. For lead and copper the limit applies to exactly the 90th-percentile figure shown, so red there means a real exceedance. For everything else the limit applies to a running annual average while the figure is the 95th percentile of this system's samples — over 100% is worth reading, but is not by itself a violation. Where a single sample came in higher than that percentile, it is noted under the bar. Formal violations are listed separately.
ContaminantLevel vs EPA limitDetection rateSourcePeriod
Copper
444.35 µg/L 34%
of the EPA limit 1300 µg/L
worst single sample: 796 µg/L
52/66 SYR4 2013–2019
Nitrate
32.5 µg/L 0.3%
of the EPA limit 10000 µg/L
worst single sample: 32.6 µg/L
44/48 SYR4 2012–2019
Lead
2.09 µg/L 14%
of the EPA limit 15 µg/L
worst single sample: 2.62 µg/L
24/66 SYR4 2013–2019
Dibromochloromethane
3.479 µg/L
No EPA limit set
worst single sample: 3.7 µg/L
18/24 SYR4 2013–2019
Bromodichloromethane
4.876 µg/L
No EPA limit set
worst single sample: 4.9 µg/L
17/24 SYR4 2013–2019
Chloroform
4.658 µg/L
No EPA limit set
worst single sample: 5.33 µg/L
17/24 SYR4 2013–2019
Lead
0.0 mg/L 0%
of the EPA limit 0.0150 mg/L
14/14 LCR 2025
Nitrate-Nitrite
31.5 µg/L 0.3%
of the EPA limit 10000 µg/L
worst single sample: 32.5 µg/L
9/9 SYR4 2012–2015
Barium
24.91 µg/L 1.2%
of the EPA limit 2000 µg/L
worst single sample: 25 µg/L
7/7 SYR4 2013–2019
Fluoride
167.5 µg/L 4.2%
of the EPA limit 4000 µg/L
worst single sample: 169 µg/L
7/7 SYR4 2013–2019
TTHM
13.33 µg/L 17%
of the EPA limit 80 µg/L
worst single sample: 13.6 µg/L
7/8 SYR4 2013–2019
Dichloroacetic Acid
1.875 µg/L
No EPA limit set
worst single sample: 1.9 µg/L
6/8 SYR4 2013–2019
Total Haloacetic Acids (HAA5)
3.9 µg/L 6.5%
of the EPA limit 60 µg/L
worst single sample: 4.1 µg/L
6/8 SYR4 2013–2019
Trichloroacetic Acid
1.4 µg/L
No EPA limit set
5/8 SYR4 2013–2019
Combined Radium (-226 And -228)
2.685 pCi/L 54%
of the EPA limit 5 pCi/L
worst single sample: 2.7 pCi/L
4/4 SYR4 2012–2015
Chromium
1.371 µg/L 1.4%
of the EPA limit 100 µg/L
worst single sample: 1.4 µg/L
2/7 SYR4 2013–2019
Dibromoacetic Acid
1.095 µg/L
No EPA limit set
worst single sample: 1.1 µg/L
2/8 SYR4 2013–2019
92 contaminants tested, none detected
1,1,1-Trichloroethane1,1,2-Trichloroethane1,1-Dichloroethylene1,2,4-Trichlorobenzene1,2-DIBROMO-3-CHLOROPROPANE1,2-Dichloroethane1,2-Dichloropropane11Cl-PF3OUdS2,4,5-TP2,4-D4:2 Fts6:2 Fts8:2 Fts9Cl-PF3ONSAdonaAntimony, TotalArsenicAsbestosAtrazineBhc-GammaBenzeneBenzo(A)PyreneBeryllium, TotalBromoformChlorobenzeneCyanideCadmiumCarbofuranCarbon TetrachlorideChlordaneCombined UraniumDichloromethaneDalaponDi(2-ethylhexyl) AdipateDi(2-ethylhexyl) PhthalateDinosebEthylene DibromideEndrinEthylbenzeneGross Alpha, Excl. Radon And UGross Beta Particle ActivityHexachlorobenzeneHfpo-DaHeptachlorHeptachlor EpoxideHexachlorocyclopentadieneLassoMercuryMethoxychlorMonobromoacetic AcidMonochloroacetic AcidNetfosaaNfdhaNmefosaaNitriteOxamylPfbaPFBSPfdaPfdoaPfeesaPfhpaPfhpsPfhxaPFHXSPfmbaPfmpaPFNAPFOAPFOSPfpeaPfpesPftaPftrdaPfunaPentachlorophenolPicloramSeleniumSimazineStyreneTetrachloroethyleneThallium, TotalTolueneToxapheneTrichloroethyleneVinyl ChlorideXylenes, Totalcis-1,2-DichloroethyleneLithiumO-DichlorobenzeneP-Dichlorobenzenetrans-1,2-Dichloroethylene

Utility contact

Contact
LANGLEY, KENNETH
Phone
903-526-5243

Frequently asked questions about Sand Flat Wsc

Is Sand Flat Wsc tap water safe to drink?

EPA monitoring detected 17 contaminants in Sand Flat Wsc's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.

What contaminants were detected in Sand Flat Wsc's water?

EPA monitoring detected Copper, Nitrate, Lead, Dibromochloromethane, Bromodichloromethane, and others. The full list with the level and data source for each is above.

How many people does Sand Flat Wsc serve?

Sand Flat Wsc reports serving 4,569 people in Texas, per its EPA record.

Has Sand Flat Wsc had any water quality violations?

The EPA has 59 violations on file for Sand Flat Wsc, of which 0 are health-based (a contaminant limit or required treatment was breached) and 1 remain open. The rest are monitoring or reporting failures.

Where does this data come from?

Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.