Compliance record
Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.
| Violation | Type | Status | Period |
|---|---|---|---|
| Other | Monitoring | Resolved | 2025-07-01 |
| Other | Monitoring | Resolved | 2025-07-01 |
| MR | Monitoring | Resolved | 2025-01-01 → 2025-03-31 |
| MR | Monitoring | Resolved | 2025-01-01 → 2025-03-31 |
| MR | Monitoring | Resolved | 2025-01-01 → 2025-03-31 |
| MR | Monitoring | Resolved | 2025-01-01 → 2025-03-31 |
| MR | Monitoring | Unaddressed | 2024-12-30 |
| MR | Monitoring | Resolved | 2016-07-01 → 2016-12-31 |
| MR | Monitoring | Resolved | 2016-07-01 → 2016-12-31 |
| MR | Monitoring | Resolved | 2016-07-01 → 2016-12-31 |
Other contaminants detected
| Contaminant | Level vs EPA limit | Detection rate | Source | Period |
|---|---|---|---|---|
| Copper | 610.65 µg/L 47% of the EPA limit 1300 µg/L
worst single sample: 690 µg/L | 108/109 | SYR4 | 2013–2017 |
| Nitrate | 34.3 µg/L 0.3% of the EPA limit 10000 µg/L
worst single sample: 45 µg/L | 58/68 | SYR4 | 2012–2019 |
| Bromodichloromethane | 9.0655 µg/L No EPA limit set
worst single sample: 10.1 µg/L | 28/35 | SYR4 | 2013–2019 |
| Chloroform | 8.503 µg/L No EPA limit set
worst single sample: 10.8 µg/L | 28/35 | SYR4 | 2013–2019 |
| Dibromochloromethane | 7.491 µg/L No EPA limit set
worst single sample: 8.28 µg/L | 27/35 | SYR4 | 2013–2019 |
| Lead | 3.769 µg/L 25% of the EPA limit 15 µg/L
worst single sample: 7 µg/L | 23/109 | SYR4 | 2013–2017 |
| Lead | 0.0 mg/L 0% of the EPA limit 0.0150 mg/L | 16/16 | LCR | 2024 |
| Barium | 93.3 µg/L 4.7% of the EPA limit 2000 µg/L
worst single sample: 96 µg/L | 10/10 | SYR4 | 2013–2019 |
| Fluoride | 183.05 µg/L 4.6% of the EPA limit 4000 µg/L
worst single sample: 188 µg/L | 10/10 | SYR4 | 2013–2019 |
| TTHM | 26.52 µg/L 33% of the EPA limit 80 µg/L
worst single sample: 29.6 µg/L | 9/10 | SYR4 | 2013–2019 |
| Bromoform | 1.5365 µg/L No EPA limit set
worst single sample: 1.54 µg/L | 8/35 | SYR4 | 2013–2019 |
| Nitrate-Nitrite | 30.125 µg/L 0.3% of the EPA limit 10000 µg/L
worst single sample: 31 µg/L | 8/12 | SYR4 | 2012–2015 |
| Total Haloacetic Acids (HAA5) | 9.115 µg/L 15% of the EPA limit 60 µg/L
worst single sample: 10.9 µg/L | 8/9 | SYR4 | 2013–2019 |
| Dichloroacetic Acid | 3.91 µg/L No EPA limit set
worst single sample: 4.3 µg/L | 7/9 | SYR4 | 2013–2019 |
| Trichloroacetic Acid | 3.15 µg/L No EPA limit set
worst single sample: 3.3 µg/L | 7/9 | SYR4 | 2013–2019 |
| Chromium | 2.2 µg/L 2.2% of the EPA limit 100 µg/L
worst single sample: 2.4 µg/L | 5/10 | SYR4 | 2013–2019 |
| Combined Radium (-226 And -228) | 1.5 pCi/L 30% of the EPA limit 5 pCi/L | 4/4 | SYR4 | 2013–2016 |
| Dibromoacetic Acid | 1.68 µg/L No EPA limit set
worst single sample: 1.7 µg/L | 3/9 | SYR4 | 2013–2019 |
| Cyanide | 41.0065 µg/L 21% of the EPA limit 200 µg/L
worst single sample: 42.9 µg/L | 2/9 | SYR4 | 2014–2017 |
| Ethylbenzene | 1.37 µg/L 0.2% of the EPA limit 700 µg/L | 1/26 | SYR4 | 2013–2019 |
| Mercury | 0.4220 µg/L 21% of the EPA limit 2 µg/L | 1/10 | SYR4 | 2013–2019 |
| Monochloroacetic Acid | 3.3 µg/L No EPA limit set | 1/9 | SYR4 | 2013–2019 |
| Xylenes, Total | 20.1 µg/L 0.2% of the EPA limit 10000 µg/L | 1/26 | SYR4 | 2013–2019 |
86 contaminants tested, none detected
Utility contact
Frequently asked questions about Crystal Systems
Is Crystal Systems tap water safe to drink?
EPA monitoring detected 23 contaminants in Crystal Systems's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.
What contaminants were detected in Crystal Systems's water?
EPA monitoring detected Copper, Nitrate, Bromodichloromethane, Chloroform, Dibromochloromethane, and others. The full list with the level and data source for each is above.
How many people does Crystal Systems serve?
Crystal Systems reports serving 3,879 people in Texas, per its EPA record.
Has Crystal Systems had any water quality violations?
The EPA has 28 violations on file for Crystal Systems, of which 0 are health-based (a contaminant limit or required treatment was breached) and 1 remain open. The rest are monitoring or reporting failures.
Where does this data come from?
Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.