Compliance record
Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.
| Violation | Type | Status | Period |
|---|---|---|---|
| MR | Monitoring | Resolved | 2025-10-01 → 2025-12-31 |
| MR | Monitoring | Resolved | 2025-10-01 → 2025-12-31 |
| MR | Monitoring | Resolved | 2025-10-01 → 2025-12-31 |
| MR | Monitoring | Resolved | 2025-10-01 → 2025-12-31 |
| MR | Monitoring | Resolved | 2015-10-01 |
| MR | Monitoring | Resolved | 2015-10-01 |
| MR | Monitoring | Resolved | 2015-10-01 |
| MR | Monitoring | Resolved | 2015-10-01 |
Other contaminants detected
| Contaminant | Level vs EPA limit | Detection rate | Source | Period |
|---|---|---|---|---|
| Bromodichloromethane | 25.98 µg/L No EPA limit set
worst single sample: 27.1 µg/L | 22/22 | SYR4 | 2012–2019 |
| Chloroform | 27.435 µg/L No EPA limit set
worst single sample: 32.1 µg/L | 22/22 | SYR4 | 2012–2019 |
| Dibromochloromethane | 21.175 µg/L No EPA limit set
worst single sample: 21.6 µg/L | 22/22 | SYR4 | 2012–2019 |
| Copper | 143 µg/L 11% of the EPA limit 1300 µg/L
worst single sample: 208 µg/L | 21/21 | SYR4 | 2016–2019 |
| Bromoform | 3.149 µg/L No EPA limit set
worst single sample: 3.37 µg/L | 18/22 | SYR4 | 2012–2019 |
| Lead | 2.92 µg/L 19% of the EPA limit 15 µg/L
worst single sample: 3.22 µg/L | 16/21 | SYR4 | 2016–2019 |
| Dichloroacetic Acid | 13.075 µg/L No EPA limit set
worst single sample: 13.4 µg/L | 14/14 | SYR4 | 2012–2019 |
| Nitrate | 39.5 µg/L 0.4% of the EPA limit 10000 µg/L | 14/16 | SYR4 | 2012–2019 |
| TTHM | 74.685 µg/L 93% of the EPA limit 80 µg/L
worst single sample: 76.7 µg/L | 14/15 | SYR4 | 2012–2019 |
| Total Haloacetic Acids (HAA5) | 29.75 µg/L 50% of the EPA limit 60 µg/L
worst single sample: 30.4 µg/L | 14/14 | SYR4 | 2012–2019 |
| Trichloroacetic Acid | 13.025 µg/L No EPA limit set
worst single sample: 14 µg/L | 14/14 | SYR4 | 2012–2019 |
| Dibromoacetic Acid | 5.38 µg/L No EPA limit set
worst single sample: 5.8 µg/L | 13/14 | SYR4 | 2012–2019 |
| Lead | 0.0028 mg/L 18% of the EPA limit 0.0150 mg/L | 8/8 | LCR | 2025 |
| Monochloroacetic Acid | 2.6 µg/L No EPA limit set
worst single sample: 2.7 µg/L | 5/14 | SYR4 | 2012–2019 |
| Barium | 6.85 µg/L 0.3% of the EPA limit 2000 µg/L
worst single sample: 6.9 µg/L | 2/2 | SYR4 | 2016–2019 |
| Chromium | 1.775 µg/L 1.8% of the EPA limit 100 µg/L
worst single sample: 1.8 µg/L | 2/2 | SYR4 | 2016–2019 |
| Fluoride | 426.2 µg/L 11% of the EPA limit 4000 µg/L
worst single sample: 432 µg/L | 2/2 | SYR4 | 2014–2017 |
| Nitrate-Nitrite | 38.8 µg/L 0.4% of the EPA limit 10000 µg/L
worst single sample: 39.5 µg/L | 2/3 | SYR4 | 2012–2015 |
| Combined Radium (-226 And -228) | 1.5 pCi/L 30% of the EPA limit 5 pCi/L | 1/1 | SYR4 | 2015 |
| Di(2-ethylhexyl) Phthalate | 0.5000 µg/L 8.3% of the EPA limit 6 µg/L | 1/6 | SYR4 | 2014–2019 |
| Xylenes, Total | 0.5700 µg/L 0% of the EPA limit 10000 µg/L | 1/8 | SYR4 | 2012–2019 |
58 contaminants tested, none detected
Utility contact
Frequently asked questions about South Sabine Wsc
Is South Sabine Wsc tap water safe to drink?
EPA monitoring detected 21 contaminants in South Sabine Wsc's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.
What contaminants were detected in South Sabine Wsc's water?
EPA monitoring detected Bromodichloromethane, Chloroform, Dibromochloromethane, Copper, Bromoform, and others. The full list with the level and data source for each is above.
How many people does South Sabine Wsc serve?
South Sabine Wsc reports serving 1,981 people in Texas, per its EPA record.
Has South Sabine Wsc had any water quality violations?
The EPA has 8 violations on file for South Sabine Wsc, of which 0 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.
Where does this data come from?
Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.