← Texas

Tap water quality report

City of Hemphill

EPA monitoring tested this supplier for 77 contaminants and detected 18. A detection doesn't automatically mean the water is unsafe — the level and EPA source for each is below.

77
contaminants tested
18
detected
1,779
people served
84
health-based violations
Water source
Surface water
Ownership
Local government
Counties served
Sabine

Compliance record

Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.

84
health-based violations
118
violations on file
0
still open
ViolationTypeStatusPeriod
TT Health-based Resolved 2010-02-01 → 2010-02-28
TT Health-based Resolved 2010-02-01 → 2010-02-28
TT Health-based Resolved 2010-02-01 → 2010-02-28
TT Health-based Resolved 2010-02-01 → 2010-02-28
TT Health-based Resolved 2010-02-01 → 2010-02-28
TT Health-based Resolved 2010-02-01 → 2010-02-28
TT Health-based Resolved 2010-02-01 → 2010-02-28
TT Health-based Resolved 2010-01-01 → 2010-01-31
TT Health-based Resolved 2010-01-01 → 2010-01-31
TT Health-based Resolved 2010-01-01 → 2010-01-31

Other contaminants detected

Each bar shows the measured level as a share of the EPA limit: green is well under, amber is close to it, red is over. For lead and copper the limit applies to exactly the 90th-percentile figure shown, so red there means a real exceedance. For everything else the limit applies to a running annual average while the figure is the 95th percentile of this system's samples — over 100% is worth reading, but is not by itself a violation. Where a single sample came in higher than that percentile, it is noted under the bar. Formal violations are listed separately.
ContaminantLevel vs EPA limitDetection rateSourcePeriod
Chloroform
23.22 µg/L
No EPA limit set
worst single sample: 49.5 µg/L
35/35 SYR4 2012–2019
TTHM
40.16 µg/L 50%
of the EPA limit 80 µg/L
worst single sample: 57.8 µg/L
27/28 SYR4 2012–2019
Bromodichloromethane
9.5125 µg/L
No EPA limit set
worst single sample: 12.6 µg/L
26/35 SYR4 2012–2019
Copper
78.425 µg/L 6%
of the EPA limit 1300 µg/L
worst single sample: 83.5 µg/L
26/36 SYR4 2012–2017
Dichloroacetic Acid
23.075 µg/L
No EPA limit set
worst single sample: 34.9 µg/L
26/27 SYR4 2012–2019
Total Haloacetic Acids (HAA5)
31.925 µg/L 53%
of the EPA limit 60 µg/L
worst single sample: 52.2 µg/L
26/27 SYR4 2012–2019
Trichloroacetic Acid
6.86 µg/L
No EPA limit set
worst single sample: 10.5 µg/L
22/27 SYR4 2012–2019
Nitrate
183 µg/L 1.8%
of the EPA limit 10000 µg/L
18/18 SYR4 2012–2019
Monochloroacetic Acid
4.05 µg/L
No EPA limit set
worst single sample: 5.7 µg/L
16/27 SYR4 2012–2019
Barium
43.59 µg/L 2.2%
of the EPA limit 2000 µg/L
worst single sample: 44.5 µg/L
8/8 SYR4 2012–2019
Lead
0.0 mg/L 0%
of the EPA limit 0.0150 mg/L
8/8 LCR 2024
Dibromochloromethane
3.664 µg/L
No EPA limit set
worst single sample: 4 µg/L
7/35 SYR4 2012–2019
Lead
2.785 µg/L 19%
of the EPA limit 15 µg/L
worst single sample: 2.98 µg/L
6/36 SYR4 2012–2017
Fluoride
49.94 µg/L 1.2%
of the EPA limit 4000 µg/L
worst single sample: 50 µg/L
4/8 SYR4 2012–2019
Dibromoacetic Acid
1.47 µg/L
No EPA limit set
worst single sample: 1.5 µg/L
3/27 SYR4 2012–2019
Arsenic
0.3210 µg/L 3.2%
of the EPA limit 10 µg/L
1/8 SYR4 2012–2019
Cyanide
9.04 µg/L 4.5%
of the EPA limit 200 µg/L
1/6 SYR4 2014–2019
Thallium, Total
0.0110 µg/L 0.5%
of the EPA limit 2 µg/L
1/8 SYR4 2012–2019
59 contaminants tested, none detected
1,1,1-Trichloroethane1,1,2-Trichloroethane1,1-Dichloroethylene1,2,4-Trichlorobenzene1,2-DIBROMO-3-CHLOROPROPANE1,2-Dichloroethane1,2-Dichloropropane2,4,5-TP2,4-DAntimony, TotalAsbestosAtrazineBhc-GammaBenzeneBenzo(A)PyreneBeryllium, TotalBromoformChlorobenzeneCadmiumCarbofuranCarbon TetrachlorideChlordaneChromiumCombined UraniumDichloromethaneDalaponDi(2-ethylhexyl) AdipateDi(2-ethylhexyl) PhthalateDinosebEthylene DibromideEndrinEthylbenzeneGross Alpha, Excl. Radon And UGross Beta Particle ActivityHexachlorobenzeneHeptachlorHeptachlor EpoxideHexachlorocyclopentadieneLassoMercuryMethoxychlorMonobromoacetic AcidNitriteOxamylPentachlorophenolPicloramSeleniumSimazineStyreneTetrachloroethyleneTolueneToxapheneTrichloroethyleneVinyl ChlorideXylenes, Totalcis-1,2-DichloroethyleneO-DichlorobenzeneP-Dichlorobenzenetrans-1,2-Dichloroethylene

Utility contact

Contact
HAMILTON, ROBERT
Phone
409-787-2251

Frequently asked questions about City of Hemphill

Is City of Hemphill tap water safe to drink?

EPA monitoring detected 18 contaminants in City of Hemphill's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.

What contaminants were detected in City of Hemphill's water?

EPA monitoring detected Chloroform, TTHM, Bromodichloromethane, Copper, Dichloroacetic Acid, and others. The full list with the level and data source for each is above.

How many people does City of Hemphill serve?

City of Hemphill reports serving 1,779 people in Texas, per its EPA record.

Has City of Hemphill had any water quality violations?

The EPA has 118 violations on file for City of Hemphill, of which 84 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.

Where does this data come from?

Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.