Compliance record
Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.
| Violation | Type | Status | Period |
|---|---|---|---|
| MCL | Health-based | Resolved | 2009-08-01 → 2009-08-31 |
| MCL | Health-based | Resolved | 2009-08-01 → 2009-08-31 |
| MCL | Health-based | Resolved | 2009-08-01 → 2009-08-31 |
| MCL | Health-based | Resolved | 2007-10-01 → 2007-10-31 |
| MCL | Health-based | Resolved | 2007-10-01 → 2007-10-31 |
| MCL | Health-based | Resolved | 2007-10-01 → 2007-10-31 |
| MCL | Health-based | Resolved | 2007-10-01 → 2007-10-31 |
| MCL | Health-based | Resolved | 2007-10-01 → 2007-10-31 |
| Other | Monitoring | Resolved | 2025-07-01 |
| Other | Monitoring | Resolved | 2025-07-01 |
Other contaminants detected
| Contaminant | Level vs EPA limit | Detection rate | Source | Period |
|---|---|---|---|---|
| Nitrate | 2720 µg/L 27% of the EPA limit 10000 µg/L | 102/102 | SYR4 | 2012–2019 |
| Copper | 1760 µg/L 135% of the EPA limit, in the worst sample — 1300 µg/L | 91/91 | SYR4 | 2012–2018 |
| Dibromochloromethane | 10.2 µg/L No EPA limit set | 50/57 | SYR4 | 2012–2019 |
| Bromodichloromethane | 11.8 µg/L No EPA limit set | 41/57 | SYR4 | 2012–2019 |
| Bromoform | 10.5 µg/L No EPA limit set | 33/57 | SYR4 | 2012–2019 |
| Chloroform | 13.1 µg/L No EPA limit set | 23/57 | SYR4 | 2012–2019 |
| Fluoride | 806 µg/L 20% of the EPA limit 4000 µg/L | 19/19 | SYR4 | 2012–2019 |
| Nitrate-Nitrite | 2170 µg/L 22% of the EPA limit 10000 µg/L | 18/18 | SYR4 | 2012–2019 |
| Barium | 120 µg/L 6% of the EPA limit 2000 µg/L | 17/17 | SYR4 | 2012–2019 |
| Combined Radium (-226 And -228) | 7.4 pCi/L 148% of the EPA limit, in the worst sample — 5 pCi/L | 17/17 | SYR4 | 2012–2019 |
| Lead | 36.3 µg/L 242% of the EPA limit, in the worst sample — 15 µg/L | 17/91 | SYR4 | 2012–2018 |
| Lithium | 49 µg/L No EPA limit set | 15/15 | UCMR-5 | 2025 |
| Gross Alpha, Excl. Radon And U | 15 pCi/L 100% of the EPA limit 15 pCi/L | 14/18 | SYR4 | 2013–2019 |
| Combined Uranium | 4.7 µg/L 16% of the EPA limit 30 µg/L | 13/18 | SYR4 | 2013–2019 |
| Gross Beta Particle Activity | 9.6 pCi/L No EPA limit set | 12/21 | SYR4 | 2012–2019 |
| Chromium | 4 µg/L 4% of the EPA limit 100 µg/L | 10/17 | SYR4 | 2012–2019 |
| TTHM | 13.1 µg/L 16% of the EPA limit 80 µg/L | 8/10 | SYR4 | 2013–2019 |
| Lead | 0.0015 mg/L 10% of the EPA limit 0.0150 mg/L | 6/6 | LCR | 2024 |
| Selenium | 1.9 µg/L 3.8% of the EPA limit 50 µg/L | 4/17 | SYR4 | 2012–2019 |
| Total Haloacetic Acids (HAA5) | 2.7 µg/L 4.5% of the EPA limit 60 µg/L | 4/8 | SYR4 | 2013–2019 |
| Xylenes, Total | 5.69 µg/L 0.1% of the EPA limit 10000 µg/L | 4/49 | SYR4 | 2012–2019 |
| Arsenic | 3 µg/L 30% of the EPA limit 10 µg/L | 3/17 | SYR4 | 2012–2019 |
| Ethylbenzene | 0.8600 µg/L 0.1% of the EPA limit 700 µg/L | 3/49 | SYR4 | 2012–2019 |
| Monochloroacetic Acid | 2.7 µg/L No EPA limit set | 2/8 | SYR4 | 2013–2019 |
| Dibromoacetic Acid | 1.3 µg/L No EPA limit set | 1/8 | SYR4 | 2013–2019 |
| Dichloroacetic Acid | 1.3 µg/L No EPA limit set | 1/8 | SYR4 | 2013–2019 |
| Mercury | 0.1420 µg/L 7.1% of the EPA limit 2 µg/L | 1/17 | SYR4 | 2012–2019 |
| Trichloroacetic Acid | 1.3 µg/L No EPA limit set | 1/8 | SYR4 | 2013–2019 |
81 contaminants tested, none detected
Utility contact
Frequently asked questions about Town of Annetta Deer Creek
Is Town of Annetta Deer Creek tap water safe to drink?
EPA monitoring detected 28 contaminants in Town of Annetta Deer Creek's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.
What contaminants were detected in Town of Annetta Deer Creek's water?
EPA monitoring detected Nitrate, Copper, Dibromochloromethane, Bromodichloromethane, Bromoform, and others. The full list with the level and data source for each is above.
How many people does Town of Annetta Deer Creek serve?
Town of Annetta Deer Creek reports serving 2,418 people in Texas, per its EPA record.
Has Town of Annetta Deer Creek had any water quality violations?
The EPA has 25 violations on file for Town of Annetta Deer Creek, of which 8 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.
Where does this data come from?
Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.