Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.
| Violation | Type | Status | Period |
|---|---|---|---|
| MCL | Health-based | Resolved | 2016-07-01 → 2016-09-30 |
| MCL | Health-based | Resolved | 2016-07-01 → 2016-09-30 |
| MCL | Health-based | Resolved | 2016-07-01 → 2016-09-30 |
| MCL | Health-based | Resolved | 2016-07-01 → 2016-09-30 |
| MCL | Health-based | Resolved | 2016-07-01 → 2016-09-30 |
| MCL | Health-based | Resolved | 2016-04-01 → 2016-06-30 |
| MCL | Health-based | Resolved | 2016-04-01 → 2016-06-30 |
| MCL | Health-based | Resolved | 2016-04-01 → 2016-06-30 |
| MCL | Health-based | Resolved | 2016-04-01 → 2016-06-30 |
| MCL | Health-based | Resolved | 2016-04-01 → 2016-06-30 |
Other contaminants detected
| Contaminant | Level vs EPA limit | Detection rate | Source | Period |
|---|---|---|---|---|
| Chloroform | 121 µg/L No EPA limit set | 58/62 | SYR4 | 2012–2019 |
| Bromodichloromethane | 45.4 µg/L No EPA limit set | 57/62 | SYR4 | 2012–2019 |
| Copper | 380 µg/L 29% of the EPA limit 1300 µg/L | 54/56 | SYR4 | 2013–2018 |
| Dibromochloromethane | 19.4 µg/L No EPA limit set | 51/62 | SYR4 | 2012–2019 |
| TTHM | 140 µg/L 175% of the EPA limit, in the worst sample — 80 µg/L | 47/48 | SYR4 | 2012–2019 |
| Trichloroacetic Acid | 65 µg/L No EPA limit set | 47/47 | SYR4 | 2012–2019 |
| Dichloroacetic Acid | 82.7 µg/L No EPA limit set | 46/47 | SYR4 | 2012–2019 |
| Total Haloacetic Acids (HAA5) | 151 µg/L 252% of the EPA limit, in the worst sample — 60 µg/L | 46/47 | SYR4 | 2012–2019 |
| Lead | 15 µg/L 100% of the EPA limit 15 µg/L | 37/56 | SYR4 | 2013–2018 |
| Nitrate | 582 µg/L 5.8% of the EPA limit 10000 µg/L | 34/34 | SYR4 | 2012–2019 |
| Bromoform | 3.26 µg/L No EPA limit set | 25/62 | SYR4 | 2012–2019 |
| Dibromoacetic Acid | 20.1 µg/L No EPA limit set | 24/47 | SYR4 | 2012–2019 |
| Monochloroacetic Acid | 9.5 µg/L No EPA limit set | 21/47 | SYR4 | 2012–2019 |
| Lead | 0.0 mg/L 0% of the EPA limit 0.0150 mg/L | 13/13 | LCR | 2025 |
| Fluoride | 1220 µg/L 31% of the EPA limit 4000 µg/L | 10/10 | SYR4 | 2012–2019 |
| Barium | 77 µg/L 3.9% of the EPA limit 2000 µg/L | 9/9 | SYR4 | 2013–2019 |
| Cyanide | 136 µg/L 68% of the EPA limit 200 µg/L | 7/8 | SYR4 | 2014–2019 |
| Monobromoacetic Acid | 2.2 µg/L No EPA limit set | 7/47 | SYR4 | 2012–2019 |
| Chromium | 3.93 µg/L 3.9% of the EPA limit 100 µg/L | 6/9 | SYR4 | 2013–2019 |
| Arsenic | 1.46 µg/L 15% of the EPA limit 10 µg/L | 3/9 | SYR4 | 2013–2019 |
| Nitrate-Nitrite | 660 µg/L 6.6% of the EPA limit 10000 µg/L | 3/3 | SYR4 | 2012–2015 |
| Selenium | 3.49 µg/L 7% of the EPA limit 50 µg/L | 3/9 | SYR4 | 2013–2019 |
| Combined Radium (-226 And -228) | 1.5 pCi/L 30% of the EPA limit 5 pCi/L | 2/2 | SYR4 | 2015 |
| Lithium | 65.4 µg/L No EPA limit set | 2/5 | UCMR-5 | 2025 |
| Atrazine | 0.1200 µg/L 4% of the EPA limit 3 µg/L | 1/10 | SYR4 | 2012–2019 |
| Ethylbenzene | 0.6800 µg/L 0.1% of the EPA limit 700 µg/L | 1/15 | SYR4 | 2012–2019 |
| Gross Beta Particle Activity | 5.2 pCi/L No EPA limit set | 1/2 | SYR4 | 2015 |
| Nitrite | 340 µg/L 34% of the EPA limit 1000 µg/L | 1/4 | SYR4 | 2012–2015 |
| Xylenes, Total | 5.35 µg/L 0.1% of the EPA limit 10000 µg/L | 1/15 | SYR4 | 2012–2019 |
80 contaminants tested, none detected
Utility contact
Frequently asked questions about City of Springtown
Is City of Springtown tap water safe to drink?
EPA monitoring detected 29 contaminants in City of Springtown's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.
What contaminants were detected in City of Springtown's water?
EPA monitoring detected Chloroform, Bromodichloromethane, Copper, Dibromochloromethane, TTHM, and others. The full list with the level and data source for each is above.
How many people does City of Springtown serve?
City of Springtown reports serving 3,781 people in Texas, per its EPA record.
Has City of Springtown had any water quality violations?
The EPA has 151 violations on file for City of Springtown, of which 96 are health-based (a contaminant limit or required treatment was breached) and 1 remain open. The rest are monitoring or reporting failures.
Where does this data come from?
Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.