EPA monitoring tested this supplier for 109 contaminants and detected 28. A detection doesn't automatically mean the water is unsafe — the level and EPA source for each is below.

109
contaminants tested
28
detected
5,371
people served
3,352
health-based violations
Water source
Ground water
Ownership
Local government
Counties served
McCulloch

Compliance record

Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.

3,352
health-based violations
3,520
violations on file
2
still open
ViolationTypeStatusPeriod
MCL Health-based Resolved 2025-01-01 → 2025-03-31
MCL Health-based Resolved 2025-01-01 → 2025-03-31
MCL Health-based Resolved 2025-01-01 → 2025-03-31
MCL Health-based Resolved 2024-10-01 → 2024-12-31
MCL Health-based Resolved 2024-10-01 → 2024-12-31
MCL Health-based Resolved 2024-10-01 → 2024-12-31
MCL Health-based Resolved 2024-07-01 → 2024-09-30
MCL Health-based Resolved 2024-07-01 → 2024-09-30
MCL Health-based Resolved 2024-07-01 → 2024-09-30
MCL Health-based Resolved 2024-07-01 → 2024-09-30

Other contaminants detected

Each bar shows the measured level as a share of the EPA limit: green is well under, amber is close to it, red is over. For lead and copper the limit applies to exactly the 90th-percentile figure shown, so red there means a real exceedance. For everything else the limit applies to a running annual average while the figure is the 95th percentile of this system's samples — over 100% is worth reading, but is not by itself a violation. Where a single sample came in higher than that percentile, it is noted under the bar. Formal violations are listed separately.
ContaminantLevel vs EPA limitDetection rateSourcePeriod
Gross Beta Particle Activity
57.85 pCi/L
No EPA limit set
worst single sample: 74.3 pCi/L
187/187 SYR4 2012–2019
Combined Radium (-226 And -228)
45.3 pCi/L 906%
of the EPA limit, at the 95th percentile of samples — 5 pCi/L
worst single sample: 55.7 pCi/L
186/186 SYR4 2012–2019
Gross Alpha, Excl. Radon And U
37.835 pCi/L 252%
of the EPA limit, at the 95th percentile of samples — 15 pCi/L
worst single sample: 62.3 pCi/L
174/174 SYR4 2012–2019
Copper
740 µg/L 57%
of the EPA limit 1300 µg/L
worst single sample: 4170 µg/L
91/95 SYR4 2012–2019
Dibromochloromethane
29.8 µg/L
No EPA limit set
worst single sample: 136 µg/L
61/103 SYR4 2012–2019
Bromoform
305.25 µg/L
No EPA limit set
worst single sample: 752 µg/L
54/103 SYR4 2012–2019
Bromodichloromethane
8.16 µg/L
No EPA limit set
worst single sample: 19 µg/L
49/103 SYR4 2012–2019
Nitrate
140 µg/L 1.4%
of the EPA limit 10000 µg/L
worst single sample: 170 µg/L
48/114 SYR4 2012–2019
Lead
13.89 µg/L 93%
of the EPA limit 15 µg/L
worst single sample: 90.3 µg/L
47/95 SYR4 2012–2019
TTHM
73 µg/L 91%
of the EPA limit 80 µg/L
worst single sample: 206 µg/L
36/63 SYR4 2012–2019
Chloroform
4.12 µg/L
No EPA limit set
worst single sample: 5.2 µg/L
35/103 SYR4 2012–2019
Total Haloacetic Acids (HAA5)
15.85 µg/L 26%
of the EPA limit 60 µg/L
worst single sample: 47.9 µg/L
34/56 SYR4 2012–2019
Fluoride
890 µg/L 22%
of the EPA limit 4000 µg/L
worst single sample: 900 µg/L
33/33 SYR4 2012–2018
Arsenic
7.7395 µg/L 77%
of the EPA limit 10 µg/L
worst single sample: 12.2 µg/L
24/29 SYR4 2012–2019
Dichloroacetic Acid
3.1 µg/L
No EPA limit set
worst single sample: 3.2 µg/L
24/56 SYR4 2012–2019
Barium
76.8 µg/L 3.8%
of the EPA limit 2000 µg/L
worst single sample: 157 µg/L
21/21 SYR4 2012–2019
Lead
0.0065 mg/L 43%
of the EPA limit 0.0150 mg/L
17/17 LCR 2024
Dibromoacetic Acid
22.11 µg/L
No EPA limit set
worst single sample: 32.9 µg/L
14/56 SYR4 2012–2019
Xylenes, Total
2.835 µg/L 0%
of the EPA limit 10000 µg/L
worst single sample: 3 µg/L
12/47 SYR4 2012–2019
Selenium
6.755 µg/L 14%
of the EPA limit 50 µg/L
worst single sample: 7.7 µg/L
8/21 SYR4 2012–2019
Chromium
6.521 µg/L 6.5%
of the EPA limit 100 µg/L
worst single sample: 6.53 µg/L
7/21 SYR4 2012–2019
Monobromoacetic Acid
3.56 µg/L
No EPA limit set
worst single sample: 4 µg/L
5/56 SYR4 2012–2019
Monochloroacetic Acid
8.3 µg/L
No EPA limit set
worst single sample: 8.8 µg/L
5/56 SYR4 2012–2019
Thallium, Total
2.388 µg/L 119%
of the EPA limit, at the 95th percentile of samples — 2 µg/L
worst single sample: 2.57 µg/L
5/29 SYR4 2012–2019
Nitrate-Nitrite
14 µg/L 0.1%
of the EPA limit 10000 µg/L
3/12 SYR4 2013–2019
Ethylbenzene
0.6900 µg/L 0.1%
of the EPA limit 700 µg/L
worst single sample: 0.7000 µg/L
2/47 SYR4 2012–2019
Antimony, Total
0.6440 µg/L 11%
of the EPA limit 6 µg/L
1/21 SYR4 2012–2019
Lithium
27.8 µg/L
No EPA limit set
1/1 UCMR-5 2025
81 contaminants tested, none detected
1,1,1-Trichloroethane1,1,2-Trichloroethane1,1-Dichloroethylene1,2,4-Trichlorobenzene1,2-DIBROMO-3-CHLOROPROPANE1,2-Dichloroethane1,2-Dichloropropane11Cl-PF3OUdS2,4,5-TP2,4-D4:2 Fts6:2 Fts8:2 Fts9Cl-PF3ONSAdonaAsbestosAtrazineBhc-GammaBenzeneBenzo(A)PyreneBeryllium, TotalChlorobenzeneCyanideCadmiumCarbofuranCarbon TetrachlorideChlordaneCombined UraniumDichloromethaneDalaponDi(2-ethylhexyl) AdipateDi(2-ethylhexyl) PhthalateDinosebEthylene DibromideEndrinHexachlorobenzeneHfpo-DaHeptachlorHeptachlor EpoxideHexachlorocyclopentadieneLassoMercuryMethoxychlorNetfosaaNfdhaNmefosaaNitriteOxamylPfbaPFBSPfdaPfdoaPfeesaPfhpaPfhpsPfhxaPFHXSPfmbaPfmpaPFNAPFOAPFOSPfpeaPfpesPftaPftrdaPfunaPentachlorophenolPicloramSimazineStyreneTetrachloroethyleneTolueneToxapheneTrichloroacetic AcidTrichloroethyleneVinyl Chloridecis-1,2-DichloroethyleneO-DichlorobenzeneP-Dichlorobenzenetrans-1,2-Dichloroethylene

Utility contact

Contact
GROVES, ANTHONY
Phone
325-597-2152

Frequently asked questions about City of Brady Water

Is City of Brady Water tap water safe to drink?

EPA monitoring detected 28 contaminants in City of Brady Water's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.

What contaminants were detected in City of Brady Water's water?

EPA monitoring detected Gross Beta Particle Activity, Combined Radium (-226 And -228), Gross Alpha, Excl. Radon And U, Copper, Dibromochloromethane, and others. The full list with the level and data source for each is above.

How many people does City of Brady Water serve?

City of Brady Water reports serving 5,371 people in Texas, per its EPA record.

Has City of Brady Water had any water quality violations?

The EPA has 3520 violations on file for City of Brady Water, of which 3352 are health-based (a contaminant limit or required treatment was breached) and 2 remain open. The rest are monitoring or reporting failures.

Where does this data come from?

Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.