← Texas

Tap water quality report

Kaufman County Mud 11

EPA monitoring tested this supplier for 44 contaminants and detected 18. A detection doesn't automatically mean the water is unsafe — the level and EPA source for each is below.

44
contaminants tested
18
detected
3,819
people served
0
health-based violations
Water source
SWP
Ownership
Local government
Counties served
Kaufman

Compliance record

Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.

0
health-based violations
21
violations on file
0
still open
ViolationTypeStatusPeriod
Other Monitoring Resolved 2016-04-20
Other Monitoring Resolved 2016-04-20
MR Monitoring Resolved 2015-07-01 → 2015-09-30
MR Monitoring Resolved 2015-07-01 → 2015-09-30
MR Monitoring Resolved 2015-07-01 → 2015-09-30
MR Monitoring Resolved 2015-07-01 → 2015-09-30
Other Monitoring Resolved 2014-12-11
Other Monitoring Resolved 2014-12-11
MR Monitoring Resolved 2014-08-01 → 2014-08-31
MR Monitoring Resolved 2014-08-01 → 2014-08-31

PFAS detected

PFAS are industrial “forever chemicals”. These are the EPA's latest nationwide test results (2023–2025).
ContaminantMaxDetection ratePeriod
Pfba 0.0073 µg/L 2/3 2025
PFBS 0.0034 µg/L 2/3 2025
Pfhxa 0.0041 µg/L 2/3 2025
Pfpea 0.0044 µg/L 2/3 2025

Other contaminants detected

Each bar shows the measured level as a share of the EPA limit: green is well under, amber is close to it, red is over. For lead and copper the limit applies to exactly the 90th-percentile figure shown, so red there means a real exceedance. For everything else the limit applies to a running annual average while the figure is the 95th percentile of this system's samples — over 100% is worth reading, but is not by itself a violation. Where a single sample came in higher than that percentile, it is noted under the bar. Formal violations are listed separately.
ContaminantLevel vs EPA limitDetection rateSourcePeriod
Copper
741.65 µg/L 57%
of the EPA limit 1300 µg/L
worst single sample: 890 µg/L
58/58 SYR4 2012–2017
Lead
2.5225 µg/L 17%
of the EPA limit 15 µg/L
worst single sample: 3.3 µg/L
26/58 SYR4 2012–2017
Bromodichloromethane
18.115 µg/L
No EPA limit set
worst single sample: 20.5 µg/L
10/10 SYR4 2012–2019
Chloroform
19.94 µg/L
No EPA limit set
worst single sample: 23 µg/L
10/10 SYR4 2012–2019
Dibromochloromethane
11.83 µg/L
No EPA limit set
worst single sample: 13 µg/L
10/10 SYR4 2012–2019
TTHM
50.585 µg/L 63%
of the EPA limit 80 µg/L
worst single sample: 59.9 µg/L
10/10 SYR4 2012–2019
Total Haloacetic Acids (HAA5)
31.175 µg/L 52%
of the EPA limit 60 µg/L
worst single sample: 39.5 µg/L
10/10 SYR4 2012–2019
Trichloroacetic Acid
5.675 µg/L
No EPA limit set
worst single sample: 6.8 µg/L
10/10 SYR4 2012–2019
Dichloroacetic Acid
15.64 µg/L
No EPA limit set
worst single sample: 15.8 µg/L
9/10 SYR4 2012–2019
Lead
0.00074 mg/L 4.9%
of the EPA limit 0.0150 mg/L
9/9 LCR 2023
Bromoform
4.285 µg/L
No EPA limit set
worst single sample: 4.31 µg/L
6/10 SYR4 2012–2019
Dibromoacetic Acid
5.725 µg/L
No EPA limit set
worst single sample: 6.1 µg/L
6/10 SYR4 2012–2019
Monochloroacetic Acid
2 µg/L
No EPA limit set
4/10 SYR4 2012–2019
Monobromoacetic Acid
16.485 µg/L
No EPA limit set
worst single sample: 17.3 µg/L
2/10 SYR4 2012–2019
26 contaminants tested, none detected
11Cl-PF3OUdS4:2 Fts6:2 Fts8:2 Fts9Cl-PF3ONSAdonaHfpo-DaNetfosaaNfdhaNmefosaaPfdaPfdoaPfeesaPfhpaPfhpsPFHXSPfmbaPfmpaPFNAPFOAPFOSPfpesPftaPftrdaPfunaLithium

Utility contact

Contact
GIBB, GREGG, E
Phone
972-788-1600
Email
jwills@crossroadsus.com

Frequently asked questions about Kaufman County Mud 11

Is Kaufman County Mud 11 tap water safe to drink?

EPA monitoring detected 18 contaminants in Kaufman County Mud 11's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.

What contaminants were detected in Kaufman County Mud 11's water?

EPA monitoring detected Copper, Lead, Bromodichloromethane, Chloroform, Dibromochloromethane, and others. The full list with the level and data source for each is above.

How many people does Kaufman County Mud 11 serve?

Kaufman County Mud 11 reports serving 3,819 people in Texas, per its EPA record.

Has Kaufman County Mud 11 had any water quality violations?

The EPA has 21 violations on file for Kaufman County Mud 11, of which 0 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.

Where does this data come from?

Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.