Compliance record
Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.
| Violation | Type | Status | Period |
|---|---|---|---|
| MCL | Health-based | Archived | 2025-04-01 → 2025-06-30 |
| MCL | Health-based | Archived | 2025-04-01 → 2025-06-30 |
| MCL | Health-based | Archived | 2025-04-01 → 2025-06-30 |
| MCL | Health-based | Archived | 2025-04-01 → 2025-06-30 |
| TT | Health-based | Resolved | 2024-10-17 |
| TT | Health-based | Resolved | 2024-10-17 |
| TT | Health-based | Resolved | 2024-10-17 |
| TT | Health-based | Resolved | 2024-10-17 |
| TT | Health-based | Resolved | 2024-10-17 |
| MCL | Health-based | Resolved | 2007-06-01 → 2007-06-30 |
Other contaminants detected
| Contaminant | Level vs EPA limit | Detection rate | Source | Period |
|---|---|---|---|---|
| Copper | 247 µg/L 19% of the EPA limit 1300 µg/L | 49/55 | SYR4 | 2013–2017 |
| Bromoform | 57 µg/L No EPA limit set | 39/39 | SYR4 | 2012–2019 |
| Dibromochloromethane | 46.4 µg/L No EPA limit set | 38/39 | SYR4 | 2012–2019 |
| Lead | 6.4 µg/L 43% of the EPA limit 15 µg/L | 37/55 | SYR4 | 2013–2017 |
| Bromodichloromethane | 14.2 µg/L No EPA limit set | 35/39 | SYR4 | 2012–2019 |
| TTHM | 120 µg/L 150% of the EPA limit, in the worst sample — 80 µg/L | 34/34 | SYR4 | 2012–2019 |
| Total Haloacetic Acids (HAA5) | 23.8 µg/L 40% of the EPA limit 60 µg/L | 31/34 | SYR4 | 2012–2019 |
| Dibromoacetic Acid | 13.2 µg/L No EPA limit set | 30/34 | SYR4 | 2012–2019 |
| Chloroform | 2.6 µg/L No EPA limit set | 25/39 | SYR4 | 2012–2019 |
| Dichloroacetic Acid | 4.2 µg/L No EPA limit set | 25/34 | SYR4 | 2012–2019 |
| Lead | 0.0022 mg/L 15% of the EPA limit 0.0150 mg/L | 14/14 | LCR | 2023 |
| Nitrate | 50 µg/L 0.5% of the EPA limit 10000 µg/L | 14/16 | SYR4 | 2012–2019 |
| Trichloroacetic Acid | 2.7 µg/L No EPA limit set | 11/34 | SYR4 | 2012–2019 |
| Monobromoacetic Acid | 2.3 µg/L No EPA limit set | 10/34 | SYR4 | 2012–2019 |
| Nitrate-Nitrite | 50 µg/L 0.5% of the EPA limit 10000 µg/L | 3/3 | SYR4 | 2012–2015 |
| Barium | 63.2 µg/L 3.2% of the EPA limit 2000 µg/L | 2/2 | SYR4 | 2016–2019 |
| Fluoride | 850 µg/L 21% of the EPA limit 4000 µg/L | 2/2 | SYR4 | 2014–2017 |
| Monochloroacetic Acid | 6.1 µg/L No EPA limit set | 2/34 | SYR4 | 2012–2019 |
| Lithium | 56.4 µg/L No EPA limit set | 2/2 | UCMR-5 | 2024 |
| Selenium | 6.9 µg/L 14% of the EPA limit 50 µg/L | 1/2 | SYR4 | 2016–2019 |
88 contaminants tested, none detected
Utility contact
Frequently asked questions about City of Karnes City
Is City of Karnes City tap water safe to drink?
EPA monitoring detected 20 contaminants in City of Karnes City's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.
What contaminants were detected in City of Karnes City's water?
EPA monitoring detected Copper, Bromoform, Dibromochloromethane, Lead, Bromodichloromethane, and others. The full list with the level and data source for each is above.
How many people does City of Karnes City serve?
City of Karnes City reports serving 4,269 people in Texas, per its EPA record.
Has City of Karnes City had any water quality violations?
The EPA has 73 violations on file for City of Karnes City, of which 19 are health-based (a contaminant limit or required treatment was breached) and 3 remain open. The rest are monitoring or reporting failures.
Where does this data come from?
Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.