Compliance record
Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.
| Violation | Type | Status | Period |
|---|---|---|---|
| MCL | Health-based | Archived | 1993-04-01 → 1993-04-30 |
| MCL | Health-based | Archived | 1992-07-01 → 1992-07-31 |
| MCL | Health-based | Archived | 1983-02-17 → 1984-02-16 |
| MCL | Health-based | Archived | 1979-05-03 → 1979-06-02 |
| MCL | Health-based | Archived | 1979-05-03 → 1980-05-02 |
| MR | Monitoring | Archived | 2021-01-01 → 2023-12-31 |
| MR | Monitoring | Archived | 2021-01-01 → 2023-12-31 |
| MR | Monitoring | Archived | 2021-01-01 → 2023-12-31 |
| MR | Monitoring | Archived | 2021-01-01 → 2023-12-31 |
| MR | Monitoring | Archived | 2021-01-01 → 2023-12-31 |
PFAS detected
| Contaminant | Max | Detection rate | Period |
|---|---|---|---|
| Pfba | 0.0059 µg/L | 4/24 | 2025 |
Other contaminants detected
| Contaminant | Level vs EPA limit | Detection rate | Source | Period |
|---|---|---|---|---|
| Nitrate | 1260 µg/L 13% of the EPA limit 10000 µg/L | 250/254 | SYR4 | 2012–2019 |
| Dibromochloromethane | 6.06 µg/L No EPA limit set | 169/209 | SYR4 | 2012–2019 |
| Bromodichloromethane | 17 µg/L No EPA limit set | 167/209 | SYR4 | 2012–2019 |
| Chloroform | 29.8 µg/L No EPA limit set | 144/209 | SYR4 | 2012–2019 |
| Total Haloacetic Acids (HAA5) | 23.1 µg/L 39% of the EPA limit 60 µg/L | 123/128 | SYR4 | 2012–2019 |
| Dichloroacetic Acid | 12.8 µg/L No EPA limit set | 121/128 | SYR4 | 2012–2019 |
| TTHM | 47.8 µg/L 60% of the EPA limit 80 µg/L | 120/128 | SYR4 | 2012–2019 |
| Copper | 882.1 µg/L 68% of the EPA limit 1300 µg/L | 113/114 | SYR4 | 2012–2019 |
| Dibromoacetic Acid | 4.6 µg/L No EPA limit set | 65/128 | SYR4 | 2012–2019 |
| Bromoform | 18.3 µg/L No EPA limit set | 64/209 | SYR4 | 2012–2019 |
| Trichloroacetic Acid | 3.9 µg/L No EPA limit set | 61/128 | SYR4 | 2012–2019 |
| Nitrate-Nitrite | 1130 µg/L 11% of the EPA limit 10000 µg/L | 53/54 | SYR4 | 2012–2019 |
| Lead | 8.11 µg/L 54% of the EPA limit 15 µg/L | 49/114 | SYR4 | 2012–2019 |
| Monochloroacetic Acid | 5.9 µg/L No EPA limit set | 49/128 | SYR4 | 2012–2019 |
| Fluoride | 1980 µg/L 50% of the EPA limit 4000 µg/L | 34/34 | SYR4 | 2012–2017 |
| Barium | 58 µg/L 2.9% of the EPA limit 2000 µg/L | 33/33 | SYR4 | 2012–2019 |
| Chromium | 5 µg/L 5% of the EPA limit 100 µg/L | 24/33 | SYR4 | 2012–2019 |
| Monobromoacetic Acid | 2.5 µg/L No EPA limit set | 22/128 | SYR4 | 2012–2019 |
| Nitrite | 770 µg/L 77% of the EPA limit 1000 µg/L | 20/67 | SYR4 | 2012–2019 |
| Lithium | 68.6 µg/L No EPA limit set | 15/24 | UCMR-5 | 2025 |
| Lead | 0.0017 mg/L 11% of the EPA limit 0.0150 mg/L | 13/13 | LCR | 2025 |
| Atrazine | 0.1400 µg/L 4.7% of the EPA limit 3 µg/L | 12/71 | SYR4 | 2012–2019 |
| Arsenic | 2.9 µg/L 29% of the EPA limit 10 µg/L | 11/33 | SYR4 | 2012–2019 |
| Cyanide | 105 µg/L 53% of the EPA limit 200 µg/L | 8/30 | SYR4 | 2014–2017 |
| Combined Radium (-226 And -228) | 1.5 pCi/L 30% of the EPA limit 5 pCi/L | 5/5 | SYR4 | 2017 |
| Selenium | 2.74 µg/L 5.5% of the EPA limit 50 µg/L | 3/33 | SYR4 | 2012–2019 |
| Ethylbenzene | 9.49 µg/L 1.4% of the EPA limit 700 µg/L | 2/81 | SYR4 | 2012–2019 |
| Gross Beta Particle Activity | 6.4 pCi/L No EPA limit set | 2/19 | SYR4 | 2012–2017 |
| Xylenes, Total | 77.6 µg/L 0.8% of the EPA limit 10000 µg/L | 2/81 | SYR4 | 2012–2019 |
| Antimony, Total | 1.06 µg/L 18% of the EPA limit 6 µg/L | 1/33 | SYR4 | 2012–2019 |
| Asbestos | 0.7512 MFL 11% of the EPA limit 7 MFL | 1/1 | SYR4 | 2012 |
| Di(2-ethylhexyl) Phthalate | 1.7 µg/L 28% of the EPA limit 6 µg/L | 1/71 | SYR4 | 2012–2019 |
76 contaminants tested, none detected
Utility contact
Frequently asked questions about Bethesda Wsc
Is Bethesda Wsc tap water safe to drink?
EPA monitoring detected 33 contaminants in Bethesda Wsc's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.
What contaminants were detected in Bethesda Wsc's water?
EPA monitoring detected Nitrate, Dibromochloromethane, Bromodichloromethane, Chloroform, Total Haloacetic Acids (HAA5), and others. The full list with the level and data source for each is above.
How many people does Bethesda Wsc serve?
Bethesda Wsc reports serving 33,441 people in Texas, per its EPA record.
Has Bethesda Wsc had any water quality violations?
The EPA has 24 violations on file for Bethesda Wsc, of which 5 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.
Where does this data come from?
Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.