Compliance record
Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.
| Violation | Type | Status | Period |
|---|---|---|---|
| MCL | Health-based | Resolved | 2018-04-01 → 2018-06-30 |
| MCL | Health-based | Resolved | 2018-04-01 → 2018-06-30 |
| MCL | Health-based | Resolved | 2018-04-01 → 2018-06-30 |
| MCL | Health-based | Resolved | 2018-04-01 → 2018-06-30 |
| MCL | Health-based | Resolved | 2018-04-01 → 2018-06-30 |
| MCL | Health-based | Resolved | 2018-04-01 → 2018-06-30 |
| MCL | Health-based | Resolved | 2002-11-01 → 2002-11-30 |
| MCL | Health-based | Resolved | 2002-11-01 → 2002-11-30 |
| MCL | Health-based | Resolved | 2002-11-01 → 2002-11-30 |
| Other | Monitoring | Resolved | 2024-07-01 |
PFAS detected
| Contaminant | Max | Detection rate | Period |
|---|---|---|---|
| Pfba | 0.0056 µg/L | 1/15 | 2025 |
Other contaminants detected
| Contaminant | Level vs EPA limit | Detection rate | Source | Period |
|---|---|---|---|---|
| Nitrate | 1870 µg/L 19% of the EPA limit 10000 µg/L | 100/110 | SYR4 | 2012–2019 |
| Dibromochloromethane | 20.9 µg/L No EPA limit set | 57/85 | SYR4 | 2012–2019 |
| TTHM | 71.2 µg/L 89% of the EPA limit 80 µg/L | 50/58 | SYR4 | 2012–2019 |
| Bromodichloromethane | 16.9 µg/L No EPA limit set | 49/85 | SYR4 | 2012–2019 |
| Copper | 270 µg/L 21% of the EPA limit 1300 µg/L | 49/50 | SYR4 | 2012–2017 |
| Chloroform | 34.7 µg/L No EPA limit set | 43/85 | SYR4 | 2012–2019 |
| Total Haloacetic Acids (HAA5) | 31.5 µg/L 53% of the EPA limit 60 µg/L | 43/58 | SYR4 | 2012–2019 |
| Bromoform | 19 µg/L No EPA limit set | 38/85 | SYR4 | 2012–2019 |
| Dichloroacetic Acid | 17.5 µg/L No EPA limit set | 33/58 | SYR4 | 2012–2019 |
| Nitrite | 1920 µg/L 192% of the EPA limit, in the worst sample — 1000 µg/L | 27/78 | SYR4 | 2012–2019 |
| Nitrate-Nitrite | 1100 µg/L 11% of the EPA limit 10000 µg/L | 23/24 | SYR4 | 2012–2019 |
| Trichloroacetic Acid | 14 µg/L No EPA limit set | 23/58 | SYR4 | 2012–2019 |
| Dibromoacetic Acid | 7.6 µg/L No EPA limit set | 22/58 | SYR4 | 2012–2019 |
| Monochloroacetic Acid | 6.9 µg/L No EPA limit set | 19/58 | SYR4 | 2012–2019 |
| Lead | 0.0015 mg/L 10% of the EPA limit 0.0150 mg/L | 15/15 | LCR | 2023 |
| Fluoride | 1660 µg/L 42% of the EPA limit 4000 µg/L | 14/14 | SYR4 | 2012–2018 |
| Barium | 89 µg/L 4.5% of the EPA limit 2000 µg/L | 13/13 | SYR4 | 2012–2019 |
| Lead | 36 µg/L 240% of the EPA limit, in the worst sample — 15 µg/L | 13/50 | SYR4 | 2012–2017 |
| Combined Radium (-226 And -228) | 3 pCi/L 60% of the EPA limit 5 pCi/L | 11/11 | SYR4 | 2013–2019 |
| Lithium | 90.3 µg/L No EPA limit set | 10/15 | UCMR-5 | 2025 |
| Monobromoacetic Acid | 5 µg/L No EPA limit set | 9/58 | SYR4 | 2012–2019 |
| Chromium | 7.28 µg/L 7.3% of the EPA limit 100 µg/L | 8/13 | SYR4 | 2012–2019 |
| Arsenic | 1.7 µg/L 17% of the EPA limit 10 µg/L | 7/13 | SYR4 | 2012–2019 |
| Cyanide | 91.5 µg/L 46% of the EPA limit 200 µg/L | 5/12 | SYR4 | 2014–2017 |
| Atrazine | 0.1000 µg/L 3.3% of the EPA limit 3 µg/L | 2/17 | SYR4 | 2012–2018 |
| Selenium | 2.13 µg/L 4.3% of the EPA limit 50 µg/L | 2/13 | SYR4 | 2012–2019 |
| Antimony, Total | 0.3960 µg/L 6.6% of the EPA limit 6 µg/L | 1/13 | SYR4 | 2012–2019 |
| Dichloromethane | 1.33 µg/L 27% of the EPA limit 5 µg/L | 1/27 | SYR4 | 2014–2019 |
| Gross Beta Particle Activity | 4.8 pCi/L No EPA limit set | 1/15 | SYR4 | 2013–2019 |
| Thallium, Total | 0.0210 µg/L 1.1% of the EPA limit 2 µg/L | 1/13 | SYR4 | 2012–2019 |
78 contaminants tested, none detected
Utility contact
Frequently asked questions about City of Keene
Is City of Keene tap water safe to drink?
EPA monitoring detected 31 contaminants in City of Keene's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.
What contaminants were detected in City of Keene's water?
EPA monitoring detected Nitrate, Dibromochloromethane, TTHM, Bromodichloromethane, Copper, and others. The full list with the level and data source for each is above.
How many people does City of Keene serve?
City of Keene reports serving 6,863 people in Texas, per its EPA record.
Has City of Keene had any water quality violations?
The EPA has 49 violations on file for City of Keene, of which 9 are health-based (a contaminant limit or required treatment was breached) and 3 remain open. The rest are monitoring or reporting failures.
Where does this data come from?
Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.