Compliance record
Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.
| Violation | Type | Status | Period |
|---|---|---|---|
| MCL | Health-based | Archived | 2026-01-01 → 2026-03-31 |
| MCL | Health-based | Archived | 2026-01-01 → 2026-03-31 |
| MCL | Health-based | Archived | 2026-01-01 → 2026-03-31 |
| MCL | Health-based | Archived | 2026-01-01 → 2026-03-31 |
| MCL | Health-based | Archived | 2026-01-01 → 2026-03-31 |
| MCL | Health-based | Archived | 2026-01-01 → 2026-03-31 |
| MCL | Health-based | Archived | 2025-10-01 → 2025-12-31 |
| MCL | Health-based | Archived | 2025-10-01 → 2025-12-31 |
| MCL | Health-based | Archived | 2025-10-01 → 2025-12-31 |
| MCL | Health-based | Archived | 2025-10-01 → 2025-12-31 |
Other contaminants detected
| Contaminant | Level vs EPA limit | Detection rate | Source | Period |
|---|---|---|---|---|
| Chloroform | 98.2 µg/L No EPA limit set | 57/60 | SYR4 | 2012–2019 |
| Dichloroacetic Acid | 50 µg/L No EPA limit set | 49/50 | SYR4 | 2012–2019 |
| Total Haloacetic Acids (HAA5) | 101 µg/L 168% of the EPA limit, in the worst sample — 60 µg/L | 49/50 | SYR4 | 2012–2019 |
| Bromodichloromethane | 59.8 µg/L No EPA limit set | 48/60 | SYR4 | 2012–2019 |
| TTHM | 189 µg/L 236% of the EPA limit, in the worst sample — 80 µg/L | 47/50 | SYR4 | 2012–2019 |
| Dibromoacetic Acid | 10.1 µg/L No EPA limit set | 40/50 | SYR4 | 2012–2019 |
| Dibromochloromethane | 42.5 µg/L No EPA limit set | 38/60 | SYR4 | 2012–2019 |
| Bromate | 46 µg/L 460% of the EPA limit, in the worst sample — 10 µg/L | 33/121 | SYR4 | 2014–2019 |
| Copper | 1680 µg/L 129% of the EPA limit, in the worst sample — 1300 µg/L | 32/34 | SYR4 | 2012–2017 |
| Nitrate | 220 µg/L 2.2% of the EPA limit 10000 µg/L | 32/32 | SYR4 | 2012–2019 |
| Bromoform | 29.2 µg/L No EPA limit set | 29/60 | SYR4 | 2012–2019 |
| Lead | 16.8 µg/L 112% of the EPA limit, in the worst sample — 15 µg/L | 25/34 | SYR4 | 2012–2017 |
| Trichloroacetic Acid | 49.9 µg/L No EPA limit set | 25/50 | SYR4 | 2012–2019 |
| Dalapon | 5 µg/L 2.5% of the EPA limit 200 µg/L | 18/54 | SYR4 | 2012–2019 |
| Monochloroacetic Acid | 7 µg/L No EPA limit set | 11/50 | SYR4 | 2012–2019 |
| Lead | 0.0 mg/L 0% of the EPA limit 0.0150 mg/L | 7/7 | LCR | 2024 |
| Nitrate-Nitrite | 110 µg/L 1.1% of the EPA limit 10000 µg/L | 6/6 | SYR4 | 2012–2015 |
| Barium | 33.7 µg/L 1.7% of the EPA limit 2000 µg/L | 5/5 | SYR4 | 2014–2019 |
| Monobromoacetic Acid | 4.7 µg/L No EPA limit set | 5/50 | SYR4 | 2012–2019 |
| Fluoride | 910 µg/L 23% of the EPA limit 4000 µg/L | 4/4 | SYR4 | 2014–2017 |
| Nitrite | 20 µg/L 2% of the EPA limit 1000 µg/L | 4/6 | SYR4 | 2012–2015 |
| Cyanide | 160 µg/L 80% of the EPA limit 200 µg/L | 2/4 | SYR4 | 2014–2017 |
| Gross Alpha, Excl. Radon And U | 4.8 pCi/L 32% of the EPA limit 15 pCi/L | 2/2 | SYR4 | 2015 |
| Gross Beta Particle Activity | 5.1 pCi/L No EPA limit set | 1/2 | SYR4 | 2015 |
56 contaminants tested, none detected
Utility contact
Frequently asked questions about Rayburn Country Mud
Is Rayburn Country Mud tap water safe to drink?
EPA monitoring detected 24 contaminants in Rayburn Country Mud's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.
What contaminants were detected in Rayburn Country Mud's water?
EPA monitoring detected Chloroform, Dichloroacetic Acid, Total Haloacetic Acids (HAA5), Bromodichloromethane, TTHM, and others. The full list with the level and data source for each is above.
How many people does Rayburn Country Mud serve?
Rayburn Country Mud reports serving 4,062 people in Texas, per its EPA record.
Has Rayburn Country Mud had any water quality violations?
The EPA has 342 violations on file for Rayburn Country Mud, of which 248 are health-based (a contaminant limit or required treatment was breached) and 2 remain open. The rest are monitoring or reporting failures.
Where does this data come from?
Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.