← Texas

Tap water quality report

Caddo Mesa Wsc

EPA monitoring tested this supplier for 79 contaminants and detected 12. A detection doesn't automatically mean the water is unsafe — the level and EPA source for each is below.

79
contaminants tested
12
detected
93
people served
8
health-based violations
Water source
Ground water
Ownership
Local government
Counties served
Hunt

Compliance record

Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.

8
health-based violations
285
violations on file
23
still open
ViolationTypeStatusPeriod
TT Health-based Addressed 2024-10-17
TT Health-based Addressed 2024-10-17
TT Health-based Addressed 2024-10-17
TT Health-based Addressed 2024-10-17
MCL Health-based Resolved 2015-08-01 → 2015-08-31
MCL Health-based Resolved 2015-08-01 → 2015-08-31
MCL Health-based Resolved 2015-08-01 → 2015-08-31
MCL Health-based Resolved 2015-08-01 → 2015-08-31
Other Monitoring Unaddressed 2026-05-03
Other Monitoring Unaddressed 2026-04-05

Other contaminants detected

Each bar shows the measured level as a share of the EPA limit: green is well under, amber is close to it, red is over. For lead and copper the limit applies to exactly the 90th-percentile figure shown, so red there means a real exceedance. For everything else the limit applies to a running annual average while the figure is the 95th percentile of this system's samples — over 100% is worth reading, but is not by itself a violation. Where a single sample came in higher than that percentile, it is noted under the bar. Formal violations are listed separately.
ContaminantLevel vs EPA limitDetection rateSourcePeriod
Copper
227.6 µg/L 18%
of the EPA limit 1300 µg/L
worst single sample: 280 µg/L
9/12 SYR4 2013–2019
Nitrate
55 µg/L 0.5%
of the EPA limit 10000 µg/L
8/16 SYR4 2012–2019
Lead
0.0017 mg/L 11%
of the EPA limit 0.0150 mg/L
4/4 LCR 1999
Barium
6.49 µg/L 0.3%
of the EPA limit 2000 µg/L
worst single sample: 6.5 µg/L
3/3 SYR4 2013–2019
Chromium
5.15 µg/L 5.2%
of the EPA limit 100 µg/L
worst single sample: 5.4 µg/L
3/3 SYR4 2013–2019
Fluoride
2023 µg/L 51%
of the EPA limit 4000 µg/L
worst single sample: 2030 µg/L
3/3 SYR4 2013–2019
Lead
1.4091 µg/L 9.4%
of the EPA limit 15 µg/L
worst single sample: 1.5 µg/L
3/12 SYR4 2013–2019
Bromoform
2.6 µg/L
No EPA limit set
1/8 SYR4 2013–2019
Cyanide
24.1 µg/L 12%
of the EPA limit 200 µg/L
1/2 SYR4 2014–2017
Combined Radium (-226 And -228)
1 pCi/L 20%
of the EPA limit 5 pCi/L
1/1 SYR4 2013
Dibromochloromethane
1.54 µg/L
No EPA limit set
1/8 SYR4 2013–2019
Nitrate-Nitrite
55 µg/L 0.5%
of the EPA limit 10000 µg/L
1/3 SYR4 2012–2015
67 contaminants tested, none detected
1,1,1-Trichloroethane1,1,2-Trichloroethane1,1-Dichloroethylene1,2,4-Trichlorobenzene1,2-DIBROMO-3-CHLOROPROPANE1,2-Dichloroethane1,2-Dichloropropane2,4,5-TP2,4-DAntimony, TotalArsenicAsbestosAtrazineBhc-GammaBenzeneBenzo(A)PyreneBeryllium, TotalBromodichloromethaneChlorobenzeneCadmiumCarbofuranCarbon TetrachlorideChlordaneChloroformCombined UraniumDichloromethaneDalaponDi(2-ethylhexyl) AdipateDi(2-ethylhexyl) PhthalateDibromoacetic AcidDichloroacetic AcidDinosebEthylene DibromideEndrinEthylbenzeneGross Alpha, Excl. Radon And UGross Beta Particle ActivityHexachlorobenzeneHeptachlorHeptachlor EpoxideHexachlorocyclopentadieneLassoMercuryMethoxychlorMonobromoacetic AcidMonochloroacetic AcidNitriteOxamylPentachlorophenolPicloramSeleniumSimazineStyreneTTHMTetrachloroethyleneThallium, TotalTolueneTotal Haloacetic Acids (HAA5)ToxapheneTrichloroacetic AcidTrichloroethyleneVinyl ChlorideXylenes, Totalcis-1,2-DichloroethyleneO-DichlorobenzeneP-Dichlorobenzenetrans-1,2-Dichloroethylene

Utility contact

Contact
KAUFMANN, SHERRY
Phone
903-824-3375
Email
caddomesa@gmail.com

Frequently asked questions about Caddo Mesa Wsc

Is Caddo Mesa Wsc tap water safe to drink?

EPA monitoring detected 12 contaminants in Caddo Mesa Wsc's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.

What contaminants were detected in Caddo Mesa Wsc's water?

EPA monitoring detected Copper, Nitrate, Lead, Barium, Chromium, and others. The full list with the level and data source for each is above.

How many people does Caddo Mesa Wsc serve?

Caddo Mesa Wsc reports serving 93 people in Texas, per its EPA record.

Has Caddo Mesa Wsc had any water quality violations?

The EPA has 285 violations on file for Caddo Mesa Wsc, of which 8 are health-based (a contaminant limit or required treatment was breached) and 23 remain open. The rest are monitoring or reporting failures.

Where does this data come from?

Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.