← Texas

Tap water quality report

The Consolidated Wsc Central

EPA monitoring tested this supplier for 44 contaminants and detected 14. A detection doesn't automatically mean the water is unsafe — the level and EPA source for each is below.

44
contaminants tested
14
detected
3,878
people served
103
health-based violations
Water source
Ground water
Ownership
Local government
Counties served
Houston

Compliance record

Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.

103
health-based violations
148
violations on file
1
still open
ViolationTypeStatusPeriod
MCL Health-based Resolved 2025-01-01 → 2025-03-31
MCL Health-based Resolved 2025-01-01 → 2025-03-31
MCL Health-based Resolved 2025-01-01 → 2025-03-31
MCL Health-based Resolved 2025-01-01 → 2025-03-31
MCL Health-based Resolved 2025-01-01 → 2025-03-31
MCL Health-based Resolved 2025-01-01 → 2025-03-31
MCL Health-based Resolved 2025-01-01 → 2025-03-31
MCL Health-based Resolved 2025-01-01 → 2025-03-31
MCL Health-based Resolved 2024-10-01 → 2024-12-31
MCL Health-based Resolved 2024-10-01 → 2024-12-31

PFAS detected

PFAS are industrial “forever chemicals”. These are the EPA's latest nationwide test results (2023–2025).
ContaminantMaxDetection ratePeriod
Pfba 0.0051 µg/L 1/5 2025

Other contaminants detected

Each bar shows the measured level as a share of the EPA limit: green is well under, amber is close to it, red is over. For lead and copper the limit applies to exactly the 90th-percentile figure shown, so red there means a real exceedance. For everything else the limit applies to a running annual average while the figure is the 95th percentile of this system's samples — over 100% is worth reading, but is not by itself a violation. Where a single sample came in higher than that percentile, it is noted under the bar. Formal violations are listed separately.
ContaminantLevel vs EPA limitDetection rateSourcePeriod
Bromodichloromethane
20.465 µg/L
No EPA limit set
worst single sample: 21.7 µg/L
50/50 SYR4 2012–2019
Chloroform
105.3 µg/L
No EPA limit set
worst single sample: 124 µg/L
50/50 SYR4 2012–2019
TTHM
125.5 µg/L 157%
of the EPA limit, at the 95th percentile of samples — 80 µg/L
worst single sample: 147 µg/L
50/50 SYR4 2012–2019
Dibromochloromethane
4.9585 µg/L
No EPA limit set
worst single sample: 5.74 µg/L
48/50 SYR4 2012–2019
Dichloroacetic Acid
51.3 µg/L
No EPA limit set
worst single sample: 58.1 µg/L
45/50 SYR4 2012–2019
Total Haloacetic Acids (HAA5)
79.4 µg/L 132%
of the EPA limit, at the 95th percentile of samples — 60 µg/L
worst single sample: 96 µg/L
45/50 SYR4 2012–2019
Trichloroacetic Acid
25.4 µg/L
No EPA limit set
worst single sample: 35.9 µg/L
41/50 SYR4 2012–2019
Copper
48 µg/L 3.7%
of the EPA limit 1300 µg/L
worst single sample: 68 µg/L
28/30 SYR4 2012–2018
Monochloroacetic Acid
6.28 µg/L
No EPA limit set
worst single sample: 7.9 µg/L
19/50 SYR4 2012–2019
Dibromoacetic Acid
2.36 µg/L
No EPA limit set
worst single sample: 2.6 µg/L
17/50 SYR4 2012–2019
Lead
5.115 µg/L 34%
of the EPA limit 15 µg/L
worst single sample: 5.5 µg/L
8/30 SYR4 2012–2018
Lead
0.0013 mg/L 8.7%
of the EPA limit 0.0150 mg/L
6/6 LCR 2025
Monobromoacetic Acid
1.58 µg/L
No EPA limit set
worst single sample: 1.6 µg/L
2/50 SYR4 2012–2019
30 contaminants tested, none detected
11Cl-PF3OUdS4:2 Fts6:2 Fts8:2 Fts9Cl-PF3ONSAdonaBromoformHfpo-DaNetfosaaNfdhaNmefosaaPFBSPfdaPfdoaPfeesaPfhpaPfhpsPfhxaPFHXSPfmbaPfmpaPFNAPFOAPFOSPfpeaPfpesPftaPftrdaPfunaLithium

Utility contact

Contact
SPELLMAN, KIMBERLY
Phone
936-544-2986

Frequently asked questions about The Consolidated Wsc Central

Is The Consolidated Wsc Central tap water safe to drink?

EPA monitoring detected 14 contaminants in The Consolidated Wsc Central's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.

What contaminants were detected in The Consolidated Wsc Central's water?

EPA monitoring detected Bromodichloromethane, Chloroform, TTHM, Dibromochloromethane, Dichloroacetic Acid, and others. The full list with the level and data source for each is above.

How many people does The Consolidated Wsc Central serve?

The Consolidated Wsc Central reports serving 3,878 people in Texas, per its EPA record.

Has The Consolidated Wsc Central had any water quality violations?

The EPA has 148 violations on file for The Consolidated Wsc Central, of which 103 are health-based (a contaminant limit or required treatment was breached) and 1 remain open. The rest are monitoring or reporting failures.

Where does this data come from?

Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.