Compliance record
Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.
| Violation | Type | Status | Period |
|---|---|---|---|
| Other | Monitoring | Resolved | 2025-07-01 |
| Other | Monitoring | Resolved | 2025-07-01 |
| MR | Monitoring | Resolved | 2016-07-01 |
| MR | Monitoring | Resolved | 2016-07-01 |
| MR | Monitoring | Resolved | 2016-07-01 |
| MR | Monitoring | Resolved | 2016-07-01 |
Other contaminants detected
| Contaminant | Level vs EPA limit | Detection rate | Source | Period |
|---|---|---|---|---|
| Copper | 1083 µg/L 83% of the EPA limit 1300 µg/L | 155/161 | SYR4 | 2015–2017 |
| Lead | 20 µg/L 133% of the EPA limit, in the worst sample — 15 µg/L | 30/161 | SYR4 | 2015–2017 |
| Dibromochloromethane | 13.8 µg/L No EPA limit set | 17/17 | SYR4 | 2015–2019 |
| Bromoform | 25.8 µg/L No EPA limit set | 14/17 | SYR4 | 2015–2019 |
| Bromodichloromethane | 4.9 µg/L No EPA limit set | 12/17 | SYR4 | 2015–2019 |
| TTHM | 43.7 µg/L 55% of the EPA limit 80 µg/L | 10/10 | SYR4 | 2015–2019 |
| Dibromoacetic Acid | 4.1 µg/L No EPA limit set | 8/10 | SYR4 | 2015–2019 |
| Nitrate | 30 µg/L 0.3% of the EPA limit 10000 µg/L | 8/10 | SYR4 | 2015–2019 |
| Total Haloacetic Acids (HAA5) | 5.2 µg/L 8.7% of the EPA limit 60 µg/L | 8/10 | SYR4 | 2015–2019 |
| Chloroform | 1.7 µg/L No EPA limit set | 6/17 | SYR4 | 2015–2019 |
| Lead | 0.0 mg/L 0% of the EPA limit 0.0150 mg/L | 6/6 | LCR | 2023 |
| Barium | 120 µg/L 6% of the EPA limit 2000 µg/L | 2/2 | SYR4 | 2015–2018 |
| Dichloroacetic Acid | 1.3 µg/L No EPA limit set | 2/10 | SYR4 | 2015–2019 |
| Fluoride | 2280 µg/L 57% of the EPA limit 4000 µg/L | 2/2 | SYR4 | 2015–2018 |
| Trichloroacetic Acid | 1.1 µg/L No EPA limit set | 2/10 | SYR4 | 2015–2019 |
| Lithium | 44.6 µg/L No EPA limit set | 2/2 | UCMR-5 | 2025 |
| Arsenic | 2.1 µg/L 21% of the EPA limit 10 µg/L | 1/2 | SYR4 | 2015–2018 |
| Selenium | 3.8 µg/L 7.6% of the EPA limit 50 µg/L | 1/2 | SYR4 | 2015–2018 |
89 contaminants tested, none detected
Utility contact
Frequently asked questions about Harris County Improvement District 18
Is Harris County Improvement District 18 tap water safe to drink?
EPA monitoring detected 18 contaminants in Harris County Improvement District 18's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.
What contaminants were detected in Harris County Improvement District 18's water?
EPA monitoring detected Copper, Lead, Dibromochloromethane, Bromoform, Bromodichloromethane, and others. The full list with the level and data source for each is above.
How many people does Harris County Improvement District 18 serve?
Harris County Improvement District 18 reports serving 5,025 people in Texas, per its EPA record.
Has Harris County Improvement District 18 had any water quality violations?
The EPA has 6 violations on file for Harris County Improvement District 18, of which 0 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.
Where does this data come from?
Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.