Compliance record
Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.
| Violation | Type | Status | Period |
|---|---|---|---|
| MR | Monitoring | Resolved | 2013-12-30 |
| Other | Monitoring | Resolved | 2006-07-01 |
| MR | Monitoring | Resolved | 2006-03-01 → 2006-03-31 |
| MR | Monitoring | Resolved | 2006-03-01 → 2006-03-31 |
| MR | Monitoring | Resolved | 2006-03-01 → 2006-03-31 |
| MR | Monitoring | Resolved | 2006-03-01 → 2006-03-31 |
PFAS detected
Other contaminants detected
| Contaminant | Level vs EPA limit | Detection rate | Source | Period |
|---|---|---|---|---|
| Copper | 262.15 µg/L 20% of the EPA limit 1300 µg/L
worst single sample: 419 µg/L | 58/64 | SYR4 | 2013–2017 |
| Nitrate | 1015 µg/L 10% of the EPA limit 10000 µg/L
worst single sample: 1070 µg/L | 32/38 | SYR4 | 2012–2019 |
| Lead | 24.6 µg/L 164% of the EPA limit, at the 95th percentile of samples — 15 µg/L
worst single sample: 29 µg/L | 23/64 | SYR4 | 2013–2017 |
| Chloroform | 15.53 µg/L No EPA limit set
worst single sample: 15.7 µg/L | 18/23 | SYR4 | 2012–2019 |
| Arsenic | 10.38 µg/L 104% of the EPA limit, at the 95th percentile of samples — 10 µg/L
worst single sample: 12.2 µg/L | 14/16 | SYR4 | 2014–2017 |
| Bromodichloromethane | 2.44 µg/L No EPA limit set
worst single sample: 2.7 µg/L | 14/23 | SYR4 | 2012–2019 |
| Dichloroacetic Acid | 28.82 µg/L No EPA limit set
worst single sample: 34.4 µg/L | 13/13 | SYR4 | 2012–2019 |
| TTHM | 17.62 µg/L 22% of the EPA limit 80 µg/L
worst single sample: 17.8 µg/L | 13/13 | SYR4 | 2012–2019 |
| Total Haloacetic Acids (HAA5) | 34.48 µg/L 57% of the EPA limit 60 µg/L
worst single sample: 38.5 µg/L | 13/13 | SYR4 | 2012–2019 |
| Atrazine | 0.8570 µg/L 29% of the EPA limit 3 µg/L
worst single sample: 1 µg/L | 12/15 | SYR4 | 2012–2019 |
| Lead | 0.0 mg/L 0% of the EPA limit 0.0150 mg/L | 12/12 | LCR | 2023 |
| Trichloroacetic Acid | 3.935 µg/L No EPA limit set
worst single sample: 4.1 µg/L | 12/13 | SYR4 | 2012–2019 |
| Nitrate-Nitrite | 834 µg/L 8.3% of the EPA limit 10000 µg/L
worst single sample: 990 µg/L | 7/7 | SYR4 | 2012–2017 |
| Monochloroacetic Acid | 7.1 µg/L No EPA limit set
worst single sample: 8.1 µg/L | 5/13 | SYR4 | 2012–2019 |
| Barium | 391.8 µg/L 20% of the EPA limit 2000 µg/L
worst single sample: 417 µg/L | 4/4 | SYR4 | 2014–2017 |
| Nitrite | 28.5 µg/L 2.9% of the EPA limit 1000 µg/L
worst single sample: 30 µg/L | 4/7 | SYR4 | 2012–2017 |
| Bromoform | 9.22 µg/L No EPA limit set
worst single sample: 10 µg/L | 3/23 | SYR4 | 2012–2019 |
| Fluoride | 973 µg/L 24% of the EPA limit 4000 µg/L
worst single sample: 1040 µg/L | 3/4 | SYR4 | 2014–2017 |
| Simazine | 0.2460 µg/L 6.2% of the EPA limit 4 µg/L
worst single sample: 0.2600 µg/L | 3/15 | SYR4 | 2012–2019 |
| Benzene | 0.8800 µg/L 18% of the EPA limit 5 µg/L
worst single sample: 0.9000 µg/L | 2/10 | SYR4 | 2012–2018 |
| Cyanide | 143 µg/L 72% of the EPA limit 200 µg/L
worst single sample: 150 µg/L | 2/4 | SYR4 | 2014–2017 |
| Dibromochloromethane | 4.495 µg/L No EPA limit set
worst single sample: 4.7 µg/L | 2/23 | SYR4 | 2012–2019 |
| Combined Radium (-226 And -228) | 3 pCi/L 60% of the EPA limit 5 pCi/L | 1/1 | SYR4 | 2014 |
| Di(2-ethylhexyl) Phthalate | 0.8600 µg/L 14% of the EPA limit 6 µg/L | 1/15 | SYR4 | 2012–2019 |
| Gross Alpha, Excl. Radon And U | 3 pCi/L 20% of the EPA limit 15 pCi/L | 1/2 | SYR4 | 2014–2017 |
| Toluene | 0.8000 µg/L 0.1% of the EPA limit 1000 µg/L | 1/10 | SYR4 | 2012–2018 |
| Xylenes, Total | 0.5000 µg/L 0% of the EPA limit 10000 µg/L | 1/10 | SYR4 | 2012–2018 |
| Lithium | 23.8 µg/L No EPA limit set | 1/8 | UCMR-5 | 2025 |
78 contaminants tested, none detected
Utility contact
Frequently asked questions about Harris County Mud 368
Is Harris County Mud 368 tap water safe to drink?
EPA monitoring detected 31 contaminants in Harris County Mud 368's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.
What contaminants were detected in Harris County Mud 368's water?
EPA monitoring detected Copper, Nitrate, Lead, Chloroform, Arsenic, and others. The full list with the level and data source for each is above.
How many people does Harris County Mud 368 serve?
Harris County Mud 368 reports serving 11,835 people in Texas, per its EPA record.
Has Harris County Mud 368 had any water quality violations?
The EPA has 6 violations on file for Harris County Mud 368, of which 0 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.
Where does this data come from?
Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.