Compliance record
Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.
| Violation | Type | Status | Period |
|---|---|---|---|
| Other | Monitoring | Unaddressed | 2025-07-01 |
| MR | Monitoring | Resolved | 2016-10-01 |
| MR | Monitoring | Resolved | 2016-10-01 |
| MR | Monitoring | Resolved | 2016-10-01 |
| MR | Monitoring | Resolved | 2016-10-01 |
| Other | Monitoring | Resolved | 2015-07-01 |
| Other | Monitoring | Resolved | 2015-07-01 |
| MR | Monitoring | Resolved | 2013-12-30 |
| MR | Monitoring | Resolved | 1992-07-01 → 1993-06-30 |
PFAS detected
Other contaminants detected
| Contaminant | Level vs EPA limit | Detection rate | Source | Period |
|---|---|---|---|---|
| Bromodichloromethane | 22.4 µg/L No EPA limit set | 133/138 | SYR4 | 2012–2019 |
| Chloroform | 36.8 µg/L No EPA limit set | 133/138 | SYR4 | 2012–2019 |
| Dichloroacetic Acid | 47.1 µg/L No EPA limit set | 123/128 | SYR4 | 2012–2019 |
| TTHM | 67.8 µg/L 85% of the EPA limit 80 µg/L | 123/128 | SYR4 | 2012–2019 |
| Total Haloacetic Acids (HAA5) | 67.3 µg/L 112% of the EPA limit, in the worst sample — 60 µg/L | 123/128 | SYR4 | 2012–2019 |
| Trichloroacetic Acid | 13.7 µg/L No EPA limit set | 119/128 | SYR4 | 2012–2019 |
| Dibromochloromethane | 8.6 µg/L No EPA limit set | 106/138 | SYR4 | 2012–2019 |
| Copper | 331 µg/L 25% of the EPA limit 1300 µg/L | 74/93 | SYR4 | 2013–2017 |
| Dibromoacetic Acid | 3 µg/L No EPA limit set | 63/128 | SYR4 | 2012–2019 |
| Nitrate | 600 µg/L 6% of the EPA limit 10000 µg/L | 32/32 | SYR4 | 2012–2019 |
| Lead | 9.4 µg/L 63% of the EPA limit 15 µg/L | 31/93 | SYR4 | 2013–2017 |
| Atrazine | 0.8300 µg/L 28% of the EPA limit 3 µg/L | 27/35 | SYR4 | 2012–2019 |
| Monochloroacetic Acid | 9.1 µg/L No EPA limit set | 22/128 | SYR4 | 2012–2019 |
| Simazine | 0.1900 µg/L 4.8% of the EPA limit 4 µg/L | 20/35 | SYR4 | 2012–2019 |
| Lead | 0.0 mg/L 0% of the EPA limit 0.0150 mg/L | 15/15 | LCR | 2023 |
| Nitrate-Nitrite | 430 µg/L 4.3% of the EPA limit 10000 µg/L | 6/6 | SYR4 | 2012–2015 |
| Bromoform | 1.4 µg/L No EPA limit set | 5/138 | SYR4 | 2012–2019 |
| Barium | 138 µg/L 6.9% of the EPA limit 2000 µg/L | 4/4 | SYR4 | 2014–2017 |
| Fluoride | 780 µg/L 20% of the EPA limit 4000 µg/L | 4/4 | SYR4 | 2014–2017 |
| Arsenic | 10 µg/L 100% of the EPA limit 10 µg/L | 2/12 | SYR4 | 2014–2017 |
| Cyanide | 150 µg/L 75% of the EPA limit 200 µg/L | 2/4 | SYR4 | 2014–2017 |
| Gross Beta Particle Activity | 5.5 pCi/L No EPA limit set | 2/2 | SYR4 | 2017 |
| Hexachlorocyclopentadiene | 0.1200 µg/L 0.2% of the EPA limit 50 µg/L | 2/35 | SYR4 | 2012–2019 |
| Nitrite | 20 µg/L 2% of the EPA limit 1000 µg/L | 2/6 | SYR4 | 2012–2015 |
| Benzo(A)Pyrene | 0.4000 µg/L 200% of the EPA limit, in the worst sample — 0.2000 µg/L | 1/35 | SYR4 | 2012–2019 |
| Di(2-ethylhexyl) Phthalate | 0.7400 µg/L 12% of the EPA limit 6 µg/L | 1/35 | SYR4 | 2012–2019 |
77 contaminants tested, none detected
Utility contact
Frequently asked questions about Harris County Mud 53
Is Harris County Mud 53 tap water safe to drink?
EPA monitoring detected 31 contaminants in Harris County Mud 53's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.
What contaminants were detected in Harris County Mud 53's water?
EPA monitoring detected Bromodichloromethane, Chloroform, Dichloroacetic Acid, TTHM, Total Haloacetic Acids (HAA5), and others. The full list with the level and data source for each is above.
How many people does Harris County Mud 53 serve?
Harris County Mud 53 reports serving 17,856 people in Texas, per its EPA record.
Has Harris County Mud 53 had any water quality violations?
The EPA has 9 violations on file for Harris County Mud 53, of which 0 are health-based (a contaminant limit or required treatment was breached) and 1 remain open. The rest are monitoring or reporting failures.
Where does this data come from?
Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.