Compliance record
Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.
| Violation | Type | Status | Period |
|---|---|---|---|
| MCL | Health-based | Resolved | 2006-04-01 → 2006-04-30 |
| MCL | Health-based | Resolved | 2006-04-01 → 2006-04-30 |
| MCL | Health-based | Resolved | 2006-04-01 → 2006-04-30 |
| MCL | Health-based | Resolved | 2006-04-01 → 2006-04-30 |
| MR | Monitoring | Resolved | 2025-10-01 |
| MR | Monitoring | Resolved | 2025-10-01 |
| MR | Monitoring | Resolved | 2025-10-01 |
PFAS detected
Other contaminants detected
| Contaminant | Level vs EPA limit | Detection rate | Source | Period |
|---|---|---|---|---|
| Copper | 508 µg/L 39% of the EPA limit 1300 µg/L | 81/82 | SYR4 | 2012–2019 |
| Chloroform | 22.4 µg/L No EPA limit set | 65/67 | SYR4 | 2012–2019 |
| Dichloroacetic Acid | 24.3 µg/L No EPA limit set | 61/62 | SYR4 | 2012–2019 |
| Total Haloacetic Acids (HAA5) | 39.3 µg/L 65% of the EPA limit 60 µg/L | 61/62 | SYR4 | 2012–2019 |
| TTHM | 25.6 µg/L 32% of the EPA limit 80 µg/L | 60/62 | SYR4 | 2012–2019 |
| Bromodichloromethane | 3.9 µg/L No EPA limit set | 57/67 | SYR4 | 2012–2019 |
| Trichloroacetic Acid | 4.1 µg/L No EPA limit set | 54/62 | SYR4 | 2012–2019 |
| Lead | 24.1 µg/L 161% of the EPA limit, in the worst sample — 15 µg/L | 33/82 | SYR4 | 2012–2019 |
| Nitrate | 1830 µg/L 18% of the EPA limit 10000 µg/L | 28/32 | SYR4 | 2012–2019 |
| Cyanide | 210 µg/L 105% of the EPA limit, in the worst sample — 200 µg/L | 15/24 | SYR4 | 2014–2019 |
| Lead | 0.0046 mg/L 30% of the EPA limit 0.0150 mg/L | 13/13 | LCR | 2026 |
| Monochloroacetic Acid | 12.7 µg/L No EPA limit set | 13/62 | SYR4 | 2012–2019 |
| Dibromoacetic Acid | 2 µg/L No EPA limit set | 6/62 | SYR4 | 2012–2019 |
| Dibromochloromethane | 5.7 µg/L No EPA limit set | 6/67 | SYR4 | 2012–2019 |
| Nitrate-Nitrite | 1850 µg/L 19% of the EPA limit 10000 µg/L | 6/7 | SYR4 | 2012–2019 |
| Nitrite | 90 µg/L 9% of the EPA limit 1000 µg/L | 5/7 | SYR4 | 2012–2019 |
| Bromoform | 8.9 µg/L No EPA limit set | 4/67 | SYR4 | 2012–2019 |
| Barium | 84.8 µg/L 4.2% of the EPA limit 2000 µg/L | 3/3 | SYR4 | 2013–2019 |
| Fluoride | 490 µg/L 12% of the EPA limit 4000 µg/L | 2/3 | SYR4 | 2012–2018 |
| Gross Beta Particle Activity | 5.3 pCi/L No EPA limit set | 2/2 | SYR4 | 2013–2019 |
| Atrazine | 0.2600 µg/L 8.7% of the EPA limit 3 µg/L | 1/2 | SYR4 | 2015–2018 |
| Combined Radium (-226 And -228) | 1 pCi/L 20% of the EPA limit 5 pCi/L | 1/1 | SYR4 | 2013 |
| Simazine | 0.1700 µg/L 4.3% of the EPA limit 4 µg/L | 1/2 | SYR4 | 2015–2018 |
83 contaminants tested, none detected
Utility contact
Frequently asked questions about Harris County Wcid 132
Is Harris County Wcid 132 tap water safe to drink?
EPA monitoring detected 26 contaminants in Harris County Wcid 132's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.
What contaminants were detected in Harris County Wcid 132's water?
EPA monitoring detected Copper, Chloroform, Dichloroacetic Acid, Total Haloacetic Acids (HAA5), TTHM, and others. The full list with the level and data source for each is above.
How many people does Harris County Wcid 132 serve?
Harris County Wcid 132 reports serving 3,501 people in Texas, per its EPA record.
Has Harris County Wcid 132 had any water quality violations?
The EPA has 7 violations on file for Harris County Wcid 132, of which 4 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.
Where does this data come from?
Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.