Compliance record
Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.
| Violation | Type | Status | Period |
|---|---|---|---|
| TT | Health-based | Resolved | 2025-10-01 → 2025-10-31 |
| TT | Health-based | Resolved | 2025-10-01 → 2025-10-31 |
| TT | Health-based | Resolved | 2025-10-01 → 2025-10-31 |
| TT | Health-based | Resolved | 2025-10-01 → 2025-10-31 |
| MCL | Health-based | Resolved | 2005-01-01 → 2005-03-31 |
| MCL | Health-based | Resolved | 2005-01-01 → 2005-03-31 |
| MCL | Health-based | Resolved | 2005-01-01 → 2005-03-31 |
| MCL | Health-based | Resolved | 2005-01-01 → 2005-03-31 |
| MCL | Health-based | Resolved | 2005-01-01 → 2005-03-31 |
| MCL | Health-based | Resolved | 2005-01-01 → 2005-03-31 |
Other contaminants detected
| Contaminant | Level vs EPA limit | Detection rate | Source | Period |
|---|---|---|---|---|
| Chloroform | 23.175 µg/L No EPA limit set
worst single sample: 29.9 µg/L | 54/60 | SYR4 | 2012–2019 |
| Bromodichloromethane | 6.49 µg/L No EPA limit set
worst single sample: 10.1 µg/L | 52/60 | SYR4 | 2012–2019 |
| TTHM | 27.725 µg/L 35% of the EPA limit 80 µg/L
worst single sample: 42.3 µg/L | 46/52 | SYR4 | 2012–2019 |
| Dichloroacetic Acid | 27.46 µg/L No EPA limit set
worst single sample: 28.9 µg/L | 44/52 | SYR4 | 2012–2019 |
| Total Haloacetic Acids (HAA5) | 37.115 µg/L 62% of the EPA limit 60 µg/L
worst single sample: 52.5 µg/L | 44/52 | SYR4 | 2012–2019 |
| Trichloroacetic Acid | 8.37 µg/L No EPA limit set
worst single sample: 17.3 µg/L | 44/52 | SYR4 | 2012–2019 |
| Copper | 391.4 µg/L 30% of the EPA limit 1300 µg/L
worst single sample: 451 µg/L | 37/45 | SYR4 | 2013–2019 |
| Nitrate | 1660 µg/L 17% of the EPA limit 10000 µg/L | 16/18 | SYR4 | 2012–2019 |
| Lead | 0.00084 mg/L 5.6% of the EPA limit 0.0150 mg/L | 15/15 | LCR | 2026 |
| Lead | 4.3445 µg/L 29% of the EPA limit 15 µg/L
worst single sample: 6.34 µg/L | 14/45 | SYR4 | 2013–2019 |
| Monochloroacetic Acid | 7.7 µg/L No EPA limit set
worst single sample: 8 µg/L | 13/52 | SYR4 | 2012–2019 |
| Dibromochloromethane | 2.055 µg/L No EPA limit set
worst single sample: 2.3 µg/L | 8/60 | SYR4 | 2012–2019 |
| Fluoride | 496.5 µg/L 12% of the EPA limit 4000 µg/L
worst single sample: 500 µg/L | 8/8 | SYR4 | 2012–2019 |
| Barium | 105.4 µg/L 5.3% of the EPA limit 2000 µg/L
worst single sample: 106 µg/L | 7/7 | SYR4 | 2013–2019 |
| Dibromoacetic Acid | 1.34 µg/L No EPA limit set
worst single sample: 1.4 µg/L | 7/52 | SYR4 | 2012–2019 |
| Cyanide | 112.5 µg/L 56% of the EPA limit 200 µg/L
worst single sample: 120 µg/L | 4/6 | SYR4 | 2014–2019 |
| Atrazine | 0.3120 µg/L 10% of the EPA limit 3 µg/L
worst single sample: 0.3200 µg/L | 3/8 | SYR4 | 2012–2019 |
| Simazine | 0.2065 µg/L 5.2% of the EPA limit 4 µg/L
worst single sample: 0.2100 µg/L | 2/8 | SYR4 | 2012–2019 |
| Arsenic | 2.6 µg/L 26% of the EPA limit 10 µg/L | 1/7 | SYR4 | 2013–2019 |
| Combined Radium (-226 And -228) | 1.5 pCi/L 30% of the EPA limit 5 pCi/L | 1/1 | SYR4 | 2016 |
| Nitrate-Nitrite | 590 µg/L 5.9% of the EPA limit 10000 µg/L | 1/1 | SYR4 | 2013 |
58 contaminants tested, none detected
Utility contact
Frequently asked questions about Crosby Mud
Is Crosby Mud tap water safe to drink?
EPA monitoring detected 21 contaminants in Crosby Mud's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.
What contaminants were detected in Crosby Mud's water?
EPA monitoring detected Chloroform, Bromodichloromethane, TTHM, Dichloroacetic Acid, Total Haloacetic Acids (HAA5), and others. The full list with the level and data source for each is above.
How many people does Crosby Mud serve?
Crosby Mud reports serving 5,130 people in Texas, per its EPA record.
Has Crosby Mud had any water quality violations?
The EPA has 59 violations on file for Crosby Mud, of which 38 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.
Where does this data come from?
Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.