| Violation | Type | Status | Period |
|---|---|---|---|
| MCL | Health-based | Archived | 2005-04-01 → 2005-04-30 |
| MCL | Health-based | Archived | 2005-04-01 → 2005-04-30 |
| MCL | Health-based | Archived | 1983-04-26 → 1984-04-25 |
| MCL | Health-based | Archived | 1980-06-16 → 1981-06-15 |
| MCL | Health-based | Archived | 1980-06-16 → 1980-07-15 |
| MR | Monitoring | Resolved | 2015-12-30 |
| MR | Monitoring | Resolved | 2015-12-30 |
| MR | Monitoring | Resolved | 2007-01-01 → 2007-03-31 |
| MR | Monitoring | Resolved | 2007-01-01 → 2007-03-31 |
| MR | Monitoring | Resolved | 2007-01-01 → 2007-03-31 |
Other contaminants detected
| Contaminant | Level vs EPA limit | Detection rate | Source | Period |
|---|---|---|---|---|
| Nitrate | 66.25 µg/L 0.7% of the EPA limit 10000 µg/L
worst single sample: 170 µg/L | 64/64 | SYR4 | 2012–2019 |
| Copper | 140 µg/L 11% of the EPA limit 1300 µg/L
worst single sample: 250 µg/L | 54/54 | SYR4 | 2015–2018 |
| Bromoform | 9.36 µg/L No EPA limit set
worst single sample: 10.9 µg/L | 33/34 | SYR4 | 2012–2019 |
| Dibromochloromethane | 3.884 µg/L No EPA limit set
worst single sample: 4.81 µg/L | 25/34 | SYR4 | 2012–2019 |
| Nitrate-Nitrite | 52.1 µg/L 0.5% of the EPA limit 10000 µg/L
worst single sample: 56.5 µg/L | 12/12 | SYR4 | 2012–2015 |
| TTHM | 14.435 µg/L 18% of the EPA limit 80 µg/L
worst single sample: 16.1 µg/L | 10/11 | SYR4 | 2013–2019 |
| Fluoride | 1910 µg/L 48% of the EPA limit 4000 µg/L
worst single sample: 1970 µg/L | 9/9 | SYR4 | 2013–2019 |
| Barium | 26.65 µg/L 1.3% of the EPA limit 2000 µg/L
worst single sample: 27 µg/L | 8/8 | SYR4 | 2015–2018 |
| Lead | 11.795 µg/L 79% of the EPA limit 15 µg/L
worst single sample: 14 µg/L | 8/54 | SYR4 | 2015–2018 |
| Lead | 0.0 mg/L 0% of the EPA limit 0.0150 mg/L | 7/7 | LCR | 2024 |
| Chromium | 4.075 µg/L 4.1% of the EPA limit 100 µg/L
worst single sample: 4.1 µg/L | 6/8 | SYR4 | 2015–2018 |
| Total Haloacetic Acids (HAA5) | 1.3 µg/L 2.2% of the EPA limit 60 µg/L | 5/10 | SYR4 | 2013–2019 |
| Arsenic | 2.555 µg/L 26% of the EPA limit 10 µg/L
worst single sample: 2.6 µg/L | 4/8 | SYR4 | 2015–2018 |
| Dibromoacetic Acid | 1.3 µg/L No EPA limit set | 4/10 | SYR4 | 2013–2019 |
| Gross Alpha, Excl. Radon And U | 7.62 pCi/L 51% of the EPA limit 15 pCi/L
worst single sample: 7.9 pCi/L | 3/4 | SYR4 | 2015 |
| Bromodichloromethane | 1.0975 µg/L No EPA limit set
worst single sample: 1.1 µg/L | 2/34 | SYR4 | 2012–2019 |
| Combined Radium (-226 And -228) | 0.6570 pCi/L 13% of the EPA limit 5 pCi/L
worst single sample: 0.6600 pCi/L | 2/3 | SYR4 | 2015 |
| Carbon Tetrachloride | 2.83 µg/L 57% of the EPA limit 5 µg/L | 1/24 | SYR4 | 2012–2019 |
| Monochloroacetic Acid | 1.2 µg/L No EPA limit set | 1/10 | SYR4 | 2013–2019 |
| Selenium | 1.3 µg/L 2.6% of the EPA limit 50 µg/L | 1/8 | SYR4 | 2015–2018 |
59 contaminants tested, none detected
Utility contact
Frequently asked questions about Starr Wsc
Is Starr Wsc tap water safe to drink?
EPA monitoring detected 20 contaminants in Starr Wsc's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.
What contaminants were detected in Starr Wsc's water?
EPA monitoring detected Nitrate, Copper, Bromoform, Dibromochloromethane, Nitrate-Nitrite, and others. The full list with the level and data source for each is above.
How many people does Starr Wsc serve?
Starr Wsc reports serving 3,100 people in Texas, per its EPA record.
Has Starr Wsc had any water quality violations?
The EPA has 59 violations on file for Starr Wsc, of which 5 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.
Where does this data come from?
Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.