← Texas

Tap water quality report

Cypress Springs Sud South Plant

EPA monitoring tested this supplier for 78 contaminants and detected 25. A detection doesn't automatically mean the water is unsafe — the level and EPA source for each is below.

78
contaminants tested
25
detected
1,821
people served
46
health-based violations
Water source
Surface water
Ownership
Local government
Counties served
Franklin

Compliance record

Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.

46
health-based violations
65
violations on file
1
still open
ViolationTypeStatusPeriod
MCL Health-based Resolved 2009-07-01 → 2009-09-30
MCL Health-based Resolved 2009-07-01 → 2009-09-30
MCL Health-based Resolved 2009-07-01 → 2009-09-30
MCL Health-based Resolved 2009-04-01 → 2009-06-30
MCL Health-based Resolved 2009-04-01 → 2009-06-30
MCL Health-based Resolved 2009-04-01 → 2009-06-30
MCL Health-based Resolved 2009-04-01 → 2009-06-30
MCL Health-based Resolved 2009-04-01 → 2009-06-30
MCL Health-based Resolved 2009-01-01 → 2009-03-31
MCL Health-based Resolved 2009-01-01 → 2009-03-31

Other contaminants detected

Each bar shows the measured level as a share of the EPA limit: green is well under, amber is close to it, red is over. For lead and copper the limit applies to exactly the 90th-percentile figure shown, so red there means a real exceedance. For everything else the limit applies to a running annual average while the figure is the 95th percentile of this system's samples — over 100% is worth reading, but is not by itself a violation. Where a single sample came in higher than that percentile, it is noted under the bar. Formal violations are listed separately.
ContaminantLevel vs EPA limitDetection rateSourcePeriod
Bromodichloromethane
20.4 µg/L
No EPA limit set
worst single sample: 23.4 µg/L
40/40 SYR4 2012–2019
Chloroform
74.895 µg/L
No EPA limit set
worst single sample: 151 µg/L
40/40 SYR4 2012–2019
Dibromochloromethane
7.055 µg/L
No EPA limit set
worst single sample: 10.1 µg/L
38/40 SYR4 2012–2019
TTHM
95.31 µg/L 119%
of the EPA limit, at the 95th percentile of samples — 80 µg/L
worst single sample: 114.8 µg/L
32/33 SYR4 2012–2019
Total Haloacetic Acids (HAA5)
50.515 µg/L 84%
of the EPA limit 60 µg/L
worst single sample: 53.3 µg/L
32/32 SYR4 2012–2019
Trichloroacetic Acid
12.18 µg/L
No EPA limit set
worst single sample: 13.7 µg/L
32/32 SYR4 2012–2019
Dichloroacetic Acid
35.05 µg/L
No EPA limit set
worst single sample: 37.8 µg/L
31/32 SYR4 2012–2019
Monochloroacetic Acid
5.3 µg/L
No EPA limit set
worst single sample: 5.7 µg/L
21/32 SYR4 2012–2019
Copper
24.1 µg/L 1.9%
of the EPA limit 1300 µg/L
worst single sample: 29 µg/L
15/25 SYR4 2013–2019
Dibromoacetic Acid
3.345 µg/L
No EPA limit set
worst single sample: 3.4 µg/L
12/32 SYR4 2012–2019
Nitrate
190 µg/L 1.9%
of the EPA limit 10000 µg/L
12/18 SYR4 2012–2019
Fluoride
226.15 µg/L 5.7%
of the EPA limit 4000 µg/L
worst single sample: 279 µg/L
8/8 SYR4 2012–2019
Barium
50.77 µg/L 2.5%
of the EPA limit 2000 µg/L
worst single sample: 51.1 µg/L
7/7 SYR4 2013–2019
Monobromoacetic Acid
2.375 µg/L
No EPA limit set
worst single sample: 2.5 µg/L
6/32 SYR4 2012–2019
Bromoform
22.67 µg/L
No EPA limit set
worst single sample: 27.9 µg/L
5/40 SYR4 2012–2019
Cyanide
70.98 µg/L 35%
of the EPA limit 200 µg/L
worst single sample: 76.8 µg/L
4/6 SYR4 2014–2019
Arsenic
1.425 µg/L 14%
of the EPA limit 10 µg/L
worst single sample: 1.45 µg/L
3/7 SYR4 2013–2019
Lead
0.0 mg/L 0%
of the EPA limit 0.0150 mg/L
3/3 LCR 2025
Di(2-ethylhexyl) Phthalate
0.5000 µg/L 8.3%
of the EPA limit 6 µg/L
2/11 SYR4 2012–2019
Asbestos
0.1987 MFL 2.8%
of the EPA limit 7 MFL
1/1 SYR4 2013
Chromium
0.4900 µg/L 0.5%
of the EPA limit 100 µg/L
1/7 SYR4 2013–2019
Combined Radium (-226 And -228)
1.5 pCi/L 30%
of the EPA limit 5 pCi/L
1/1 SYR4 2015
Gross Beta Particle Activity
7.1 pCi/L
No EPA limit set
1/1 SYR4 2015
Nitrite
8 µg/L 0.8%
of the EPA limit 1000 µg/L
1/1 SYR4 2013
Selenium
2 µg/L 4%
of the EPA limit 50 µg/L
1/7 SYR4 2013–2019
53 contaminants tested, none detected
1,1,1-Trichloroethane1,1,2-Trichloroethane1,1-Dichloroethylene1,2,4-Trichlorobenzene1,2-DIBROMO-3-CHLOROPROPANE1,2-Dichloroethane1,2-Dichloropropane2,4,5-TP2,4-DAntimony, TotalAtrazineBhc-GammaBenzeneBenzo(A)PyreneBeryllium, TotalChlorobenzeneCadmiumCarbofuranCarbon TetrachlorideChlordaneCombined UraniumDichloromethaneDalaponDi(2-ethylhexyl) AdipateDinosebEthylene DibromideEndrinEthylbenzeneGross Alpha, Excl. Radon And UHexachlorobenzeneHeptachlorHeptachlor EpoxideHexachlorocyclopentadieneLassoLeadMercuryMethoxychlorOxamylPentachlorophenolPicloramSimazineStyreneTetrachloroethyleneThallium, TotalTolueneToxapheneTrichloroethyleneVinyl ChlorideXylenes, Totalcis-1,2-DichloroethyleneO-DichlorobenzeneP-Dichlorobenzenetrans-1,2-Dichloroethylene

Utility contact

Contact
DANIELS, LARRY
Phone
903-508-0981

Frequently asked questions about Cypress Springs Sud South Plant

Is Cypress Springs Sud South Plant tap water safe to drink?

EPA monitoring detected 25 contaminants in Cypress Springs Sud South Plant's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.

What contaminants were detected in Cypress Springs Sud South Plant's water?

EPA monitoring detected Bromodichloromethane, Chloroform, Dibromochloromethane, TTHM, Total Haloacetic Acids (HAA5), and others. The full list with the level and data source for each is above.

How many people does Cypress Springs Sud South Plant serve?

Cypress Springs Sud South Plant reports serving 1,821 people in Texas, per its EPA record.

Has Cypress Springs Sud South Plant had any water quality violations?

The EPA has 65 violations on file for Cypress Springs Sud South Plant, of which 46 are health-based (a contaminant limit or required treatment was breached) and 1 remain open. The rest are monitoring or reporting failures.

Where does this data come from?

Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.